1SDA055538R1 ABB E4S 4000A 4P PR121/P-LSIG Fixed Air Circuit Breaker

1SDA055538R1 ABB E4S 4000A 4P PR121/P-LSIG Fixed Air Circuit Breaker

ABB 1SDA055538R1 is a SACE Emax E4S 4000 A four-pole fixed air circuit breaker with full-size neutral, rear horizontal terminals and a PR121/P-LSIG R4000 electronic overcurrent release.

SKU: 1SDA055538R1MPN: 1SDA055538R1
Price
List Price £44,177.34 ex VAT
Your Price (ex VAT) Save 25%
£33,133.01 25% OFF
You save £11,044.34 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £33,133.01
Trade pricing is personalised to your account

Manufacturer Lead Time

£33,133.01

Why Choose the ABB E4S/f 4000 PR121/P-LSIG 1SDA055538R1 Circuit Breaker?

The ABB 1SDA055538R1 is a SACE Emax E4S 4000 A four-pole fixed air circuit breaker designed for switching and protection in demanding low-voltage power distribution systems. It combines the E4S platform with an ABB PR121/P-LSIG R4000 electronic overcurrent release.

This circuit breaker features a four-pole configuration with full-size neutral, fixed construction and rear horizontal terminals. The PR121/P-LSIG electronic trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection, delivering comprehensive LSIG protection for high-capacity distribution circuits.

Rated at 4000 A with a rated operational voltage of 690 V AC, the 1SDA055538R1 provides an ultimate short-circuit breaking capacity of 80 kA at 400 V AC. Four auxiliary change-over contacts and circuit-breaker open/closed position indication support integration into switchboard control and signalling systems.

Key Advantages

  • High-current 4000 A SACE Emax E4S air circuit breaker.
  • Four-pole fixed configuration with full-size neutral.
  • PR121/P-LSIG R4000 electronic trip unit for comprehensive electronic protection.
  • LSIG protection functions cover long-time overload, short-time, instantaneous and earth-fault conditions.
  • 80 kA ultimate and service short-circuit breaking capacity at 400 V AC.
  • Rear horizontal terminals support integration with switchboard busbar systems.
  • Four auxiliary change-over contacts and open/closed position indication support control and signalling.

Key Features

  • ABB SACE Emax E4S air circuit breaker.
  • 4000 A rated uninterrupted current.
  • Four-pole (4P) configuration.
  • Full-size neutral.
  • Fixed (F) version.
  • Rear horizontal (HR) terminal arrangement.
  • PR121/P-LSIG R4000 electronic overcurrent release.
  • LSIG protection: long-time, short-time, instantaneous and earth fault.
  • 690 V AC rated operational voltage.
  • 80 kA breaking capacity at 400–440 V AC.
  • 75 kA breaking capacity at 500–690 V AC.
  • 80 kA short-time withstand current for 1 s.
  • Four auxiliary change-over contacts for signalling and control.

Comprehensive LSIG Protection for High-Current Distribution

The ABB SACE Emax E4S platform is designed for demanding low-voltage distribution applications requiring high continuous current capability and robust short-circuit performance. The fixed construction and rear horizontal terminals of the 1SDA055538R1 make it suitable for permanent integration into compatible switchboards and busbar systems.

The PR121/P-LSIG electronic release provides long-time protection against sustained overloads, short-time protection for controlled fault response and selective coordination, instantaneous protection against severe short circuits, and integrated earth-fault protection. Combined with the 4000 A E4S platform, these functions provide comprehensive protection for high-capacity incoming and feeder circuits.

Typical Applications

  • Main low-voltage distribution switchboards.
  • Industrial power distribution systems.
  • High-current incoming circuits.
  • High-capacity feeder protection.
  • Manufacturing and process plants.
  • Commercial and infrastructure electrical systems.
  • Transformer and generator distribution systems.
  • Fixed power distribution and switchgear assemblies.

Technical Specifications

Series SACE Emax
Product designation E4S/f 4000 PR121/P-LSIG In=4000A 4p F HR
ABB order code 1SDA055538R1
EAN 8015644568788
Product type Air circuit breaker
Frame E4
Short-circuit performance level S
Rated uninterrupted current 4000 A
Rated operational current 4000 A
Rated operational voltage 690 V AC
Rated insulation voltage 1000 V
Rated impulse withstand voltage 12 kV
Rated ultimate short-circuit breaking capacity 80 kA at 220–440 V AC; 75 kA at 500–690 V AC
Rated service short-circuit breaking capacity 80 kA at 220–440 V AC; 75 kA at 500–690 V AC
Rated short-time withstand current 80 kA for 1 s / 75 kA for 3 s
Number of poles 4P
Neutral Full size
Version Fixed
Terminal arrangement Rear horizontal (HR)
Trip unit PR121/P-LSIG R4000
Release type Electronic
Protection functions Long-time, short-time, instantaneous and earth fault (LSIG)
Overload release setting range 1600–4000 A
Short-time delayed short-circuit release setting range 4000–40000 A
Instantaneous short-circuit release setting range 6000–60000 A
Integrated earth-fault protection Yes
Auxiliary contacts 4 change-over contacts
Position indication Circuit breaker open / closed
Electrical durability 5000 cycles at ≤440 V; 4000 cycles at 500–690 V
Mechanical durability 15000 cycles
Power loss 360 W
Dimensions (W × H × D) 746 × 418 × 302 mm
Product net weight 109 kg
Standard IEC
Product group 310513-New Emax

Frequently Asked Questions

What is the ABB 1SDA055538R1?

The ABB 1SDA055538R1 is a SACE Emax E4S 4000 A four-pole fixed air circuit breaker with full-size neutral, rear horizontal terminals and a PR121/P-LSIG R4000 electronic overcurrent release.

What is the rated current of the ABB 1SDA055538R1?

The circuit breaker has a rated uninterrupted current of 4000 A, making it suitable for high-current low-voltage distribution applications.

What protection does the PR121/P-LSIG trip unit provide?

The PR121/P-LSIG electronic trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection.

What is the breaking capacity of the ABB 1SDA055538R1?

The E4S circuit breaker has rated ultimate and service short-circuit breaking capacities of 80 kA at 400 V AC and 75 kA at 690 V AC.

Is the ABB 1SDA055538R1 fixed or withdrawable?

The 1SDA055538R1 is a fixed four-pole circuit breaker with a full-size neutral and rear horizontal terminals.

Trusted ABB Power Distribution Protection

ABB SACE Emax air circuit breakers provide purpose-designed switching and electronic protection for demanding low-voltage power distribution systems, supporting reliable integration into industrial, commercial and infrastructure switchgear.