Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA054327R1 Tmax T5N 400 moulded case circuit breaker with PR221DS-I electronic trip unit, 400 A rated current, four-pole configuration and fixed front terminals for industrial power distribution.
£2,375.44
The ABB 1SDA054327R1 is a robust and reliable Tmax T5N moulded case circuit breaker (MCCB) designed for industrial power distribution, electrical switchboards and OEM control panel applications. Featuring a 400 A rated current, four-pole configuration and PR221DS-I electronic trip unit, this MCCB provides dependable protection against short circuit conditions in demanding low voltage installations.
As part of the proven ABB SACE Tmax T series, this circuit breaker combines high breaking performance, compact dimensions and durable ABB engineering. The fixed installation design with front terminals allows straightforward integration into electrical panels, switchgear assemblies and machinery protection systems.
With a rated operational voltage of up to 690 V AC and compliance with IEC 60947, the ABB 1SDA054327R1 is ideal for use in commercial and industrial electrical systems where safe, consistent and efficient circuit protection is essential.
The ABB Tmax T5N range is engineered to protect low voltage electrical installations against fault conditions while supporting reliable power distribution. The PR221DS-I electronic release provides accurate instantaneous protection, helping safeguard cables, equipment and downstream electrical circuits.
Its compact construction, high mechanical durability and proven ABB design make the 1SDA054327R1 a strong choice for panel builders, electrical contractors, industrial engineers and OEMs requiring dependable MCCB protection in demanding environments.
Tick the specs you need, then view products that match.
| Current | 400 A | |
|---|---|---|
| Phase | Three Phase | |
| Poles | 4-pole | |
| Device Type | MCCB | |
| Breaking Capacity | 36 kA | |
| Trip Unit | Electronic | |
| Manufacturer | ABB | |
| Series | SACE Tmax T | |
| Model | T5N 400 PR221DS-I In=400 4P F F | |
| Product code | 1SDA054327R1 | |
| Product type | Moulded Case Circuit Breaker (MCCB) | |
| Rated current (In) | 400 A | |
| Frame size | 400 A | |
| Number of poles | 4 | |
| Trip unit | PR221DS-I electronic release | |
| Rated operational voltage | Up to 690 V AC | |
| Rated insulation voltage (Ui) | 1000 V | |
| Rated impulse withstand voltage (Uimp) | 8 kV | |
| Breaking capacity | 36 kA at 400 V AC | |
| Terminal type | Fixed front terminals | |
| Standards | IEC 60947 | |
| Dimensions (H × W × D) | approx. 205 × 186 × 103.5 mm | |
| Weight | approx. 6.09 kg |
It is used to protect low voltage electrical circuits, switchboards and industrial distribution systems against short circuit and fault conditions.
The ABB 1SDA054327R1 has a 400 A rated current.
This model has a four-pole (4P) configuration, making it suitable for three-phase systems with neutral protection requirements.
It is fitted with a PR221DS-I electronic trip unit for accurate instantaneous protection.
It is commonly installed in electrical switchboards, power distribution panels, motor control centres and OEM machinery control panels.
ABB SACE Tmax moulded case circuit breakers are trusted by electrical engineers, panel builders and industrial operators worldwide for reliable circuit protection, strong performance and long-term dependability.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.