Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA054593R1 is a SACE Tmax T5S 630 fixed four-pole MCCB breaking part with front terminals, a 630 A rated uninterrupted current and 50 kA short-circuit breaking capacity at 400 V AC.
£2,483.21
The ABB T5S 630 Breaking Part 4P F F, order code 1SDA054593R1, is a fixed four-pole breaking unit for the ABB SACE Tmax T5 moulded case circuit breaker platform. It provides the switching and fault-interruption section of a configurable Tmax T5 assembly, with a rated uninterrupted current of 630 A and front terminals for integration into industrial low-voltage distribution equipment.
The T5S designation identifies the S short-circuit performance level. Within the Tmax T5 platform, this version provides an ultimate short-circuit breaking capacity of 50 kA at 400 V AC, making it suitable for industrial and commercial distribution systems requiring dependable fault interruption at substantial current levels.
The 1SDA054593R1 combines a four-pole configuration, fixed built-in construction, front-side bolt connections and an IP20 degree of protection. Its four-pole arrangement enables simultaneous switching of all four conductors where required, while the modular Tmax design supports configuration with compatible ABB T5 protection and operating components.
The ABB T5S 630 breaking part provides the current-carrying, switching and fault-interruption functions within a compatible Tmax T5 circuit breaker configuration. Its 630 A rated uninterrupted current makes it suitable for substantial feeders and distribution circuits, while the modular construction enables the required compatible ABB protection components to be selected for the finished assembly.
The S performance level provides a short-circuit breaking capacity of 50 kA at 400 V AC. Combined with its four-pole arrangement, fixed installation and front terminals, the 1SDA054593R1 provides a robust basis for industrial switchboards, commercial distribution systems and other installations requiring dependable four-pole power switching and fault interruption.
| Series | SACE Tmax T5 |
|---|---|
| Order code | 1SDA054593R1 |
| EAN | 8015644556914 |
| Product type | MCCB breaking part |
| Frame | T5 630 |
| Short-circuit performance level | S |
| Rated uninterrupted current (Iu) | 630 A |
| Number of poles | 4 |
| Rated operational voltage | up to 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC, 50 Hz | 50 kA |
| Service short-circuit breaking capacity (Ics) at 400 V AC | 50 kA |
| Service short-circuit breaking capacity (Ics) at 440 V AC | 40 kA |
| Service short-circuit breaking capacity (Ics) at 500 V AC | 30 kA |
| Service short-circuit breaking capacity (Ics) at 690 V AC | 25 kA |
| Mounting | Fixed built-in |
| Main-circuit connection position | Front |
| Main-circuit connection type | Bolt connection |
| Operating mechanism | Toggle |
| Integrated earth-leakage protection | No |
| Integrated motor operator | No |
| Optional motor operator | Yes |
| Protection rating | IP20 |
| Weight | approximately 4.5 kg |
| Standard | IEC |
The ABB 1SDA054593R1 is a T5S 630 fixed four-pole breaking part with front terminals for the ABB SACE Tmax T5 moulded case circuit breaker platform.
The T5S 630 breaking unit has a rated uninterrupted current of 630 A.
The T5S 630 provides an ultimate short-circuit breaking capacity of 50 kA at 400 V AC.
The 1SDA054593R1 has a four-pole configuration, allowing it to form part of a compatible circuit-breaker assembly where four-pole switching is required.
The 1SDA054593R1 is a fixed built-in unit with front-side bolt connections for the main electrical circuit.
The Tmax T5S 630 platform has a rated operational voltage of up to 690 V AC, making it suitable for a wide range of industrial low-voltage distribution systems.
ABB SACE Tmax circuit breaker components are used in industrial and commercial power-distribution systems worldwide, providing robust fault interruption, configurable protection and dependable performance for demanding electrical installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.