ABB 1SDA055659R1 SACE Emax E1B 1250 is a 1250 A four-pole withdrawable air circuit breaker moving part with a PR122/P-LI R1250 electronic trip unit, 42 kA short-circuit breaking capacity at 400 V AC and four auxiliary contacts.
£9,822.71
The ABB E1B 1250 PR122/P-LI, order code 1SDA055659R1, is a 1250 A four-pole withdrawable air circuit breaker moving part designed for protection and switching in demanding low-voltage electrical distribution systems. Part of the proven ABB SACE Emax / New Emax range, it combines E1B circuit-breaking performance with a PR122/P-LI R1250 electronic overcurrent release.
The fitted PR122/P-LI R1250 trip unit provides long-time overload and instantaneous short-circuit protection. Its overload release can be adjusted across a 500–1250 A range, while instantaneous short-circuit protection provides rapid interruption of severe fault currents. This LI configuration is suited to applications where short-time delayed and integrated earth-fault protection are not required.
Supplied as a withdrawable moving part, the breaker connects through the appropriate separate SACE Emax fixed part or cradle, supporting convenient isolation, servicing and replacement. The four-pole arrangement is suitable for three-phase systems requiring neutral switching, while four auxiliary contacts and open/closed position indication support integration into switchboard control and monitoring systems.
Air circuit breakers such as the ABB SACE Emax E1B protect high-current electrical distribution systems by detecting and interrupting abnormal current conditions before cables, switchgear and connected equipment can be damaged. This E1B 1250 combines a continuous current capability of 1250 A with a 42 kA short-circuit breaking capacity at 400 V AC, making it suitable for demanding main distribution and feeder duties.
The PR122/P-LI electronic release combines adjustable long-time overload protection with instantaneous short-circuit protection. Together with the withdrawable moving-part design, this provides a practical solution for installations requiring high-current circuit protection and convenient breaker isolation for inspection, maintenance or replacement.
| Series | SACE Emax / New Emax |
|---|---|
| ABB order code | 1SDA055659R1 |
| Product type | Air circuit breaker moving part |
| Frame / sub-type | E1B 1250 |
| Performance level | B |
| Rated uninterrupted current (Iu) | 1250 A |
| Number of poles | 4 |
| Rated voltage | 690 V |
| Short-circuit breaking capacity at 400 V, 50 Hz | 42 kA |
| Trip unit | PR122/P-LI R1250 |
| Release type | Electronic overcurrent release |
| Protection functions | L and I |
| Overload release adjustment range | 500–1250 A |
| Instantaneous short-circuit adjustment range | 1875–18,750 A |
| Integrated earth-fault protection | No |
| Execution | Withdrawable |
| Component | Moving part (MP) |
| Main-circuit connection | Through separate fixed part / cradle |
| Auxiliary contacts | 4 total, 2 NO + 2 NC |
| Position indication | Circuit breaker open / closed |
| Trip indication | Yes |
| Operating mechanism | Push-button |
| Integrated motor operator | No |
| Optional motor operator | Yes |
| Integrated undervoltage release | No |
| Degree of protection | IP2X |
| DIN rail mounting | No |
| Weight | approx. 67 kg |
| EAN | 8015644569990 |
The ABB 1SDA055659R1 is a 1250 A four-pole SACE Emax withdrawable air circuit breaker moving part used for switching and protecting high-current low-voltage industrial and commercial electrical distribution systems.
The PR122/P-LI R1250 electronic trip unit provides long-time overload (L) and instantaneous short-circuit (I) protection.
This E1B 1250 has a short-circuit breaking capacity of 42 kA at 400 V AC, 50 Hz, making it suitable for demanding low-voltage distribution applications.
The 1SDA055659R1 is a withdrawable moving part designed to connect through the appropriate separate ABB SACE Emax fixed part or cradle.
No. The fitted PR122/P-LI release provides long-time overload and instantaneous short-circuit protection but does not include integrated earth-fault protection.
ABB SACE Emax air circuit breakers are widely used in low-voltage distribution systems where dependable high-current switching, electronic overcurrent protection and service-friendly withdrawable construction are required.