ABB 1SDA055684R1 SACE Emax E1B1600 three-pole withdrawable air circuit breaker moving part rated at 1600 A with a PR122/P-LSI R1600 electronic overcurrent release for low-voltage power distribution protection.
£9,107.42
The ABB E1B1600 PR122/P-LSI, order code 1SDA055684R1, is a high-performance SACE Emax air circuit breaker moving part designed for switching and protection in low-voltage power distribution systems. Rated at 1600 A, this three-pole unit combines the E1B breaker frame with the advanced PR122/P-LSI electronic overcurrent release.
This model is supplied as a withdrawable moving part (W MP) for installation with the corresponding Emax fixed part. Its withdrawable construction allows the breaker to be isolated and removed for inspection, servicing or replacement, making it particularly suitable for industrial switchboards where maintainability and continuity of service are important.
The PR122/P-LSI electronic trip unit provides long-time overload, short-time short-circuit and instantaneous short-circuit protection. With a rated uninterrupted current of 1600 A and an E1B ultimate short-circuit breaking capacity of 42 kA at 380–415 V AC, this circuit breaker provides dependable protection for demanding industrial and commercial electrical distribution systems.
Air circuit breakers such as the ABB SACE Emax E1B1600 provide switching and protection for high-current low-voltage distribution circuits. The withdrawable arrangement allows the breaker moving part to be separated from its corresponding fixed part, supporting efficient inspection and maintenance in switchboards where service continuity is a priority.
The PR122/P-LSI electronic trip unit provides coordinated protection against overloads and short circuits through its long-time, short-time and instantaneous protection functions. Combined with the E1B withdrawable platform, it provides a robust solution for main incomers, feeders and other critical power distribution circuits.
| Series | SACE Emax |
|---|---|
| Order code | 1SDA055684R1 |
| Product type | Air circuit breaker moving part |
| Frame / sub-type | E1B |
| Rated current | 1600 A |
| Frame current | 1600 A |
| Number of poles | 3P |
| Version | Withdrawable |
| Configuration | Moving part (W MP) |
| Trip unit | PR122/P-LSI R1600 |
| Protection functions | Long-time, short-time and instantaneous |
| Rated ultimate short-circuit breaking capacity (Icu) at 380–415 V AC | 42 kA |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Mounting system | Withdrawable switchboard installation |
| Weight | 55 kg |
| EAN | 8015644570248 |
It is an ABB SACE Emax E1B 1600 A three-pole withdrawable air circuit breaker moving part equipped with a PR122/P-LSI R1600 electronic overcurrent release.
The circuit breaker has a rated uninterrupted current of 1600 A.
The PR122/P-LSI provides long-time, short-time and instantaneous protection, commonly identified as LSI protection.
The E1B configuration has a rated ultimate short-circuit breaking capacity of 42 kA at 380–415 V AC.
The 1SDA055684R1 is a withdrawable moving part designed for installation with the corresponding fixed part of an ABB SACE Emax circuit-breaker assembly.
ABB SACE Emax air circuit breakers are engineered for dependable switching and protection in demanding low-voltage power distribution systems, combining high-current performance, electronic protection and maintainable withdrawable switchgear configurations.