1SDA054432R1 ABB T5V630 PR221DS-LS/I 630 A 4-Pole MCCB

1SDA054432R1 ABB T5V630 PR221DS-LS/I 630 A 4-Pole MCCB

ABB 1SDA054432R1 SACE Tmax T5V630 fixed four-pole 630 A moulded case circuit breaker with PR221DS-LS/I electronic protection, selectable neutral protection and 200 kA ultimate breaking capacity at 380–415 V AC.

SKU: 1SDA054432R1Alt SKU: T5V630R630MPN: 1SDA054432R1
Price
List Price £7,991.08 ex VAT
Your Price (ex VAT) Save 25%
£5,993.31 25% OFF
You save £1,997.77 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £5,993.31
Trade pricing is personalised to your account

Manufacturer Lead Time

£5,993.31

Why Choose the ABB T5V630 PR221DS-LS/I 630 A 1SDA054432R1 Circuit Breaker?

The ABB 1SDA054432R1 is a high-performance SACE Tmax T5V 630 moulded case circuit breaker (MCCB) designed for protection and isolation in demanding low-voltage power distribution systems. Configured as a fixed four-pole breaker with front terminals, it combines a 630 A rated current with ABB's PR221DS-LS/I electronic trip unit.

Part of the established ABB SACE Tmax T5 series, the T5V630 provides electronic LS/I protection for overload and short-circuit conditions. Its electronic release offers adjustable thermal protection from 0.4–1 × In and adjustable magnetic protection from 1–10 × In, allowing the breaker to be coordinated with cables, feeders and connected equipment.

The T5V performance level is designed for installations with exceptionally high prospective fault currents, delivering an ultimate short-circuit breaking capacity of 200 kA at 380–415 V AC. The four-pole configuration also provides selectable neutral protection settings of OFF, 50% or 100%, making the 1SDA054432R1 a flexible solution for demanding three-phase four-wire distribution systems.

Key Advantages

  • High-performance ABB SACE Tmax T5V 630 moulded case circuit breaker.
  • 630 A rated current for substantial low-voltage distribution circuits.
  • Four-pole configuration for three-phase four-wire systems.
  • PR221DS-LS/I electronic trip unit with adjustable electronic protection.
  • Thermal protection adjustable from 0.4–1 × In.
  • Magnetic protection adjustable from 1–10 × In.
  • Selectable OFF, 50% or 100% neutral protection.
  • 200 kA ultimate breaking capacity at 380–415 V AC.
  • Fixed mounting with front terminals for practical switchboard integration.

Key Features

  • ABB SACE Tmax T5V 630 circuit breaker platform.
  • 630 A rated current.
  • 4-pole construction.
  • PR221DS-LS/I electronic release.
  • Long-time overload protection.
  • Short-circuit protection with adjustable trip threshold.
  • Adjustable thermal setting from 252–630 A.
  • Adjustable magnetic setting from 630–6,300 A.
  • Selectable neutral protection: OFF / 50% / 100%.
  • 200 kA Icu at 380–415 V AC.
  • Fixed circuit breaker configuration with front terminals.

Reliable Circuit Protection for Power Distribution

The ABB SACE Tmax T5V platform is engineered for demanding low-voltage power distribution where substantial current capacity and very high short-circuit interruption performance are required. With a 630 A rated current and 200 kA Icu at 380–415 V AC, the 1SDA054432R1 is particularly suited to high-current feeders and distribution systems with significant prospective fault levels.

Its PR221DS-LS/I electronic trip unit provides adjustable overload and short-circuit protection, while selectable neutral protection adds flexibility for four-wire distribution systems. Together with fixed mounting and front terminals, these characteristics make the breaker suitable for integration into industrial switchboards, commercial distribution panels and infrastructure power systems.

Typical Applications

  • Industrial low-voltage power distribution systems.
  • Main and sub-main distribution switchboards.
  • High-current three-phase four-wire feeder circuits.
  • Manufacturing and process installations.
  • Commercial and infrastructure power distribution.
  • Installations with very high prospective short-circuit currents.

Technical Specifications

Series SACE Tmax T5
ABB order code 1SDA054432R1
Product group 310511-T-Max T4 - T8
Product type Moulded case circuit breaker (MCCB)
Frame T5 630
Performance level V
Rated current (In) 630 A
Number of poles 4
Trip unit PR221DS-LS/I electronic release
Protection functions LS/I — long-time overload and short-circuit protection
Thermal protection adjustment 0.4–1 × In (252–630 A)
Magnetic protection adjustment 1–10 × In (630–6,300 A)
Neutral protection setting OFF / 50% / 100%
Rated operational voltage up to 690 V AC
Ultimate breaking capacity (Icu) at 220/230 V AC 200 kA
Ultimate breaking capacity (Icu) at 380/415 V AC 200 kA
Ultimate breaking capacity (Icu) at 440 V AC 180 kA
Ultimate breaking capacity (Icu) at 500 V AC 150 kA
Ultimate breaking capacity (Icu) at 690 V AC 80 kA
Mounting type Fixed
Terminal type Front terminals
Dimensions (H × W × D) 205 × 165 × 103.5 mm
Weight approx. 4.7 kg
EAN 8015644555368

Frequently Asked Questions

What is the ABB 1SDA054432R1 used for?

The ABB 1SDA054432R1 is a 630 A four-pole electronic moulded case circuit breaker designed to protect and isolate demanding low-voltage power distribution circuits against overload and short-circuit conditions.

What is the current rating of the ABB T5V630 1SDA054432R1?

The circuit breaker has a rated current of 630 A and is based on the ABB SACE Tmax T5V 630 platform.

What protection does the PR221DS-LS/I trip unit provide?

The PR221DS-LS/I provides electronic overload and short-circuit protection, with thermal protection adjustable from 0.4–1 × In and magnetic protection adjustable from 1–10 × In.

What is the breaking capacity of the ABB 1SDA054432R1?

The T5V performance version provides an ultimate short-circuit breaking capacity (Icu) of 200 kA at 380–415 V AC, making it suitable for systems with exceptionally high prospective fault currents.

Does the ABB 1SDA054432R1 provide neutral protection?

Yes. This four-pole version provides selectable OFF, 50% or 100% neutral protection settings, allowing the neutral protection level to be configured for the distribution system.