1SDA054427R1 ABB T5L 630 PR222DS/P-LSIG 630 A 4-Pole MCCB

1SDA054427R1 ABB T5L 630 PR222DS/P-LSIG 630 A 4-Pole MCCB

ABB 1SDA054427R1 T5L 630 PR222DS/P-LSIG is a 630 A four-pole fixed moulded case circuit breaker with front terminals, adjustable LSIG electronic protection and 120 kA ultimate short-circuit breaking capacity at 380–415 V AC.

SKU: 1SDA054427R1MPN: 1SDA054427R1
Price
List Price £8,337.16 ex VAT
Your Price (ex VAT) Save 25%
£6,252.87 25% OFF
You save £2,084.29 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £6,252.87
Trade pricing is personalised to your account

Manufacturer Lead Time

£6,252.87

Why Choose the ABB T5L 630 PR222DS/P-LSIG Circuit Breaker?

The ABB T5L 630 PR222DS/P-LSIG, order code 1SDA054427R1, is a high-performance 4-pole moulded case circuit breaker (MCCB) designed for protection and switching in demanding low-voltage power distribution systems. Part of the ABB SACE Tmax T5 series, it combines a 630 A rated current with an advanced PR222DS/P-LSIG solid-state electronic trip unit.

The PR222DS/P-LSIG electronic release provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection. Its adjustable protection settings allow effective coordination with conductors, loads and other protective devices throughout industrial and commercial distribution networks.

The T5L performance level provides an ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC. With its 4-pole fixed construction and front terminals, the 1SDA054427R1 is well suited to three-phase plus neutral switchboards, main and feeder circuits and installations requiring comprehensive LSIG electronic protection.

Key Advantages

  • ABB SACE Tmax T5 MCCB for demanding power distribution applications.
  • 630 A rated current and rated uninterrupted current.
  • PR222DS/P-LSIG electronic trip unit with comprehensive adjustable protection.
  • Long-time, short-time, instantaneous and earth-fault protection functions.
  • Overload adjustment from 252–630 A.
  • Short-time delayed short-circuit adjustment from 378–6300 A.
  • Instantaneous short-circuit adjustment from 945–5985 A.
  • Earth-fault protection adjustable from 0.2–1 × In.
  • 120 kA Icu at 380–415 V AC for demanding fault levels.
  • 4-pole configuration for three-phase plus neutral distribution systems.

Key Features

  • ABB SACE Tmax T5L 630 platform.
  • 630 A rated current (In).
  • 630 A rated uninterrupted current (Iu).
  • PR222DS/P-LSIG solid-state electronic release.
  • LSIG protection: long-time, short-time, instantaneous and earth fault.
  • Configurable neutral protection.
  • 4-pole configuration.
  • 690 V AC rated operational voltage.
  • Fixed mounting.
  • Front terminals.

Advanced LSIG Electronic Circuit Protection

The ABB PR222DS/P-LSIG electronic trip unit combines four principal protection functions. Long-time protection responds to sustained overloads, short-time protection provides a configurable delayed response to short circuits, instantaneous protection rapidly disconnects severe faults, and the integrated earth-fault function adds protection against current flowing to earth.

The adjustable LSIG functions allow the T5L 630 to be coordinated with the wider electrical protection system. In this four-pole configuration, configurable neutral protection further supports three-phase plus neutral networks, making the breaker a flexible solution for high-current industrial and commercial distribution.

Typical Applications

  • Industrial low-voltage distribution switchboards.
  • Main incoming and feeder circuit protection.
  • Three-phase plus neutral distribution systems.
  • Manufacturing and process plants.
  • Commercial building electrical distribution.
  • Infrastructure and utility installations.
  • Systems requiring adjustable LSIG electronic protection.

Technical Specifications

Series SACE Tmax T5
ABB order code 1SDA054427R1
EAN 8015644555313
Product type Moulded case circuit breaker (MCCB)
Frame T5
Performance level L
Rated uninterrupted current (Iu) 630 A
Rated current (In) 630 A
Trip unit PR222DS/P-LSIG electronic
Protection functions L, S, I, G
Overload release adjustment 252–630 A
Short-time delayed short-circuit adjustment 378–6300 A
Instantaneous short-circuit adjustment 945–5985 A
Earth-fault adjustment 0.2–1 × In
Neutral protection settings OFF / 50% / 100%
Number of poles 4
Rated operational voltage 690 V AC
Ultimate short-circuit breaking capacity (Icu) at 220–230 V AC 200 kA
Ultimate short-circuit breaking capacity (Icu) at 380–415 V AC 120 kA
Ultimate short-circuit breaking capacity (Icu) at 440 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 500 V AC 85 kA
Ultimate short-circuit breaking capacity (Icu) at 690 V AC 70 kA
Degree of protection IP20
Mounting Fixed
Terminal arrangement Front terminals
Power loss 41 W
Dimensions (W × H × D) 186 × 205 × 103.5 mm
Net weight 6.2 kg

Frequently Asked Questions

What is the ABB 1SDA054427R1?

The ABB 1SDA054427R1 is a Tmax T5L 630 fixed 4-pole moulded case circuit breaker with front terminals, a 630 A rating and a PR222DS/P-LSIG electronic trip unit.

What protection functions does the PR222DS/P-LSIG provide?

The PR222DS/P-LSIG provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection, represented by the LSIG designation.

What are the adjustable overcurrent protection ranges?

The overload release is adjustable from 252–630 A, the short-time delayed short-circuit protection from 378–6300 A, and the instantaneous short-circuit protection from 945–5985 A.

What is the breaking capacity of ABB 1SDA054427R1?

The T5L 630 provides an ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC.

Does the ABB 1SDA054427R1 provide earth-fault protection?

Yes. The PR222DS/P-LSIG release includes an earth-fault protection function with an adjustable threshold from 0.2–1 × In, in addition to its long-time, short-time and instantaneous protection functions.

Trusted ABB Electronic Circuit Protection

ABB SACE Tmax moulded case circuit breakers combine high short-circuit interruption capability, adjustable electronic protection and robust construction for dependable industrial and commercial low-voltage power distribution.