ABB 1SDA055799R1 E2B1600 three-pole fixed air circuit breaker rated at 1600 A with rear horizontal terminals and a PR123/P-LSIG R1600 electronic release providing long-time, short-time, instantaneous and ground-fault protection.
£14,532.38
The ABB E2B1600 PR123/P-LSIG, order code 1SDA055799R1, is a three-pole fixed air circuit breaker (ACB) designed for switching and protection in low-voltage power distribution systems. Part of the ABB SACE Emax E2 series, it combines a rated uninterrupted current of 1600 A with the advanced PR123/P-LSIG R1600 electronic overcurrent release.
The PR123/P-LSIG trip unit provides long-time, short-time, instantaneous and ground-fault protection. These LSIG functions help protect conductors, switchgear and connected equipment against sustained overloads, short circuits and earth-fault conditions while providing adjustable electronic protection for effective system coordination.
This E2B1600 configuration uses fixed construction with rear horizontal terminals and is supplied with four change-over auxiliary contacts plus circuit-breaker open/closed indication. With a rated voltage of 690 V AC and a rated ultimate short-circuit breaking capacity of 42 kA at 400 V AC, 50 Hz, it provides dependable protection for industrial, commercial and infrastructure distribution systems.
The ABB SACE Emax E2B1600 provides switching, isolation and overcurrent protection for high-current low-voltage distribution systems. Its 1600 A current rating and fixed rear-horizontal-terminal arrangement make it well suited to main switchboards, incoming supplies and feeder circuits where robust circuit protection and straightforward switchgear integration are required.
The PR123/P-LSIG electronic release provides long-time protection against sustained overloads, short-time protection for coordinated fault clearing, instantaneous protection against severe short circuits and ground-fault protection for earth-fault conditions. Combined with auxiliary status contacts and open/closed indication, this E2B1600 provides comprehensive protection and monitoring capability for critical electrical distribution systems.
| Series | SACE Emax E2 |
|---|---|
| ABB order code | 1SDA055799R1 |
| Product type | Air circuit breaker |
| Frame / performance level | E2B |
| Number of poles | 3 |
| Rated current (In) | 1600 A |
| Rated uninterrupted current (Iu) | 1600 A |
| Rated voltage | 690 V AC |
| Trip unit | PR123/P-LSIG R1600 |
| Release type | Electronic |
| Protection functions | LSIG – Long-time, Short-time, Instantaneous and Ground-fault |
| Overload release current setting | 640–1600 A |
| Short-time delayed short-circuit release setting | 960 A |
| Instantaneous short-circuit release adjustment range | 2400–24000 A |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC, 50 Hz | 42 kA |
| Installation | Fixed |
| Terminal arrangement | Rear horizontal |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Circuit breaker open / closed |
| Integrated earth-fault protection | Yes |
| Motor operating mechanism | Optional |
| Weight | 55 kg |
| EAN | 8015644571399 |
The ABB 1SDA055799R1 is a three-pole fixed SACE Emax E2B1600 air circuit breaker rated at 1600 A, equipped with rear horizontal terminals and a PR123/P-LSIG R1600 electronic overcurrent release.
The PR123/P-LSIG provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection.
The E2B1600 has a rated uninterrupted current of 1600 A and uses a three-pole configuration.
ABB 1SDA055799R1 is a fixed air circuit breaker with rear horizontal main terminals for integration into suitable low-voltage switchgear.
This E2B1600 configuration has a rated ultimate short-circuit breaking capacity of 42 kA at 400 V AC, 50 Hz.
ABB SACE Emax air circuit breakers combine electronic overcurrent protection, robust switching performance and practical switchgear integration to provide dependable protection for demanding low-voltage power distribution systems.