Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA054256R1 T4V 250 TMA 100-1000 is a 100 A four-pole fixed moulded case circuit breaker with front terminals, adjustable thermomagnetic protection and a 200 kA ultimate short-circuit breaking capacity at 380–415 V AC.
£1,500.41
The ABB T4V 250 TMA 100-1000, order code 1SDA054256R1, is a high-performance 4-pole moulded case circuit breaker (MCCB) designed for protection and switching in low-voltage electrical distribution systems. As part of the proven ABB Tmax T4 series, it combines a 100 A rated current with a TMA thermomagnetic trip unit for dependable protection of industrial and commercial power circuits.
The TMA thermomagnetic trip unit provides adjustable thermal overload and magnetic short-circuit protection without requiring an external power supply. Thermal protection is adjustable from 0.7 to 1 times the rated current, while magnetic protection is adjustable from 5 to 10 times the rated current, providing a magnetic trip adjustment range of 500–1000 A.
With a rated current of 100 A and an ultimate short-circuit breaking capacity of 200 kA at 380–415 V AC, the T4V 250 provides exceptionally high fault-current interruption capability. This configuration is a 4-pole fixed circuit breaker with front terminals, making it suitable for permanent installation in switchboards, distribution panels and demanding industrial electrical assemblies.
Moulded case circuit breakers such as the ABB Tmax T4 protect electrical installations by automatically interrupting excessive currents caused by overloads and short circuits. The T4V performance level combines compact construction with very high short-circuit interruption capability, making it particularly suitable for demanding industrial and commercial distribution systems.
The TMA release combines adjustable thermal overload protection with adjustable magnetic short-circuit protection. This enables the protection characteristics to be coordinated with the connected circuit while retaining the simplicity and reliability of a self-powered thermomagnetic protection system.
| Series | Tmax T4 |
|---|---|
| ABB order code | 1SDA054256R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Frame | T4 |
| Performance level | V |
| Rated current (In) | 100 A |
| Trip unit | TMA thermomagnetic |
| Thermal protection setting | 0.7–1 × In |
| Magnetic protection setting | 5–10 × In |
| Magnetic trip adjustment range | 500–1000 A |
| Number of poles | 4 |
| Ultimate short-circuit breaking capacity (Icu) at 220–230 V AC | 200 kA |
| Ultimate short-circuit breaking capacity (Icu) at 380–415 V AC | 200 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 180 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 150 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 80 kA |
| Mounting | Fixed |
| Terminal arrangement | Front terminals |
| Dimensions (H × W × D) | 205 × 130 × 103.5 mm |
| Weight | approx. 3.84 kg |
The ABB 1SDA054256R1 is a Tmax T4V 250 fixed 4-pole moulded case circuit breaker with front terminals and a 100 A TMA thermomagnetic trip unit.
This T4V 250 configuration has a rated current of 100 A.
The TMA trip unit provides adjustable thermal overload and magnetic short-circuit protection, with this model offering a magnetic adjustment range of 500–1000 A.
This configuration provides an ultimate short-circuit breaking capacity of 200 kA at 380–415 V AC, with the available breaking capacity varying according to operating voltage.
It is typically installed in industrial and commercial low-voltage switchboards, machinery and distribution panels requiring 4-pole adjustable thermomagnetic protection and very high short-circuit breaking performance.
ABB Tmax moulded case circuit breakers are widely used in industrial and commercial electrical distribution systems, providing dependable switching, adjustable thermomagnetic protection and high short-circuit performance for demanding low-voltage installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.