ABB 1SDA055695R1 SACE Emax E1B 1600 is a 1600 A four-pole withdrawable air circuit breaker moving part with a PR123/P-LSIG R1600 electronic trip unit providing LSIG protection and 42 kA short-circuit breaking capacity across 220–690 V AC.
£17,985.13
The ABB E1B 1600 PR123/P-LSIG, order code 1SDA055695R1, is a high-performance 1600 A four-pole withdrawable air circuit breaker moving part designed for protection and switching in demanding low-voltage electrical distribution systems. Part of the established ABB SACE Emax / New Emax range, it combines the E1B frame's robust circuit-breaking capability with the advanced PR123/P-LSIG R1600 electronic overcurrent release.
The fitted PR123/P-LSIG R1600 electronic trip unit provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection. This comprehensive LSIG configuration supports selective and coordinated protection strategies while helping safeguard cables, busbars, switchgear and connected equipment against overloads, short circuits and earth faults.
Supplied as a withdrawable moving part, this four-pole breaker is designed for use with the appropriate ABB SACE Emax fixed part or cradle. Its withdrawable construction facilitates isolation, inspection and maintenance, while four auxiliary contacts and open/closed circuit-breaker position indication support integration with switchboard signalling, monitoring and control systems.
Air circuit breakers such as the ABB SACE Emax E1B protect high-current electrical distribution systems by detecting and interrupting abnormal current conditions before cables, busbars, switchgear and connected equipment can sustain serious damage. The E1B 1600 combines a continuous current capability of 1600 A with 42 kA ultimate and service short-circuit breaking capacities across its specified 220–690 V AC operating range.
The PR123/P-LSIG electronic release combines long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection within one advanced trip unit. The short-time function supports selective coordination with downstream protective devices, while the G function extends protection to earth-fault conditions. Combined with four-pole switching and withdrawable construction, the 1SDA055695R1 is particularly suited to sophisticated three-phase four-wire distribution systems requiring comprehensive protection and convenient maintenance access.
| Series | SACE Emax / New Emax |
|---|---|
| ABB order code | 1SDA055695R1 |
| ABB product group | 310513-New Emax |
| Product type | Air circuit breaker moving part |
| Frame / sub-type | E1B 1600 |
| Short-circuit performance level | B |
| Rated current (In) | 1600 A |
| Rated operational current (Ie) | 1600 A |
| Rated uninterrupted current (Iu) | 1600 A |
| Number of poles | 4 |
| Current type | AC |
| Rated operational voltage | 690 V AC |
| Rated voltage (Ur) | 690 V |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) | 42 kA at 220–690 V AC |
| Rated service short-circuit breaking capacity (Ics) | 42 kA at 220–690 V AC |
| Rated short-time withstand current (Icw) | 42 kA for 1 s |
| Trip unit | PR123/P-LSIG R1600 |
| Release type | Electronic |
| Protection functions | L, S, I and G |
| Long-time protection | Overload protection |
| Short-time protection | Delayed short-circuit protection |
| Instantaneous protection | Short-circuit protection |
| Earth-fault protection | Integrated G function |
| Execution | Withdrawable |
| Component | Moving part (MP) |
| Terminal connection type | Withdrawable circuit breaker |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Power loss | 378 W |
| Electrical durability | 10,000 cycles at ≤440 V; 8000 cycles at 500–690 V |
| Electrical operating frequency | 30 cycles per hour |
| Mechanical durability | 25,000 cycles |
| Mechanical operating frequency | 60 cycles per hour |
| Product dimensions (W × H × D) | 414 × 461 × 396.5 mm |
| Product net weight | 54 kg |
| Standard | IEC |
| Customs tariff number | 85362090 |
| EAN | 8015644570354 |
The ABB 1SDA055695R1 is a 1600 A four-pole SACE Emax withdrawable air circuit breaker moving part designed for switching and protecting high-current low-voltage industrial and commercial electrical distribution systems.
The PR123/P-LSIG R1600 electronic trip unit provides long-time overload (L), short-time delayed short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection.
The E1B 1600 has rated ultimate and service short-circuit breaking capacities of 42 kA across 220–690 V AC, together with rated short-time withstand currents of 42 kA for 1 s and 36 kA for 3 s.
The 1SDA055695R1 is a withdrawable moving part designed for use with the appropriate compatible ABB SACE Emax fixed part or cradle, enabling convenient circuit isolation and breaker removal for inspection or maintenance.
Yes. The fitted PR123/P-LSIG electronic release includes integrated G earth-fault protection in addition to long-time, short-time and instantaneous overcurrent protection.
ABB SACE Emax air circuit breakers are widely used in low-voltage distribution systems where dependable high-current switching, advanced electronic protection and service-friendly withdrawable construction are required.