1SDA055804R1 ABB E2B 1600 PR122/P-LSI 1600 A 4-Pole Air Circuit Breaker

1SDA055804R1 ABB E2B 1600 PR122/P-LSI 1600 A 4-Pole Air Circuit Breaker

ABB 1SDA055804R1 SACE Emax E2B 1600 is a 1600 A four-pole fixed air circuit breaker with a PR122/P-LSI electronic release, rear horizontal terminals and 42 kA short-circuit breaking capacity at 415 V AC.

SKU: 1SDA055804R1MPN: 1SDA055804R1
Price
List Price £14,247.96 ex VAT
Your Price (ex VAT) Save 25%
£10,685.97 25% OFF
You save £3,561.99 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £10,685.97
Trade pricing is personalised to your account

Manufacturer Lead Time

£10,685.97

Why Choose the ABB 1SDA055804R1 E2B 1600 Air Circuit Breaker?

The ABB 1SDA055804R1 is a high-performance SACE Emax E2B 1600 air circuit breaker designed for switching and overcurrent protection in low-voltage AC power distribution systems. This four-pole fixed circuit breaker has a rated current of 1600 A and is equipped with an electronic PR122/P-LSI R1600 overcurrent release providing long-time, short-time and instantaneous protection.

Part of the proven ABB SACE Emax range, the E2B 1600 combines high-current switching capability with configurable electronic protection for industrial switchboards and power distribution assemblies. Its B performance level provides rated ultimate and service short-circuit breaking capacities of 42 kA at 415 V AC, with the same 42 kA rating specified across the breaker’s 220–690 V AC operating range.

The 1SDA055804R1 is a four-pole fixed (F) circuit breaker with rear flat horizontal terminals. It has a rated operational voltage of 690 V AC, rated insulation voltage of 1000 V and rated impulse withstand voltage of 12 kV. Four auxiliary contacts and circuit-breaker open/closed position indication are included for integration with switchboard signalling and monitoring systems.

Key Advantages

  • Heavy-duty 1600 A air circuit breaker for low-voltage power distribution.
  • PR122/P-LSI electronic overcurrent release provides long-time, short-time and instantaneous protection.
  • 42 kA rated ultimate and service short-circuit breaking capacity at 415 V AC.
  • Four-pole configuration supports switching and protection in three-phase systems with neutral.
  • Fixed installation provides robust permanent integration into low-voltage switchboards.
  • Rear flat horizontal terminals support practical busbar and conductor connections.
  • Four auxiliary contacts and open/closed position indication support breaker status monitoring.

Key Features

  • ABB SACE Emax E2B 1600 air circuit breaker.
  • 1600 A rated current.
  • 4-pole configuration.
  • PR122/P-LSI R1600 electronic release.
  • LSI protection provides long-time, short-time and instantaneous overcurrent protection.
  • Fixed (F) circuit-breaker version.
  • Rear flat horizontal terminals.
  • 690 V AC rated operational voltage.
  • 42 kA rated ultimate short-circuit breaking capacity at 415 V AC.
  • 42 kA rated service short-circuit breaking capacity at 415 V AC.
  • 42 kA rated short-time withstand current for 1 s and 3 s.
  • Four auxiliary contacts with circuit-breaker open/closed position indication.

Reliable LSI Protection for High-Current Power Distribution

Air circuit breakers such as the ABB SACE Emax E2B 1600 provide switching and overcurrent protection for high-current low-voltage distribution circuits. The PR122/P-LSI electronic release provides long-time protection against sustained overloads, short-time protection for selective fault coordination and instantaneous protection against severe short-circuit currents.

The combination of 1600 A current capacity, four-pole construction, fixed mounting and 42 kA short-circuit performance at 415 V AC makes the 1SDA055804R1 well suited to main incoming and high-current feeder applications. Its rear horizontal terminals and auxiliary signalling contacts also support effective integration into industrial switchboards and power distribution assemblies.

Typical Applications

  • Industrial low-voltage distribution switchboards.
  • Main incoming circuit protection.
  • Four-pole power distribution systems.
  • High-current feeder protection.
  • Power distribution centres and switchgear assemblies.
  • Manufacturing and process plants.
  • Commercial and infrastructure electrical distribution.
  • OEM switchboards requiring selective LSI electronic protection.

Technical Specifications

Series SACE Emax
ABB order code 1SDA055804R1
Product type Air circuit breaker
Frame / sub-type E2
Performance level B
Rated current (In) 1600 A
Rated uninterrupted current (Iu) 1600 A
Rated operational current (Ie) 1600 A
Number of poles 4
Current type AC
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC 42 kA
Rated service short-circuit breaking capacity (Ics) at 415 V AC 42 kA
Rated short-time withstand current (Icw) 42 kA for 1 s
Release PR122/P-LSI R1600
Release type Electronic
Protection functions LSI – long-time, short-time and instantaneous
Long-time protection (L) Overload protection
Short-time protection (S) Selective short-circuit protection
Instantaneous protection (I) Instantaneous short-circuit protection
Installation Fixed
Terminal connection Rear flat horizontal
Auxiliary contacts 4
Position indication Circuit breaker open / closed
Power loss 115 W
Mechanical durability 25,000 cycles
Electrical durability at ≤440 V 12,000 cycles
Electrical durability at 500–690 V 10,000 cycles
Standard IEC
Weight 68 kg
EAN 8015644571443

Frequently Asked Questions

What is the ABB 1SDA055804R1 used for?

The ABB 1SDA055804R1 is a 1600 A four-pole air circuit breaker designed for switching and overcurrent protection in industrial, commercial and infrastructure low-voltage power distribution systems.

What protection release is fitted to the ABB 1SDA055804R1?

The breaker is fitted with a PR122/P-LSI R1600 electronic release providing long-time, short-time and instantaneous overcurrent protection.

What does LSI protection mean on the PR122/P release?

LSI denotes long-time, short-time and instantaneous protection, providing protection against sustained overloads and different levels of short-circuit current while supporting selective fault coordination.

Is the ABB 1SDA055804R1 fixed or withdrawable?

The 1SDA055804R1 is a fixed four-pole circuit breaker with rear flat horizontal terminals for permanent installation within a low-voltage switchboard.

What is the short-circuit rating of the ABB E2B 1600?

The E2B 1600 has rated ultimate and service short-circuit breaking capacities of 42 kA at 415 V AC and a rated short-time withstand current of 42 kA for both 1 s and 3 s.

Trusted ABB Protection for Critical Distribution Systems

ABB SACE Emax air circuit breakers provide robust switching and electronic protection for low-voltage power distribution, combining high current capability, configurable protection and dependable short-circuit performance for demanding industrial switchboards and infrastructure.