1SDA055076R1 ABB T4L 250 MA 52-728 3p F F Moulded Case Circuit Breaker

1SDA055076R1 ABB T4L 250 MA 52-728 3p F F Moulded Case Circuit Breaker

ABB 1SDA055076R1 T4L 250 is a three-pole fixed moulded case circuit breaker with an MA 52 magnetic-only trip unit adjustable from 312–728 A and a 120 kA ultimate breaking capacity at 415 V AC.

SKU: 1SDA055076R1Alt SKU: T4L250RM52MPN: 1SDA055076R1
Price
List Price £1,541.30 ex VAT
Your Price (ex VAT) Save 25%
£1,155.98 25% OFF
You save £385.33 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,155.98
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,155.98

Why Choose the ABB T4L 250 MA 52-728 3p F F?

The ABB 1SDA055076R1 is a high-performance SACE Tmax T4L 250 moulded case circuit breaker (MCCB) designed for motor protection and low-voltage industrial power applications. Identified by ABB as T4L 250 MA 52-728 3p F F, it combines the T4 250 frame with an MA magnetic-only trip unit for instantaneous short-circuit protection.

As part of the ABB SACE Tmax T4 series, this three-pole circuit breaker is designed for fixed installation with front terminals. The magnetic-only MA release is particularly suited to motor circuits where overload protection is provided separately, allowing the breaker to provide high-performance short-circuit protection while coordinating with external motor protection equipment.

The T4L 250 version provides a high breaking capacity of 120 kA at 415 V AC. This model uses an MA 52 magnetic trip unit with an adjustable instantaneous trip range of 312–728 A, making it suitable for demanding motor feeders and industrial installations requiring robust fault-current interruption.

Key Advantages

  • High-performance ABB SACE Tmax T4L moulded case circuit breaker.
  • 250 A frame size for industrial low-voltage applications.
  • MA 52 magnetic-only trip unit optimised for motor protection applications.
  • Adjustable instantaneous magnetic trip range of 312–728 A.
  • High 120 kA breaking capacity at 415 V AC.
  • 3-pole configuration for three-phase systems.
  • Fixed installation with front terminals for straightforward panel integration.

Key Features

  • ABB SACE Tmax T4L 250 circuit-breaker platform.
  • MA magnetic-only release.
  • 52 A trip-unit rating.
  • 312–728 A adjustable magnetic trip range.
  • 120 kA Icu at 415 V AC.
  • 3-pole configuration.
  • Fixed (F) execution.
  • Front terminals (F).
  • Suitable for motor protection and industrial power distribution applications.
  • ABB order code 1SDA055076R1.
  • EAN 8015644562243.

High-Performance Short-Circuit Protection for Motor Circuits

Magnetic-only circuit breakers are commonly used in motor circuits where overload protection is provided by a separate overload relay or electronic motor protection device. The magnetic release responds rapidly to high fault currents, allowing the circuit breaker to interrupt short circuits while avoiding the duplication of thermal overload protection.

The ABB T4L 250 combines this motor-protection functionality with a high 120 kA Icu at 415 V AC. Its adjustable 312–728 A magnetic threshold allows the protection setting to be coordinated with the motor circuit and associated starting characteristics while maintaining effective short-circuit protection.

Typical Applications

  • Three-phase industrial motor feeders.
  • Motor control centres and MCC panels.
  • Industrial machinery and production equipment.
  • Pumps, fans and compressor systems.
  • Conveyors and material handling equipment.
  • Low-voltage switchboards and distribution panels.
  • Industrial installations with separate motor overload protection.

Technical Specifications

Series SACE Tmax T4
Product group 310511-T-Max T4 - T8
Order code 1SDA055076R1
Product type Moulded case circuit breaker
Frame T4
Performance level L
Frame rated current 250 A
Trip unit MA magnetic-only
Trip-unit rating 52 A
Magnetic trip range 312–728 A
Ultimate breaking capacity (Icu) at 415 V AC 120 kA
Number of poles 3
Mounting execution Fixed
Terminal arrangement Front terminals
EAN 8015644562243

Frequently Asked Questions

What is the ABB 1SDA055076R1 used for?

The ABB 1SDA055076R1 is a Tmax T4L 250 moulded case circuit breaker with a magnetic-only trip unit, making it particularly suitable for short-circuit protection of three-phase motor circuits where overload protection is provided separately.

What is the magnetic trip range of the ABB 1SDA055076R1?

The MA 52 magnetic trip unit provides an adjustable instantaneous trip range of 312–728 A.

What is the breaking capacity of the ABB T4L 250 1SDA055076R1?

The T4L version has an ultimate short-circuit breaking capacity of 120 kA at 415 V AC.

Does the ABB 1SDA055076R1 provide thermal overload protection?

No. This model uses an MA magnetic-only trip unit for short-circuit protection, so suitable separate overload protection is required where overload protection is needed for the connected motor or circuit.

What do 3p F F mean in the ABB product designation?

3p identifies a three-pole circuit breaker, while the two F designations identify the fixed circuit-breaker execution and front terminal arrangement.

Trusted ABB Motor Protection

ABB SACE Tmax moulded case circuit breakers provide robust short-circuit protection and flexible integration for motor feeders, industrial machinery and low-voltage distribution systems, with high breaking capacities suited to demanding electrical installations.