1SDA055725R1 ABB E1N 800 PR122/P-LSIG 800A 4P Withdrawable Air Circuit Breaker Moving Part

1SDA055725R1 ABB E1N 800 PR122/P-LSIG 800A 4P Withdrawable Air Circuit Breaker Moving Part

ABB 1SDA055725R1 E1N 800 four-pole withdrawable air circuit breaker moving part rated at 800 A with a PR122/P-LSIG electronic release, integrated earth-fault protection and 50 kA short-circuit breaking capacity at 415 V AC.

SKU: 1SDA055725R1Alt SKU: E1N 800 4P WMPMPN: 1SDA055725R1
Price
List Price £14,790.56 ex VAT
Your Price (ex VAT) Save 25%
£11,092.92 25% OFF
You save £3,697.64 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £11,092.92
Trade pricing is personalised to your account

Manufacturer Lead Time

£11,092.92

Why Choose the ABB E1N 800 PR122/P-LSIG 800A 4P Withdrawable Air Circuit Breaker Moving Part?

The ABB E1N 800 PR122/P-LSIG, order code 1SDA055725R1, is a high-performance four-pole withdrawable air circuit breaker moving part designed for protection and switching in demanding low-voltage electrical distribution systems. As part of the ABB SACE New Emax E1N series, it combines an 800 A frame and rated current with the advanced PR122/P-LSIG electronic protection release.

This E1N configuration is the withdrawable moving part (W MP) of the circuit breaker and is designed for use with the corresponding ABB Emax withdrawable fixed part. The draw-out architecture supports convenient inspection, servicing and replacement, while the four-pole construction enables switching and protection of three phases and neutral in suitable distribution systems.

The E1N 800 platform provides a 50 kA short-circuit breaking capacity at 415 V AC and 50 kA short-time withstand current for 1 s. Its PR122/P-LSIG trip unit provides long-time, short-time, instantaneous and earth-fault protection, making this breaker moving part particularly suitable for installations requiring advanced protection, selectivity and dependable power distribution.

Key Advantages

  • Heavy-duty ABB SACE New Emax air circuit breaker moving part for low-voltage distribution.
  • 800 A rated current for high-current electrical installations.
  • Four-pole configuration for three-phase and neutral switching.
  • PR122/P-LSIG electronic protection release with comprehensive overcurrent and earth-fault protection.
  • 50 kA short-circuit breaking capacity at 415 V AC.
  • 50 kA short-time withstand current for 1 s for demanding distribution networks.
  • Withdrawable moving-part construction supports efficient switchboard maintenance and servicing.

Key Features

  • ABB SACE New Emax E1N series.
  • 800 A frame size and rated current.
  • 4-pole air circuit breaker moving part.
  • PR122/P-LSIG electronic trip unit.
  • Long-time (L), short-time (S), instantaneous (I) and earth-fault (G) protection functions.
  • 50 kA rated ultimate short-circuit breaking capacity at 415 V AC.
  • 50 kA rated short-time withstand current for 1 s.
  • Withdrawable / draw-out moving-part construction.
  • Designed for use with the corresponding ABB Emax withdrawable fixed part.
  • Advanced electronic protection suitable for selective low-voltage distribution systems.

Advanced Protection for Low-Voltage Distribution Systems

Air circuit breakers such as the ABB E1N 800 provide switching and automatic protection for high-current low-voltage circuits. The electronic trip unit monitors electrical conditions and commands the breaker to interrupt the circuit when configured protection thresholds are exceeded, helping protect cables, switchgear and connected equipment against overloads, short circuits and earth faults.

The PR122/P-LSIG release combines long-time overload, short-time selective, instantaneous short-circuit and earth-fault protection. Together with the E1N breaker platform and its withdrawable construction, this provides a flexible solution for switchboards where protection coordination, maintainability and continuity of electrical service are important.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Main incomer and feeder circuit protection.
  • Manufacturing and process plants.
  • Commercial and infrastructure electrical installations.
  • Generator and transformer distribution systems.
  • Withdrawable switchgear requiring advanced overcurrent and earth-fault protection.

Technical Specifications

Series SACE New Emax E1N
ABB order code 1SDA055725R1
Product group 310513-New Emax
Product type Air circuit breaker withdrawable moving part
Performance level E1N
Frame size 800 A
Rated current (In) 800 A
Number of poles 4
Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC 50 kA
Rated short-time withstand current (Icw) for 1 s 50 kA
Protection release PR122/P-LSIG
Release type Electronic overcurrent release
Protection functions Long-time (L), short-time (S), instantaneous (I) and earth-fault (G)
Earth-fault protection Integrated
Mounting version Withdrawable / draw-out
Component Moving part (W MP)

Frequently Asked Questions

What is the ABB 1SDA055725R1?

The ABB 1SDA055725R1 is an E1N 800 four-pole withdrawable SACE New Emax air circuit breaker moving part rated at 800 A and equipped with a PR122/P-LSIG electronic protection release.

What protection functions does the PR122/P-LSIG provide?

The PR122/P-LSIG electronic release provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection.

What is the breaking capacity of the ABB E1N 800?

The E1N 800 has a rated ultimate short-circuit breaking capacity of 50 kA at 415 V AC and a rated short-time withstand current of 50 kA for 1 s.

Is the ABB 1SDA055725R1 a fixed or withdrawable circuit breaker?

The 1SDA055725R1 is the withdrawable moving part of the E1N 800 circuit breaker and is designed for use with the corresponding ABB Emax withdrawable fixed part.

Why use a four-pole E1N 800 circuit breaker?

The four-pole configuration enables switching and protection of all three phase conductors together with the neutral, making it suitable for low-voltage distribution systems where neutral switching is required.

Trusted Low-Voltage Protection from ABB

ABB SACE Emax air circuit breakers are engineered for dependable switching and protection in demanding low-voltage distribution systems, combining high interruption performance, advanced electronic protection and service-friendly withdrawable configurations.