Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA054275R1 SACE Tmax T4S 125 A four-pole moulded case circuit breaker with TMA thermomagnetic release, fully rated neutral and fixed front terminals for low voltage distribution systems.
£1,392.41
The ABB 1SDA054275R1 is a reliable Tmax T4S moulded case circuit breaker (MCCB) designed for dependable protection of low voltage electrical distribution systems. Part of the proven ABB SACE Tmax T series, this four-pole circuit breaker provides robust overload and short-circuit protection for industrial, commercial and OEM applications.
This MCCB features a TMA thermomagnetic release, combining thermal overload protection with adjustable magnetic short-circuit protection. The fully rated neutral configuration makes it suitable for four-pole distribution systems where neutral protection and isolation are required.
With a rated current of 125 A, a 250 A frame size and a four-pole fixed front terminal design, the ABB 1SDA054275R1 is ideal for switchboards, distribution panels and machinery systems requiring compact, dependable ABB circuit protection.
Moulded case circuit breakers such as the ABB Tmax T4S help protect electrical installations against overloads and short-circuit faults. By interrupting fault currents quickly and reliably, they help reduce equipment damage, improve system safety and support continuity of operation.
The fully rated neutral design makes this breaker suitable for installations where neutral conductors must be protected and isolated at the same rating as the phase conductors. This is particularly useful in distribution systems with unbalanced loads or applications requiring four-pole switching.
Tick the specs you need, then view products that match.
| Current | 125 A | |
|---|---|---|
| Phase | Three Phase | |
| Poles | 4-pole | |
| Device Type | MCCB | |
| Breaking Capacity | 50 kA | |
| Trip Unit | Thermal-magnetic | |
| Manufacturer | ABB | |
| Series | SACE Tmax T | |
| Model | T4S 250 TMA 125-1250 4P F F InN=100%In | |
| Product code | 1SDA054275R1 | |
| Product type | Moulded Case Circuit Breaker | |
| Rated current (In) | 125 A | |
| Rated uninterrupted current (Iu) | 250 A | |
| Number of poles | 4 | |
| Neutral rating | Fully rated neutral, InN = 100% In | |
| Trip unit | TMA thermomagnetic release | |
| Magnetic adjustment range | 625-1250 A | |
| Rated operational voltage | 690 V AC / 750 V DC | |
| Rated insulation voltage (Ui) | 1000 V | |
| Rated impulse withstand voltage (Uimp) | 8 kV | |
| Breaking capacity | 50 kA at 400 V AC | |
| Short-circuit performance level | S | |
| Terminal type | Fixed front terminals | |
| Standards | IEC | |
| Dimensions (H × W × D) | approx. 205 × 140 × 103.5 mm | |
| Weight | approx. 3.05 kg |
This MCCB is used to protect low voltage electrical circuits against overloads and short-circuit faults in industrial, commercial and OEM distribution systems.
The ABB 1SDA054275R1 has a 125 A rated current with a 250 A frame size.
This model is a four-pole moulded case circuit breaker.
Fully rated neutral means the neutral pole is rated at 100% of the phase current, making it suitable for four-pole systems requiring full neutral protection and isolation.
It is fitted with a TMA thermomagnetic release, providing thermal overload protection and adjustable magnetic short-circuit protection.
ABB SACE Tmax moulded case circuit breakers are trusted by panel builders, contractors and industrial engineers for reliable protection, compact installation and proven long-term performance in low voltage electrical systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.