Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA055658R1 is a SACE Emax E1B 1250 A four-pole withdrawable air circuit breaker moving part with a PR121/P-LSIG electronic release providing long-time, short-time, instantaneous and ground-fault protection.
£11,187.69
The ABB 1SDA055658R1 is a SACE Emax E1B 1250 withdrawable air circuit breaker moving part designed for switching and protection in demanding low-voltage power distribution systems. Identified as E1B1250PR121/P-LSIGIn=1250A4pW, this configuration combines a 1250 A rated current, four-pole withdrawable construction and ABB's PR121/P-LSIG electronic overcurrent release.
The PR121/P-LSIG release provides long-time, short-time, instantaneous and ground-fault protection, delivering comprehensive protection against overload, short-circuit and earth-fault conditions. The E1B performance level provides rated ultimate and service short-circuit breaking capacities of 42 kA across its specified IEC AC operating voltages up to 690 V AC.
As a withdrawable circuit-breaker moving part, the 1SDA055658R1 supports switchboard architectures where maintainability and efficient servicing are important. Its four-pole arrangement and LSIG protection make it particularly suitable for high-current distribution systems requiring comprehensive electronic protection.
Withdrawable air circuit breakers provide high-current switching and protection while allowing the circuit-breaker moving assembly to be separated from the switchgear fixed section for inspection, servicing and replacement. This architecture is particularly useful in industrial distribution boards where maintainability, equipment availability and efficient servicing are important design requirements.
The PR121/P-LSIG electronic release combines long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection. Together with the 1250 A E1B frame, four-pole arrangement, 42 kA short-circuit performance and withdrawable construction, the 1SDA055658R1 provides comprehensive protection for demanding low-voltage power distribution assemblies.
| Series | SACE Emax |
|---|---|
| ABB order code | 1SDA055658R1 |
| Product designation | E1B1250PR121/P-LSIGIn=1250A4pW |
| Product type | Air circuit breaker |
| Component | Withdrawable circuit-breaker moving part |
| Frame / sub-type | E1 |
| Short-circuit performance level | B |
| Rated current (In) | 1250 A |
| Rated uninterrupted current (Iu) | 1250 A |
| Rated operational current (Ie) | 1250 A |
| Number of poles | 4 |
| Release | PR121/P-LSIG |
| Release type | Electronic |
| Protection functions | Long-time, short-time, instantaneous and ground-fault protection |
| Version | Withdrawable |
| Current type | AC |
| Rated operational voltage | 690 V AC |
| Rated voltage (Ur) | 690 V |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) | 42 kA at 220–690 V AC |
| Rated service short-circuit breaking capacity (Ics) | 42 kA at 220–690 V AC |
| Rated short-time withstand current (Icw) | 42 kA for 1 s |
| Power loss | 230 W |
| Electrical durability at Ue ≤ 440 V | 10,000 cycles |
| Electrical durability at Ue 500–690 V | 8,000 cycles |
| Mechanical durability | 25,000 cycles |
| Product net width | 414 mm |
| Product net height | 461 mm |
| Product net depth | 396.5 mm |
| Product net weight | 54 kg |
| EAN | 8015644569983 |
| Customs tariff number | 85362090 |
| Standard | IEC |
The ABB 1SDA055658R1 is an E1B 1250 four-pole withdrawable air circuit breaker moving part rated at 1250 A and fitted with a PR121/P-LSIG electronic overcurrent release.
The ABB 1SDA055658R1 has a rated current and rated uninterrupted current of 1250 A.
The circuit breaker is fitted with the ABB PR121/P-LSIG electronic overcurrent release.
The LSIG configuration provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection.
The 1SDA055658R1 is a withdrawable four-pole circuit-breaker moving part.
The E1B 1250 provides rated ultimate and service short-circuit breaking capacities of 42 kA across its specified IEC AC operating voltages from 220–690 V AC.
The rated short-time withstand current is 42 kA for 1 s and 36 kA for 3 s.
Yes. The PR121/P-LSIG release includes ground-fault protection in addition to long-time, short-time and instantaneous overcurrent protection.
ABB SACE Emax air circuit breakers are engineered for dependable switching and protection in demanding low-voltage electrical installations, combining serviceable withdrawable construction, high short-circuit performance and electronic LSIG protection for industrial power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.