1sda054407r1  t5s 630 pr222ds/p-lsig in=630 3 pole abb mccb

1sda054407r1 t5s 630 pr222ds/p-lsig in=630 3 pole abb mccb

ABB 1SDA054407R1 SACE Tmax T5S moulded case circuit breaker with 630 A rating, three-pole configuration, fixed front terminals and PR222DS/P-LSIG electronic trip unit for industrial power distribution.

SKU: 1SDA054407R1Alt SKU: T5S 630 PR222DS/P-LSIG In=630 3p F FMPN: 1SDA054407R1
Price
List Price £5,254.88 ex VAT
Your Price (ex VAT) Save 25%
£3,941.16 25% OFF
You save £1,313.72 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £3,941.16
Trade pricing is personalised to your account

Manufacturer Lead Time

£3,941.16

Why Choose the ABB 1SDA054407R1 Tmax T5S Moulded Case Circuit Breaker?

The ABB 1SDA054407R1 is a high-performance SACE Tmax T5S moulded case circuit breaker (MCCB) designed to provide reliable circuit protection for industrial power distribution, switchboards, machinery and commercial electrical installations. As part of the proven ABB Tmax T series, it combines compact construction with advanced electronic protection for demanding three-phase systems.

This MCCB features a 630 A rated current, three-pole configuration and a PR222DS/P-LSIG electronic trip unit, offering long-time, short-time, instantaneous and ground fault protection functions. The fixed design with front terminals makes it suitable for integration into electrical panels, distribution boards and switchgear assemblies.

With operation up to 690 V AC and a strong short-circuit breaking capacity, the ABB 1SDA054407R1 is ideal for installations requiring dependable protection, accurate fault detection and improved safety across industrial low voltage electrical networks.

Key Advantages

  • 630 A moulded case circuit breaker for industrial power distribution.
  • Three-pole fixed design for three-phase electrical systems.
  • PR222DS/P-LSIG electronic trip unit with ground fault protection.
  • Provides long-time, short-time, instantaneous and ground fault protection.
  • Front terminal connections for practical switchboard installation.
  • Compact ABB Tmax T5 frame supports efficient panel layouts.
  • Suitable for critical distribution, machinery and infrastructure applications.

Key Features

  • ABB SACE Tmax T5S series.
  • Product code: 1SDA054407R1.
  • Rated current: 630 A.
  • Three-pole (3P) configuration.
  • PR222DS/P-LSIG electronic release.
  • Fixed mounting with front terminals.
  • Rated operational voltage: up to 690 V AC.
  • Designed for AC industrial power distribution applications.

Advanced Protection for Industrial Electrical Networks

Moulded case circuit breakers such as the ABB Tmax T5S help protect electrical systems by interrupting overload and short-circuit conditions before they can damage cables, equipment or connected loads. Electronic trip technology provides accurate adjustment and improved coordination across low voltage distribution networks.

The PR222DS/P-LSIG release provides long-time, short-time, instantaneous and ground fault protection, making this MCCB suitable for installations where enhanced selectivity, operational safety and fault monitoring are required.

Typical Applications

  • Industrial power distribution panels.
  • Main and sub-distribution switchboards.
  • Motor control centres.
  • Commercial and industrial electrical installations.
  • Generator, transformer and feeder protection.
  • OEM machinery and process equipment.
  • Infrastructure, utilities and building services.

Technical Specifications

Tick the specs you need, then view products that match.

Current 630 A
Phase Three Phase
Poles 3-pole
Device Type MCCB
Breaking Capacity 50 kA
Trip Unit Electronic
Manufacturer ABB
Series SACE Tmax T
Model T5S 630 PR222DS/P-LSIG In=630 3P F F
Product code 1SDA054407R1
Product type Moulded Case Circuit Breaker (MCCB)
Rated current (In) 630 A
Rated uninterrupted current (Iu) 630 A
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 8 kV
Number of poles 3
Trip unit PR222DS/P-LSIG Electronic
Release type Electronic / solid-state
Short-circuit performance level S
Rated ultimate breaking capacity 50 kA at 415 V AC
Rated service breaking capacity 50 kA at 415 V AC
Protection functions LSIG
Mounting Fixed
Terminal type Front terminals
Standards IEC 60947
Dimensions (H × W × D) 205 × 140 × 103.5 mm
Weight approx. 5 kg

Frequently Asked Questions

What is the ABB 1SDA054407R1 used for?

It is used to protect industrial electrical circuits, switchboards and distribution systems against overloads, short circuits and ground fault conditions.

What is the rated current of this MCCB?

The ABB 1SDA054407R1 has a rated current of 630 A.

Which trip unit is included?

This model is fitted with a PR222DS/P-LSIG electronic trip unit, providing long-time, short-time, instantaneous and ground fault protection.

How many poles does this circuit breaker have?

The breaker has a three-pole (3P) configuration for use in three-phase electrical systems.

Where is this MCCB typically installed?

It is typically installed in electrical switchboards, distribution panels, motor control centres, industrial control panels and power distribution systems.

Trusted by Electrical Professionals Worldwide

ABB SACE Tmax moulded case circuit breakers are trusted by panel builders, electrical engineers and industrial maintenance teams for reliable protection, compact installation and proven performance in demanding power distribution applications.