1SDA054238R1 ABB T4L250 TMA 100-1000 100 A 4-Pole MCCB

1SDA054238R1 ABB T4L250 TMA 100-1000 100 A 4-Pole MCCB

ABB 1SDA054238R1 SACE Tmax T4L250 fixed four-pole 100 A moulded case circuit breaker with adjustable TMA thermomagnetic protection and 120 kA breaking capacity at 380–415 V AC.

SKU: 1SDA054238R1MPN: 1SDA054238R1
Price
List Price £2,365.44 ex VAT
Your Price (ex VAT) Save 25%
£1,774.08 25% OFF
You save £591.36 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,774.08
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,774.08

Why Choose the ABB T4L250 TMA 100-1000 1SDA054238R1 Circuit Breaker?

The ABB 1SDA054238R1 is a high-performance SACE Tmax T4L 250 moulded case circuit breaker (MCCB) designed for reliable protection and isolation of low-voltage electrical distribution systems. Configured as a fixed four-pole breaker with front terminals, it combines a 100 A rated current with ABB's TMA thermomagnetic trip unit for dependable overload and short-circuit protection.

Part of the proven ABB SACE Tmax T4 series, the T4L250 is designed for industrial and commercial power distribution applications requiring compact construction and high short-circuit interruption performance. Its TMA release provides adjustable thermal overload protection together with adjustable instantaneous magnetic protection, helping safeguard cables, equipment and distribution circuits against damaging overcurrents.

The TMA release is rated at 100 A, with thermal protection adjustable from 70–100 A and instantaneous magnetic protection adjustable from 500–1,000 A. The T4L performance level provides an ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC, making the 1SDA054238R1 suitable for demanding electrical distribution installations.

Key Advantages

  • High-performance ABB SACE Tmax T4L moulded case circuit breaker.
  • 100 A rated current for industrial and commercial distribution circuits.
  • Four-pole configuration for multipole low-voltage distribution systems.
  • TMA thermomagnetic trip unit with adjustable overload and short-circuit protection.
  • 70–100 A thermal adjustment range for flexible overload protection.
  • 500–1,000 A instantaneous magnetic adjustment range.
  • 120 kA ultimate breaking capacity at 380–415 V AC.
  • Fixed mounting with front terminals for straightforward switchboard integration.

Key Features

  • ABB SACE Tmax T4L 250 circuit breaker platform.
  • 100 A rated current.
  • 4-pole construction.
  • TMA thermomagnetic release.
  • Adjustable thermal protection from 0.7–1 × In.
  • Adjustable instantaneous magnetic protection from 5–10 × In.
  • 120 kA Icu at 380–415 V AC.
  • Rated for operation up to 690 V AC.
  • Fixed circuit breaker configuration with front terminals.

Reliable Circuit Protection for Power Distribution

Moulded case circuit breakers such as the ABB SACE Tmax T4L protect electrical distribution circuits against damaging overcurrents while also providing a convenient means of circuit isolation. The T4 platform combines compact construction with robust switching performance, making it suitable for demanding industrial and commercial low-voltage distribution applications.

The TMA thermomagnetic trip unit provides complementary overload and short-circuit protection. Its adjustable thermal element responds to sustained overload currents that could overheat cables and connected equipment, while the adjustable magnetic element provides rapid tripping during severe short-circuit conditions. This flexibility allows the breaker protection characteristics to be matched more closely to the requirements of the electrical circuit.

Typical Applications

  • Industrial low-voltage distribution systems.
  • Main and sub-distribution switchboards.
  • Electrical control and distribution panels.
  • Commercial building power distribution.
  • Manufacturing and process installations.
  • Machinery and plant electrical distribution.

Technical Specifications

Series SACE Tmax T4
ABB order code 1SDA054238R1
Product group 310511-T-Max T4 - T8
Product type Moulded case circuit breaker (MCCB)
Frame T4 250
Performance level L
Rated current 100 A
Thermal protection adjustment 70–100 A (0.7–1 × In)
Instantaneous magnetic protection adjustment 500–1,000 A (5–10 × In)
Number of poles 4
Trip unit TMA thermomagnetic release
Protection functions Thermal overload and magnetic short-circuit protection
Rated operational voltage up to 690 V AC
Ultimate breaking capacity (Icu) at 220/230 V AC 200 kA
Ultimate breaking capacity (Icu) at 380/415 V AC 120 kA
Ultimate breaking capacity (Icu) at 440 V AC 100 kA
Ultimate breaking capacity (Icu) at 500 V AC 85 kA
Ultimate breaking capacity (Icu) at 690 V AC 70 kA
Mounting type Fixed
Terminal type Front terminals
Dimensions (H × W × D) approx. 205 × 140 × 103.5 mm
Weight approx. 3.5 kg
EAN 8015644553357

Frequently Asked Questions

What is the ABB 1SDA054238R1 used for?

The ABB 1SDA054238R1 is a 100 A moulded case circuit breaker designed to protect low-voltage electrical distribution circuits against overloads and short circuits.

What is the current rating of the ABB T4L250 1SDA054238R1?

The circuit breaker has a rated current of 100 A and is based on the ABB SACE Tmax T4L 250 frame.

What does TMA 100-1000 mean on this ABB circuit breaker?

The TMA thermomagnetic release is rated at 100 A, with thermal overload protection adjustable from 70–100 A and instantaneous magnetic protection adjustable from 500–1,000 A.

What is the breaking capacity of the ABB 1SDA054238R1?

The T4L version provides an ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC, with breaking capacity varying according to the system operating voltage.

How is the ABB 1SDA054238R1 installed?

This model is a fixed four-pole circuit breaker with front terminals, designed for installation in electrical distribution panels and switchboards.

Trusted Protection from ABB

ABB SACE Tmax moulded case circuit breakers are engineered for dependable low-voltage power distribution, combining robust switching performance with adjustable thermomagnetic protection for industrial and commercial electrical systems.