ABB 1SDA054311R1 T4L 250 MA is a 160 A three-pole fixed moulded case circuit breaker for motor protection with front terminals, an adjustable 960–2,240 A magnetic release and a 120 kA ultimate breaking capacity at 380–415 V AC.

SKU: 1SDA054311R1Alt SKU: T4L250MA160,1SDA05MPN: 1SDA054311R1
Price
List Price £1,730.79 ex VAT
Your Price (ex VAT) Save 25%
£1,298.09 25% OFF
You save £432.70 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,298.09
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,298.09

Why Choose the ABB T4L 250 MA 160-2240 3P F F Circuit Breaker?

The ABB 1SDA054311R1 is a high-performance SACE Tmax T4L moulded case circuit breaker (MCCB) for motor protection, designed to provide reliable short-circuit protection and switching in industrial low-voltage electrical systems. Part of the proven ABB SACE Tmax T4 series, this three-pole circuit breaker combines a 250 A frame with a 160 A MA magnetic-only trip unit.

Unlike a conventional thermomagnetic MCCB, the MA release provides magnetic short-circuit protection without thermal overload protection, making it particularly suitable for motor circuits where overload protection is provided separately by a motor overload relay or electronic motor protection device. The adjustable instantaneous magnetic release has a setting range of 960–2,240 A, enabling protection to be coordinated with motor starting currents and the characteristics of the protected circuit.

With a 160 A rated current, three-pole construction, fixed installation and front terminals, the T4L 250 MA 160-2240 is designed for straightforward integration into motor control centres, switchboards and industrial distribution panels. The T4L performance level provides an ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC, delivering robust fault protection in demanding motor applications.

Key Advantages

  • High-performance ABB SACE Tmax T4L motor-protection circuit breaker.
  • 160 A rated current for industrial motor circuits.
  • Three-pole configuration suitable for three-phase motors and electrical systems.
  • MA magnetic-only trip unit specifically suited to motor protection applications.
  • Adjustable instantaneous magnetic protection from 960–2,240 A.
  • High ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC.
  • 690 V AC / 750 V DC rated operational voltage.
  • Fixed installation with front terminals for straightforward switchboard and motor control centre integration.

Key Features

  • ABB SACE Tmax T4 series.
  • T4L 250 frame with L breaking-capacity performance level.
  • 160 A rated current.
  • 250 A rated uninterrupted frame current.
  • 3-pole circuit breaker configuration.
  • MA magnetic-only release for short-circuit protection.
  • 960–2,240 A adjustable instantaneous magnetic trip range.
  • 120 kA Icu at 380–415 V AC.
  • 1,000 V rated insulation voltage.
  • 8 kV rated impulse withstand voltage.
  • Fixed circuit-breaker construction with front terminals.
  • Designed for motor circuits with separate overload protection.

Reliable Short-Circuit Protection for Industrial Motors

Magnetic-only moulded case circuit breakers such as the ABB SACE Tmax T4L MA are designed for motor circuits where overload protection is handled by a separate protective device. The MA release responds rapidly to high short-circuit currents while its adjustable threshold allows the breaker to accommodate the temporary inrush currents associated with motor starting.

The 960–2,240 A magnetic adjustment range provides flexibility when coordinating the 1SDA054311R1 with motor starters, contactors and overload protection devices. Combined with the T4L's 120 kA breaking capacity at 380–415 V AC, this makes the breaker well suited to demanding industrial motor control centres and machinery installations where high prospective fault currents may be present.

Typical Applications

  • Three-phase industrial motor protection.
  • Motor control centres and starter assemblies.
  • Pumps, fans and compressor motor circuits.
  • Conveyors and material handling equipment.
  • Manufacturing and process machinery.
  • Industrial switchboards and control panels.
  • Motor circuits using separate overload relays.
  • Installations with high prospective short-circuit currents.

Technical Specifications

Series SACE Tmax T4
ABB order code 1SDA054311R1
Product group 310511-T-Max T4 - T8
Product type Moulded case circuit breaker (MCCB) for motor protection
Frame T4 250
Performance level L
Rated current (In) 160 A
Rated uninterrupted current (Iu) 250 A
Number of poles 3P
Trip unit MA magnetic-only release
Instantaneous magnetic trip range (I3) 960–2,240 A
Rated operational voltage 690 V AC / 750 V DC
Rated insulation voltage (Ui) 1,000 V
Rated impulse withstand voltage (Uimp) 8 kV
Ultimate short-circuit breaking capacity (Icu) at 220–230 V AC 200 kA
Ultimate short-circuit breaking capacity (Icu) at 380–415 V AC 120 kA
Ultimate short-circuit breaking capacity (Icu) at 440 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 500 V AC 85 kA
Ultimate short-circuit breaking capacity (Icu) at 690 V AC 70 kA
Mounting type Fixed
Terminal type Front terminals
Electrical durability 8,000 operating cycles
Mechanical durability 20,000 operating cycles
Power loss 7.4 W per pole at rated operating conditions
Dimensions (H × W × D) 205 × 105 × 103.5 mm
Net weight approx. 2.35 kg
EAN 8015644554088

Frequently Asked Questions

What is the ABB 1SDA054311R1 used for?

The ABB 1SDA054311R1 is a three-pole moulded case circuit breaker for motor protection, providing adjustable magnetic short-circuit protection for industrial motor circuits.

What is the rated current of the ABB T4L 250 MA 1SDA054311R1?

The circuit breaker has a rated current of 160 A and is built on the ABB SACE Tmax T4 250 A frame.

What is the magnetic trip range of the ABB 1SDA054311R1?

The MA release provides an adjustable instantaneous magnetic trip range of 960–2,240 A, allowing short-circuit protection to be coordinated with motor starting characteristics.

Does the ABB T4L 250 MA provide thermal overload protection?

No. The MA trip unit is magnetic-only and provides short-circuit protection. Motor overload protection should therefore be provided by a suitable separate overload relay or motor protection device.

What breaking capacity does the ABB 1SDA054311R1 provide?

The T4L circuit breaker provides an ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC, making it suitable for demanding industrial motor circuits with high prospective fault currents.