Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA055076R1 T4L 250 is a three-pole fixed moulded case circuit breaker with an MA 52 magnetic-only trip unit adjustable from 312–728 A and a 120 kA ultimate breaking capacity at 415 V AC.
£1,155.98
The ABB 1SDA055076R1 is a high-performance SACE Tmax T4L 250 moulded case circuit breaker (MCCB) designed for motor protection and low-voltage industrial power applications. Identified by ABB as T4L 250 MA 52-728 3p F F, it combines the T4 250 frame with an MA magnetic-only trip unit for instantaneous short-circuit protection.
As part of the ABB SACE Tmax T4 series, this three-pole circuit breaker is designed for fixed installation with front terminals. The magnetic-only MA release is particularly suited to motor circuits where overload protection is provided separately, allowing the breaker to provide high-performance short-circuit protection while coordinating with external motor protection equipment.
The T4L 250 version provides a high breaking capacity of 120 kA at 415 V AC. This model uses an MA 52 magnetic trip unit with an adjustable instantaneous trip range of 312–728 A, making it suitable for demanding motor feeders and industrial installations requiring robust fault-current interruption.
Magnetic-only circuit breakers are commonly used in motor circuits where overload protection is provided by a separate overload relay or electronic motor protection device. The magnetic release responds rapidly to high fault currents, allowing the circuit breaker to interrupt short circuits while avoiding the duplication of thermal overload protection.
The ABB T4L 250 combines this motor-protection functionality with a high 120 kA Icu at 415 V AC. Its adjustable 312–728 A magnetic threshold allows the protection setting to be coordinated with the motor circuit and associated starting characteristics while maintaining effective short-circuit protection.
| Series | SACE Tmax T4 |
|---|---|
| Product group | 310511-T-Max T4 - T8 |
| Order code | 1SDA055076R1 |
| Product type | Moulded case circuit breaker |
| Frame | T4 |
| Performance level | L |
| Frame rated current | 250 A |
| Trip unit | MA magnetic-only |
| Trip-unit rating | 52 A |
| Magnetic trip range | 312–728 A |
| Ultimate breaking capacity (Icu) at 415 V AC | 120 kA |
| Number of poles | 3 |
| Mounting execution | Fixed |
| Terminal arrangement | Front terminals |
| EAN | 8015644562243 |
The ABB 1SDA055076R1 is a Tmax T4L 250 moulded case circuit breaker with a magnetic-only trip unit, making it particularly suitable for short-circuit protection of three-phase motor circuits where overload protection is provided separately.
The MA 52 magnetic trip unit provides an adjustable instantaneous trip range of 312–728 A.
The T4L version has an ultimate short-circuit breaking capacity of 120 kA at 415 V AC.
No. This model uses an MA magnetic-only trip unit for short-circuit protection, so suitable separate overload protection is required where overload protection is needed for the connected motor or circuit.
3p identifies a three-pole circuit breaker, while the two F designations identify the fixed circuit-breaker execution and front terminal arrangement.
ABB SACE Tmax moulded case circuit breakers provide robust short-circuit protection and flexible integration for motor feeders, industrial machinery and low-voltage distribution systems, with high breaking capacities suited to demanding electrical installations.