ABB 1SDA055668R1 SACE Emax E1B 1600 is a 1600 A three-pole fixed air circuit breaker with horizontal rear terminals, a PR122/P-LSI R1600 electronic trip unit providing LSI protection and 42 kA short-circuit breaking capacity across 220–690 V AC.
£8,056.11
The ABB E1B 1600 PR122/P-LSI, order code 1SDA055668R1, is a high-performance 1600 A three-pole fixed air circuit breaker designed for protection and switching in demanding low-voltage electrical distribution systems. Part of the proven ABB SACE Emax / New Emax range, it combines robust E1B short-circuit performance with a PR122/P-LSI R1600 electronic overcurrent release.
The fitted PR122/P-LSI R1600 electronic trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. This LSI protection configuration supports selective and coordinated protection strategies, helping safeguard cables, busbars, switchgear and connected equipment against damaging overcurrent and short-circuit conditions.
This model is supplied in a fixed three-pole configuration with horizontal rear terminals for permanent installation within compatible low-voltage switchboards. With 42 kA rated ultimate and service short-circuit breaking capacity across 220–690 V AC, four auxiliary contacts and open/closed circuit-breaker position indication, it is well suited to high-current industrial distribution duties.
Air circuit breakers such as the ABB SACE Emax E1B protect high-current electrical distribution systems by detecting and interrupting abnormal current conditions before cables, busbars, switchgear and connected equipment can be damaged. The E1B 1600 combines a continuous current capability of 1600 A with 42 kA ultimate and service short-circuit breaking capacities across its specified 220–690 V AC operating range.
The PR122/P-LSI electronic release combines long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection within one trip unit. The short-time function supports selective protection strategies by allowing coordinated fault-clearing with downstream protective devices, while the fixed construction and horizontal rear terminals provide a robust arrangement for permanent switchboard installations.
| Series | SACE Emax / New Emax |
|---|---|
| ABB order code | 1SDA055668R1 |
| Product type | Air circuit breaker |
| Frame / sub-type | E1B 1600 |
| Short-circuit performance level | B |
| Rated current (In) | 1600 A |
| Rated operational current (Ie) | 1600 A |
| Rated uninterrupted current (Iu) | 1600 A |
| Number of poles | 3 |
| Current type | AC |
| Rated operational voltage | 690 V AC |
| Rated voltage (Ur) | 690 V |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) | 42 kA at 220–690 V AC |
| Rated service short-circuit breaking capacity (Ics) | 42 kA at 220–690 V AC |
| Rated short-time withstand current (Icw) | 42 kA for 1 s |
| Trip unit | PR122/P-LSI R1600 |
| Release type | Electronic |
| Protection functions | L, S and I |
| Installation | Fixed |
| Terminal arrangement | Horizontal rear terminals (HR) |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Power loss | 253 W |
| Electrical durability | 10,000 cycles at ≤440 V; 8000 cycles at 500–690 V |
| Electrical operating frequency | 30 cycles per hour |
| Mechanical durability | 25,000 cycles |
| Mechanical operating frequency | 60 cycles per hour |
| Product net weight | approx. 50 kg |
| Standard | IEC |
| EAN | 8015644570088 |
The ABB 1SDA055668R1 is a 1600 A three-pole fixed SACE Emax air circuit breaker used for switching and protecting high-current low-voltage industrial and commercial electrical distribution systems.
The PR122/P-LSI R1600 electronic trip unit provides long-time overload (L), short-time delayed short-circuit (S) and instantaneous short-circuit (I) protection.
This E1B 1600 has rated ultimate and service short-circuit breaking capacities of 42 kA across 220–690 V AC, together with a rated short-time withstand current of 42 kA for 1 s.
The 1SDA055668R1 is a fixed air circuit breaker with horizontal rear terminals, designed for permanent installation within compatible ABB SACE Emax low-voltage switchgear assemblies.
LSI provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. Unlike an LSIG release, the PR122/P-LSI configuration does not include the additional G earth-fault protection function.
ABB SACE Emax air circuit breakers are widely used in low-voltage distribution systems where dependable high-current switching, adjustable electronic protection and robust switchboard integration are required.