ABB 1SDA054482R1 SACE Tmax T5H moulded case circuit breaker with 400 A rating, TMA thermal magnetic release, four-pole fixed construction, front terminals and fully rated neutral for industrial power distribution.

SKU: 1SDA054482R1Alt SKU: T5H 400 TMA 400-4000 4p F F InN=100%InMPN: 1SDA054482R1
Price
List Price £3,460.91 ex VAT
Your Price (ex VAT) Save 25%
£2,595.68 25% OFF
You save £865.23 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £2,595.68
Trade pricing is personalised to your account

Manufacturer Lead Time

£2,595.68

Why Choose the ABB 1SDA054482R1 Tmax T5H Moulded Case Circuit Breaker?

The ABB 1SDA054482R1 is a high performance Tmax T5H moulded case circuit breaker (MCCB) designed to provide dependable protection for low voltage electrical distribution systems. As part of the proven ABB SACE Tmax T series, this circuit breaker is engineered for industrial, commercial and infrastructure applications where reliable overload and short circuit protection is essential.

This model features a 400 A rated current within a 400 A frame size and is fitted with a TMA thermal magnetic release. The release provides overload protection and adjustable instantaneous short circuit protection from 2000 to 4000 A, making it suitable for demanding distribution and machinery protection applications.

With a fixed four-pole construction, front terminals and a fully rated neutral, the ABB 1SDA054482R1 is ideal for three-phase plus neutral installations, switchboards, distribution panels and industrial feeder circuits requiring robust and reliable circuit protection.

Key Advantages

  • High performance ABB Tmax T5H moulded case circuit breaker.
  • 400 A rated current in a 400 A frame size.
  • Four-pole fixed configuration with fully rated neutral.
  • TMA thermal magnetic trip unit with adjustable short circuit protection.
  • Front terminal connections for switchboard and panel mounting.
  • High breaking capacity for dependable fault interruption.

Key Features

  • ABB SACE Tmax T series.
  • Model: T5H 400 TMA 400-4000.
  • 400 A rated current.
  • 400 A frame size.
  • Four-pole (4P) MCCB configuration.
  • Fully rated neutral InN=100%In.
  • TMA thermal magnetic release.
  • Designed in accordance with IEC 60947-2.

Reliable Protection for Industrial Power Distribution

The ABB Tmax T5H range is designed to protect electrical systems by detecting overload and short circuit conditions quickly and reliably. The TMA thermal magnetic release provides robust protection for distribution circuits, helping reduce equipment damage, improve safety and maintain operational continuity.

The ABB 1SDA054482R1 is well suited to applications requiring dependable four-pole protection with a fully rated neutral. Its fixed front terminal design, high breaking capacity and proven ABB engineering make it a reliable choice for low voltage electrical infrastructure and three-phase plus neutral distribution systems.

Typical Applications

  • Industrial power distribution systems.
  • Main incoming and outgoing feeders.
  • Three-phase plus neutral electrical installations.
  • Commercial distribution boards.
  • Motor control centres.
  • Infrastructure and utility power systems.

Technical Specifications

Tick the specs you need, then view products that match.

Current 400 A
Phase Three Phase
Poles 4-pole
Device Type MCCB
Breaking Capacity 70 kA
Trip Unit Thermal-magnetic
Manufacturer ABB
Series SACE Tmax T
Model T5H 400 TMA 400-4000 4p F F InN=100%In
Product code 1SDA054482R1
EAN 8015644555191
Product type Moulded case circuit breaker (MCCB)
Rated current (In) 400 A
Rated uninterrupted current (Iu) 400 A
Frame size T5 400
Number of poles 4
Neutral rating Fully rated neutral, InN=100%In
Trip unit TMA thermal magnetic release
Release type Thermal magnetic
Instantaneous setting 2000-4000 A
Rated operational voltage 690 V AC / 750 V DC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 8 kV
Rated ultimate breaking capacity (Icu) 70 kA at 400 V AC
Rated service breaking capacity (Ics) 70 kA at 400 V AC
Short-time withstand current (Icw) 5 kA for 1 s
Terminal type Fixed front terminals
Mounting Panel mounted
Electrical durability 7,000 cycles
Mechanical durability 20,000 cycles
Standards IEC 60947-2
Dimensions (H × W × D) 205 × 186 × 103.5 mm
Weight Approx. 5.8 kg

Frequently Asked Questions

What is the ABB 1SDA054482R1 used for?

It is used to protect low voltage electrical distribution systems against overloads and short circuits in industrial, commercial and infrastructure installations.

What is the rated current of this MCCB?

The ABB 1SDA054482R1 has a rated current of 400 A.

How many poles does this circuit breaker have?

This model has a four-pole (4P) configuration, making it suitable for three-phase plus neutral electrical systems.

What does InN=100%In mean?

It means the neutral pole is fully rated, so the neutral current rating is equal to the rated phase current of the breaker.

Which trip unit is fitted?

The breaker is fitted with a TMA thermal magnetic release with adjustable short circuit protection from 2000 to 4000 A.