Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA054298R1 Tmax T4N 250 three-pole moulded case circuit breaker with magnetic-only MA release, 125 A rated current, 750-1750 A instantaneous setting, fixed version and front terminals for motor feeder and short-circuit protection.
The ABB 1SDA054298R1 is a dependable Tmax T4N moulded case circuit breaker (MCCB) designed for reliable short-circuit protection in low-voltage electrical systems. As part of the proven ABB SACE Tmax T4N 250 series, this fixed three-pole breaker is suitable for motor feeder systems, industrial switchboards, OEM machinery panels and control assemblies where overload protection is provided separately.
This model features a magnetic-only MA release with a 125 A rated current and an adjustable instantaneous magnetic setting from 750–1750 A. The magnetic release provides fast fault interruption, making the breaker well suited to coordinated motor protection systems using separate thermal overload relays or electronic overload protection.
With its fixed front terminal configuration, compact Tmax T4 frame and ABB’s trusted circuit protection technology, the ABB 1SDA054298R1 delivers practical installation, dependable performance and long service life in demanding industrial environments.
Magnetic-only moulded case circuit breakers are commonly used where rapid short-circuit interruption is required and overload protection is handled by a separate relay or protective device. This approach is often used in motor feeders and coordinated industrial control systems.
The ABB 1SDA054298R1 provides dependable short-circuit protection while maintaining compact installation dimensions, making it a practical choice for panel builders, electrical contractors and maintenance engineers working with low-voltage motor control and distribution systems.
Tick the specs you need, then view products that match.
| Current | 125 A | |
|---|---|---|
| Phase | Three Phase | |
| Poles | 3-pole | |
| Device Type | MCCB | |
| Breaking Capacity | 36 kA | |
| Trip Unit | Magnetic only | |
| Manufacturer | ABB | |
| Series | SACE Tmax T4N | |
| Model | T4N 250 MA 125-1750 3P F F | |
| Product code | 1SDA054298R1 | |
| Product type | Moulded Case Circuit Breaker | |
| Frame size | T4N 250 | |
| Number of poles | 3 | |
| Rated current | 125 A | |
| Release type | Magnetic only | |
| Trip unit | MA | |
| Instantaneous setting | 750–1750 A | |
| Version | Fixed | |
| Terminal connection | Front terminals | |
| Rated operational voltage | Up to 690 V AC | |
| Breaking capacity at 415 V AC | 36 kA | |
| Mounting type | Panel / switchboard mounting | |
| Dimensions (H × W × D) | Approx. 205 × 105 × 103.5 mm | |
| Weight | Approx. 2.35 kg |
The ABB 1SDA054298R1 is used for short-circuit protection in low-voltage electrical and motor feeder systems where overload protection is provided separately.
This model is a three-pole moulded case circuit breaker, suitable for three-phase applications.
It uses a magnetic-only MA release, designed for short-circuit protection rather than integrated overload protection.
The ABB 1SDA054298R1 has a rated current of 125 A with an instantaneous magnetic setting range of 750–1750 A.
It is typically installed in motor feeder panels, control panels, switchboards, motor control centres and OEM machinery assemblies.
ABB Tmax moulded case circuit breakers are widely specified by panel builders, electrical contractors and industrial maintenance teams for dependable protection, compact installation and long-term reliability in low-voltage power distribution and motor protection systems.
We use cookies