1sda054298r1  t4n 250 ma 125-1750 3 pole abb mccb

1sda054298r1 t4n 250 ma 125-1750 3 pole abb mccb

ABB 1SDA054298R1 Tmax T4N 250 three-pole moulded case circuit breaker with magnetic-only MA release, 125 A rated current, 750-1750 A instantaneous setting, fixed version and front terminals for motor feeder and short-circuit protection.

SKU: 1SDA054298R1Alt SKU: T4N 250 MA 125-1750 3p F FMPN: 1SDA054298R1
Price on application Contact us for pricing and availability.
Call 01708 343600

Why Choose the ABB 1SDA054298R1 Tmax T4N Moulded Case Circuit Breaker?

The ABB 1SDA054298R1 is a dependable Tmax T4N moulded case circuit breaker (MCCB) designed for reliable short-circuit protection in low-voltage electrical systems. As part of the proven ABB SACE Tmax T4N 250 series, this fixed three-pole breaker is suitable for motor feeder systems, industrial switchboards, OEM machinery panels and control assemblies where overload protection is provided separately.

This model features a magnetic-only MA release with a 125 A rated current and an adjustable instantaneous magnetic setting from 750–1750 A. The magnetic release provides fast fault interruption, making the breaker well suited to coordinated motor protection systems using separate thermal overload relays or electronic overload protection.

With its fixed front terminal configuration, compact Tmax T4 frame and ABB’s trusted circuit protection technology, the ABB 1SDA054298R1 delivers practical installation, dependable performance and long service life in demanding industrial environments.

Key Advantages

  • High-quality ABB Tmax T4N moulded case circuit breaker.
  • 125 A rated current for motor and low-voltage protection systems.
  • Magnetic-only MA release for short-circuit protection.
  • Adjustable instantaneous setting from 750–1750 A.
  • Three-pole fixed design with front terminals.
  • Suitable where overload protection is provided by a separate protection device.

Key Features

  • ABB SACE Tmax T4N 250 series.
  • Product code: 1SDA054298R1.
  • Rated current: 125 A.
  • Three-pole (3P) moulded case circuit breaker.
  • Magnetic-only MA trip unit.
  • Instantaneous setting: 750–1750 A.
  • Fixed breaker version.
  • Front terminal connection.
  • Designed for motor feeder circuits, control panels and switchboards.

Reliable Short-Circuit Protection for Motor Circuits

Magnetic-only moulded case circuit breakers are commonly used where rapid short-circuit interruption is required and overload protection is handled by a separate relay or protective device. This approach is often used in motor feeders and coordinated industrial control systems.

The ABB 1SDA054298R1 provides dependable short-circuit protection while maintaining compact installation dimensions, making it a practical choice for panel builders, electrical contractors and maintenance engineers working with low-voltage motor control and distribution systems.

Typical Applications

  • Motor feeder protection systems.
  • Industrial control panels.
  • Motor control centres.
  • OEM machinery and automation equipment.
  • Low-voltage switchboards.
  • Short-circuit protection with separate overload relays.

Technical Specifications

Tick the specs you need, then view products that match.

Current 125 A
Phase Three Phase
Poles 3-pole
Device Type MCCB
Breaking Capacity 36 kA
Trip Unit Magnetic only
Manufacturer ABB
Series SACE Tmax T4N
Model T4N 250 MA 125-1750 3P F F
Product code 1SDA054298R1
Product type Moulded Case Circuit Breaker
Frame size T4N 250
Number of poles 3
Rated current 125 A
Release type Magnetic only
Trip unit MA
Instantaneous setting 750–1750 A
Version Fixed
Terminal connection Front terminals
Rated operational voltage Up to 690 V AC
Breaking capacity at 415 V AC 36 kA
Mounting type Panel / switchboard mounting
Dimensions (H × W × D) Approx. 205 × 105 × 103.5 mm
Weight Approx. 2.35 kg

Frequently Asked Questions

What is the ABB 1SDA054298R1 used for?

The ABB 1SDA054298R1 is used for short-circuit protection in low-voltage electrical and motor feeder systems where overload protection is provided separately.

How many poles does this circuit breaker have?

This model is a three-pole moulded case circuit breaker, suitable for three-phase applications.

What type of trip unit does the ABB 1SDA054298R1 use?

It uses a magnetic-only MA release, designed for short-circuit protection rather than integrated overload protection.

What is the rated current of this MCCB?

The ABB 1SDA054298R1 has a rated current of 125 A with an instantaneous magnetic setting range of 750–1750 A.

Where is this MCCB typically installed?

It is typically installed in motor feeder panels, control panels, switchboards, motor control centres and OEM machinery assemblies.

Trusted by Electrical Professionals Worldwide

ABB Tmax moulded case circuit breakers are widely specified by panel builders, electrical contractors and industrial maintenance teams for dependable protection, compact installation and long-term reliability in low-voltage power distribution and motor protection systems.