ABB 1SDA054312R1 T4L 250 MA is a 200 A three-pole fixed moulded case circuit breaker for motor protection with front terminals, an adjustable 1,200–2,800 A magnetic release and a 120 kA ultimate breaking capacity at 380–415 V AC.
£1,714.56
The ABB 1SDA054312R1 is a high-performance SACE Tmax T4L moulded case circuit breaker (MCCB) for motor protection, designed to provide reliable short-circuit protection and switching in industrial low-voltage electrical systems. Part of the proven ABB SACE Tmax T4 series, this three-pole circuit breaker combines a 250 A frame with a 200 A MA magnetic-only trip unit.
The MA release provides instantaneous magnetic short-circuit protection without thermal overload protection, making it particularly suitable for motor circuits where overload protection is provided separately by an overload relay or electronic motor protection device. Its adjustable magnetic release operates over a range of 1,200–2,800 A, allowing the protection threshold to accommodate motor starting currents while providing rapid interruption during severe short-circuit conditions.
With a rated current of 200 A, three-pole construction, fixed installation and front terminals, the T4L 250 MA 200-2800 is designed for integration into motor control centres, industrial switchboards and machinery panels. The T4L performance level provides an ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC, delivering robust fault protection for demanding industrial motor applications.
Magnetic-only moulded case circuit breakers such as the ABB SACE Tmax T4L MA are designed for motor circuits where overload protection is handled by a separate protective device. The MA release responds rapidly to high short-circuit currents while its adjustable threshold allows the breaker to accommodate the temporary inrush currents associated with motor starting.
The 1,200–2,800 A magnetic adjustment range provides flexibility when coordinating the 1SDA054312R1 with motor starters, contactors and overload protection devices. Combined with the T4L's 120 kA breaking capacity at 380–415 V AC, this makes the breaker well suited to demanding industrial motor control centres and machinery installations where high prospective fault currents may be present.
| Series | SACE Tmax T4 |
|---|---|
| ABB order code | 1SDA054312R1 |
| Product group | 310511-T-Max T4 - T8 |
| Product type | Moulded case circuit breaker (MCCB) for motor protection |
| Frame | T4 250 |
| Short-circuit performance level | L |
| Rated current (In) | 200 A |
| Rated uninterrupted current (Iu) | 250 A |
| Number of poles | 3P |
| Trip unit | MA magnetic-only release |
| Instantaneous magnetic trip range (I3) | 1,200–2,800 A |
| Rated operational voltage | 690 V AC / 750 V DC |
| Rated insulation voltage (Ui) | 1,000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Ultimate short-circuit breaking capacity (Icu) at 220–230 V AC | 200 kA |
| Ultimate short-circuit breaking capacity (Icu) at 380–415 V AC | 120 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 85 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 70 kA |
| Mounting type | Fixed |
| Terminal type | Front terminals |
| Electrical durability | 8,000 operating cycles |
| Mechanical durability | 20,000 operating cycles |
| Power loss | 9.9 W per pole at rated operating conditions |
| Dimensions (H × W × D) | 205 × 105 × 103.5 mm |
| Net weight | approx. 2.35 kg |
| Standards | IEC 60947 |
| EAN | 8015644554095 |
The ABB 1SDA054312R1 is a three-pole moulded case circuit breaker for motor protection, providing adjustable magnetic short-circuit protection for industrial motor circuits.
The circuit breaker has a rated current of 200 A and is built on the ABB SACE Tmax T4 250 A frame.
The MA release provides an adjustable instantaneous magnetic trip range of 1,200–2,800 A, allowing short-circuit protection to be coordinated with motor starting characteristics.
No. The MA trip unit is magnetic-only and provides short-circuit protection, so motor overload protection should be provided by a suitable separate overload relay or motor protection device.
The T4L circuit breaker provides an ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC, making it suitable for demanding industrial motor circuits with high prospective fault currents.