1SDA054579R1 ABB T5H 400 Breaking Part 3P F F

1SDA054579R1 ABB T5H 400 Breaking Part 3P F F

ABB 1SDA054579R1 is a SACE Tmax T5H 400 fixed three-pole MCCB breaking part with front terminals, a 400 A rated uninterrupted current and 70 kA ultimate and service short-circuit breaking capacity at 400/415 V AC.

SKU: 1SDA054579R1Alt SKU: T5H400MPN: 1SDA054579R1
Price
List Price £1,201.50 ex VAT
Your Price (ex VAT) Save 25%
£901.13 25% OFF
You save £300.38 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £901.13
Trade pricing is personalised to your account

Manufacturer Lead Time

£901.13

Why Choose the ABB T5H 400 Breaking Part 3P F F?

The ABB T5H 400 Breaking Part 3P F F, order code 1SDA054579R1, is a fixed three-pole breaking unit for the ABB SACE Tmax T5 moulded case circuit breaker platform. Designed as the switching and fault-interruption section of a configurable Tmax T5 assembly, it provides a 400 A rated uninterrupted current and front-terminal construction for integration into industrial power-distribution equipment.

The T5H designation identifies the H short-circuit performance level. This breaking unit provides an ultimate and service short-circuit breaking capacity of 70 kA at 400/415 V AC, with further ratings of 65 kA at 440 V AC, 50 kA at 500 V AC and 40 kA at 690 V AC.

With a rated operational voltage of up to 690 V AC and 750 V DC, together with 1000 V insulation voltage and 8 kV impulse withstand voltage, the 1SDA054579R1 provides a robust foundation for demanding industrial distribution applications. Its fixed three-pole construction is designed for use with compatible ABB Tmax T5 protection releases and accessories.

Key Advantages

  • Genuine ABB SACE Tmax T5H 400 breaking part.
  • 400 A rated uninterrupted current.
  • H high-breaking-capacity performance level.
  • 70 kA Icu and Ics at 400/415 V AC.
  • Rated operational voltage up to 690 V AC and 750 V DC.
  • Three-pole fixed configuration for three-phase distribution systems.
  • Front-terminal construction for straightforward switchboard integration.

Key Features

  • ABB SACE Tmax T5 series.
  • T5H 400 breaking unit.
  • 400 A rated uninterrupted current (Iu).
  • Three-pole configuration.
  • H short-circuit performance level.
  • 70 kA breaking capacity at 400/415 V AC.
  • 1000 V rated insulation voltage (Ui).
  • 8 kV rated impulse withstand voltage (Uimp).
  • 5 kA rated short-time withstand current for 1 s.
  • Fixed installation configuration.
  • Front terminals.
  • IP20 protection rating.

High-Breaking-Capacity Unit for ABB Tmax T5 Circuit Breaker Assemblies

The ABB T5H 400 breaking part provides the current-carrying, switching and fault-interruption functions within a compatible Tmax T5 circuit breaker configuration. The modular Tmax design allows the breaking unit to be combined with an appropriate protection release so that the completed assembly can be configured for the overload and short-circuit protection requirements of the installation.

The H performance level delivers substantial fault-interruption capability, including 70 kA at 400/415 V AC and 40 kA at 690 V AC. Together with its 400 A current rating, fixed three-pole construction and front terminals, the 1SDA054579R1 is well suited to demanding industrial switchboards and distribution systems with high prospective fault currents.

Typical Applications

  • ABB SACE Tmax T5 circuit breaker assemblies.
  • Industrial low-voltage distribution switchboards.
  • Electrical systems with high prospective short-circuit currents.
  • Main and sub-distribution panels.
  • Manufacturing and process plant electrical systems.
  • Commercial and infrastructure power distribution.
  • Replacement or configuration of compatible Tmax T5 MCCB assemblies.

Technical Specifications

Series SACE Tmax T5
Order code 1SDA054579R1
EAN 8015644556778
Product type MCCB breaking part
Frame T5 400
Short-circuit performance level H
Rated uninterrupted current (Iu) 400 A
Number of poles 3
Rated operational voltage up to 690 V AC / 750 V DC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 8 kV
Icu / Ics at 220–230 V AC 100 kA / 100 kA
Icu / Ics at 380–415 V AC 70 kA / 70 kA
Icu / Ics at 440 V AC 65 kA / 65 kA
Icu / Ics at 500 V AC 50 kA / 50 kA
Icu / Ics at 690 V AC 40 kA / 40 kA
DC breaking capacity at 250 V DC 70 kA with 2 poles in series
DC breaking capacity at 500 V DC 50 kA with 2 poles in series
DC breaking capacity at 750 V DC 36 kA with 3 poles in series
Rated short-time withstand current (Icw) 5 kA for 1 s
Mounting Fixed
Terminal position Front
Operating mechanism Toggle handle
Integrated earth-leakage protection No
Integrated motor operator No
Optional motor operator Yes
Protection rating IP20
Standard IEC

Frequently Asked Questions

What is the ABB 1SDA054579R1?

The ABB 1SDA054579R1 is a T5H 400 fixed three-pole breaking part with front terminals for the ABB SACE Tmax T5 moulded case circuit breaker platform.

What is the current rating of the ABB T5H 400 breaking part?

The T5H 400 breaking unit has a rated uninterrupted current of 400 A.

What is the breaking capacity of the ABB T5H 400 at 400 V AC?

The T5H 400 provides both an ultimate short-circuit breaking capacity and service short-circuit breaking capacity of 70 kA at 400 V AC.

What is the breaking capacity of the ABB T5H 400 at 690 V AC?

At 690 V AC, the T5H 400 has an ultimate and service short-circuit breaking capacity of 40 kA.

How many poles does the ABB 1SDA054579R1 have?

The breaking unit has a three-pole configuration and is designed for fixed installation with front terminals.

Can the ABB T5H 400 breaking part be used on DC circuits?

Yes. The breaking unit is rated for operation up to 750 V DC, with the applicable poles connected in series according to the system voltage and ABB installation requirements.

Trusted by Electrical Professionals Worldwide

ABB SACE Tmax circuit breaker components are used in demanding industrial and commercial power-distribution systems worldwide, providing robust fault interruption, configurable protection and dependable performance for critical electrical installations.