ABB 1SDA055653R1 SACE Emax E1B 1250 is a 1250 A three-pole withdrawable air circuit breaker moving part with a PR122/P-LSIG R1250 electronic trip unit providing LSIG protection and 42 kA short-circuit breaking capacity across 220–690 V AC.
£9,377.10
The ABB E1B 1250 PR122/P-LSIG, order code 1SDA055653R1, is a high-performance 1250 A three-pole withdrawable air circuit breaker moving part designed for protection and switching in demanding low-voltage electrical distribution systems. Part of the proven ABB SACE Emax / New Emax range, it combines robust E1B short-circuit performance with a PR122/P-LSIG electronic overcurrent release.
The PR122/P-LSIG R1250 trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection. This comprehensive LSIG protection enables the breaker to respond to multiple fault conditions while supporting selective and coordinated protection within industrial and commercial distribution networks.
Supplied as a withdrawable moving part, the breaker is designed for use with the appropriate SACE Emax fixed part or cradle. Its withdrawable construction facilitates isolation and maintenance, while four auxiliary contacts and open/closed position indication support integration into switchboard control and monitoring systems.
Air circuit breakers such as the ABB SACE Emax E1B protect high-current electrical distribution systems by detecting and interrupting abnormal current conditions before cables, switchgear and connected equipment can be damaged. The E1B 1250 combines a continuous current rating of 1250 A with 42 kA ultimate and service short-circuit breaking capacities across its specified AC voltage range.
The PR122/P-LSIG electronic release combines long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection within one electronic trip unit. Together with the withdrawable moving-part design, this provides a flexible solution for installations requiring comprehensive protection, high fault-handling capability and convenient breaker isolation for servicing.
| Series | SACE Emax / New Emax |
|---|---|
| ABB order code | 1SDA055653R1 |
| Product type | Air circuit breaker moving part |
| Frame / sub-type | E1B 1250 |
| Short-circuit performance level | B |
| Rated current (In) | 1250 A |
| Rated operational current (Ie) | 1250 A |
| Rated uninterrupted current (Iu) | 1250 A |
| Number of poles | 3 |
| Current type | AC |
| Rated operational voltage | 690 V AC |
| Rated voltage (Ur) | 690 V |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) | 42 kA at 220–690 V AC |
| Rated service short-circuit breaking capacity (Ics) | 42 kA at 220–690 V AC |
| Rated short-time withstand current (Icw) | 42 kA for 1 s |
| Trip unit | PR122/P-LSIG R1250 |
| Release type | Electronic |
| Protection functions | L, S, I and G |
| Overload release adjustment range | 400–1250 A |
| Short-time delayed short-circuit adjustment range | 750–12,500 A |
| Instantaneous short-circuit adjustment range | 1875–18,750 A |
| Integrated earth-fault protection | Yes |
| Execution | Withdrawable |
| Component | Moving part (MP) |
| Auxiliary contacts | 4 total, 2 NO + 2 NC |
| Position indication | Circuit breaker open / closed |
| Power loss | 230 W |
| Electrical durability | 10,000 cycles at ≤440 V; 8000 cycles at 500–690 V |
| Mechanical durability | 25,000 cycles |
| Weight | 55 kg |
| Standard | IEC |
| EAN | 8015644569938 |
The ABB 1SDA055653R1 is a 1250 A three-pole SACE Emax withdrawable air circuit breaker moving part used for switching and protecting high-current low-voltage industrial and commercial electrical distribution systems.
The PR122/P-LSIG R1250 electronic trip unit provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection.
This E1B 1250 has rated ultimate and service short-circuit breaking capacities of 42 kA across 220–690 V AC, together with a rated short-time withstand current of 42 kA for 1 s.
The 1SDA055653R1 is a withdrawable moving part designed for use with the appropriate compatible ABB SACE Emax fixed part or cradle.
Yes. The fitted PR122/P-LSIG electronic release includes integrated G earth-fault protection in addition to long-time, short-time and instantaneous overcurrent protection.
ABB SACE Emax air circuit breakers are widely used in low-voltage distribution systems where dependable high-current switching, comprehensive electronic protection and service-friendly withdrawable construction are required.
We use cookies