1SDA055691R1 ABB E1B1600 PR122/P-LI 1600A 4P Withdrawable Air Circuit Breaker

1SDA055691R1 ABB E1B1600 PR122/P-LI 1600A 4P Withdrawable Air Circuit Breaker

ABB 1SDA055691R1 SACE Emax E1B1600 four-pole withdrawable air circuit breaker moving part rated at 1600 A with a PR122/P-LI R1600 electronic overcurrent release for low-voltage power distribution protection.

SKU: 1SDA055691R1MPN: 1SDA055691R1
Price
List Price £14,891.66 ex VAT
Your Price (ex VAT) Save 25%
£11,168.75 25% OFF
You save £3,722.92 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £11,168.75
Trade pricing is personalised to your account

Manufacturer Lead Time

£11,168.75

Why Choose the ABB E1B1600 PR122/P-LI 1600A 4P Withdrawable Air Circuit Breaker?

The ABB E1B1600 PR122/P-LI, order code 1SDA055691R1, is a high-performance SACE Emax air circuit breaker moving part designed for switching and protection in low-voltage power distribution systems. Rated at 1600 A, this four-pole unit combines the E1B breaker frame with the advanced PR122/P-LI electronic overcurrent release.

This model is supplied as a withdrawable moving part (W MP) for installation with the corresponding Emax fixed part. Its withdrawable construction allows the breaker to be isolated and removed for inspection, maintenance or replacement, making it particularly suitable for industrial switchboards where maintainability and continuity of service are important.

The PR122/P-LI R1600 electronic trip unit provides long-time overload and instantaneous short-circuit protection. With a rated uninterrupted current of 1600 A, a rated voltage of 690 V AC and an ultimate short-circuit breaking capacity of 42 kA at 400 V AC, the E1B1600 provides dependable protection for demanding industrial and commercial electrical distribution systems.

Key Advantages

  • Heavy-duty ABB SACE Emax air circuit breaker moving part for low-voltage distribution.
  • 1600 A rated uninterrupted current for high-current electrical installations.
  • Four-pole withdrawable configuration for three-phase systems requiring neutral switching.
  • Advanced PR122/P-LI R1600 electronic overcurrent release.
  • Provides long-time overload and instantaneous short-circuit protection.
  • 42 kA ultimate short-circuit breaking capacity at 400 V AC.
  • Four auxiliary change-over contacts support circuit-breaker status signalling.

Key Features

  • ABB SACE Emax E1B series.
  • 1600 A rated uninterrupted current.
  • Four-pole (4P) construction.
  • Withdrawable moving part (W MP) configuration.
  • PR122/P-LI R1600 electronic overcurrent release.
  • LI protection functions: long-time overload and instantaneous short-circuit protection.
  • 690 V AC rated voltage.
  • 42 kA Icu at 400 V AC.
  • Four auxiliary change-over contacts.
  • Open/closed circuit-breaker position indication.
  • Optional motor operating mechanism capability.
  • Designed for installation with the corresponding E1 withdrawable fixed part.

Reliable Protection for Low-Voltage Power Distribution

Air circuit breakers such as the ABB SACE Emax E1B1600 provide switching and protection for high-current low-voltage distribution circuits. The withdrawable arrangement enables the breaker moving part to be separated from its corresponding fixed part, supporting efficient isolation, inspection and maintenance in critical switchboard applications.

The PR122/P-LI electronic trip unit provides coordinated protection against overloads and high-level short circuits through its long-time and instantaneous protection functions. Combined with the four-pole E1B withdrawable platform, it provides a robust solution for main incomers, feeders and distribution circuits where neutral switching and maintainability are required.

Typical Applications

  • Industrial low-voltage switchboards.
  • Main incoming power distribution circuits.
  • High-current feeder protection.
  • Three-phase distribution systems requiring neutral switching.
  • Manufacturing and process plants.
  • Commercial and infrastructure power systems.

Technical Specifications

Series SACE Emax
Order code 1SDA055691R1
Product type Air circuit breaker moving part
Frame / sub-type E1B
Rated current 1600 A
Number of poles 4P
Version Withdrawable
Configuration Moving part (W MP)
Trip unit PR122/P-LI R1600
Protection functions Long-time overload and instantaneous short circuit
Rated voltage 690 V AC
Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC 42 kA
Overload release setting range 640–1600 A
Instantaneous short-circuit release setting range 2400–24000 A
Integrated earth-fault protection No
Auxiliary contacts 4 change-over contacts
Position indication Circuit breaker open / closed
Motor operating mechanism Optional
Mounting system Withdrawable switchboard installation
Weight approx. 67 kg
EAN 8015644570316

Frequently Asked Questions

What is the ABB 1SDA055691R1?

It is an ABB SACE Emax E1B 1600 A four-pole withdrawable air circuit breaker moving part equipped with a PR122/P-LI R1600 electronic overcurrent release.

What is the rated current of the ABB E1B1600 1SDA055691R1?

The circuit breaker has a rated uninterrupted current of 1600 A.

What protection does the PR122/P-LI trip unit provide?

The PR122/P-LI provides long-time overload and instantaneous short-circuit protection, commonly identified as LI protection.

What is the breaking capacity of this E1B circuit breaker?

The E1B configuration has a rated ultimate short-circuit breaking capacity of 42 kA at 400 V AC.

Is the ABB 1SDA055691R1 fixed or withdrawable?

The 1SDA055691R1 is a withdrawable moving part designed for installation with the corresponding fixed part of an ABB SACE Emax circuit-breaker assembly.

Trusted by Power Distribution Professionals Worldwide

ABB SACE Emax air circuit breakers are engineered for dependable switching and protection in demanding low-voltage power distribution systems, combining high-current performance, electronic protection and maintainable withdrawable switchgear configurations.