ABB 1SDA054519R1 T4V 250 PR222DS/P-LSI is a 250 A three-pole fixed moulded case circuit breaker with front terminals for copper cables, LSI electronic protection and ultimate breaking capacities of 20 kA at 1000 V AC and 12 kA at 1150 V AC.
£3,667.65
The ABB 1SDA054519R1 is a specialist SACE Tmax T4V moulded case circuit breaker (MCCB) designed for demanding AC power distribution applications operating at elevated voltages. This three-pole fixed circuit breaker combines a 250 A rated current with ABB's advanced PR222DS/P-LSI electronic trip unit.
The PR222DS/P-LSI electronic release provides long-time overload, short-time short-circuit and instantaneous short-circuit protection. These LSI protection functions provide greater flexibility for protection coordination than basic thermomagnetic or instantaneous-only releases, making the breaker particularly useful in specialist industrial distribution systems.
This T4V configuration is designed for operation at up to 1,150 V AC. The V performance level provides an ultimate short-circuit breaking capacity of 20 kA at 1,000 V AC and 12 kA at 1,150 V AC. Fixed mounting and front terminals for copper cables support permanent integration into purpose-built switchboards and high-voltage AC distribution assemblies.
The ABB SACE Tmax T4 range includes specialist circuit breakers engineered for AC systems operating at voltages beyond conventional low-voltage distribution levels. The PR222DS/P-LSI release fitted to the 1SDA054519R1 provides long-time, short-time and instantaneous protection, supporting selective and coordinated protection of substantial three-phase circuits.
The T4V performance level provides 20 kA ultimate breaking capacity at 1,000 V AC and 12 kA at 1,150 V AC. Together with its 250 A rating, fixed construction and front copper-cable terminals, this makes the breaker a strong choice for specialist industrial switchboards, power conversion systems and other elevated-voltage AC distribution assemblies.
| Series | SACE Tmax T4 |
|---|---|
| ABB order code | 1SDA054519R1 |
| Product group | 310511-T-Max T4 - T8 |
| Product type | Moulded case circuit breaker (MCCB) |
| Frame | T4 250 |
| Performance level | V |
| Rated current (In) | 250 A |
| Number of poles | 3P |
| Trip unit | PR222DS/P-LSI electronic release |
| Protection functions | Long-time, short-time and instantaneous |
| Maximum application voltage | 1,150 V AC |
| Ultimate short-circuit breaking capacity (Icu) at 1,000 V AC | 20 kA |
| Ultimate short-circuit breaking capacity (Icu) at 1,150 V AC | 12 kA |
| Mounting type | Fixed |
| Terminal type | Front terminals for copper cables |
| Net weight | 2.5 kg |
| EAN | 8015644556211 |
The ABB 1SDA054519R1 is a three-pole moulded case circuit breaker designed for advanced electronic protection and switching in specialist industrial AC distribution systems operating at up to 1,150 V AC.
The circuit breaker has a rated current of 250 A and uses an ABB PR222DS/P-LSI electronic trip unit.
The PR222DS/P-LSI electronic trip unit provides long-time overload, short-time short-circuit and instantaneous short-circuit protection.
The T4V circuit breaker provides an ultimate short-circuit breaking capacity of 20 kA at 1,000 V AC and 12 kA at 1,150 V AC.
The 1SDA054519R1 is a fixed three-pole circuit breaker with front terminals for copper cables, designed for permanent installation within suitable electrical distribution assemblies.
ABB SACE Tmax moulded case circuit breakers provide dependable protection for demanding power distribution systems, with specialist T4V configurations combining advanced electronic protection with operation at AC voltages up to 1,150 V.
We use cookies