ABB T4L 250 TMA 80-800 3p F F moulded case circuit breaker with thermal-magnetic protection for reliable low-voltage industrial power distribution.
£1,196.42
The ABB T4L 250 TMA 80-800 3p F F is a reliable moulded case circuit breaker (MCCB) designed for dependable protection and switching in low-voltage electrical distribution systems. Part of the established ABB SACE Tmax T4 series, this circuit breaker combines compact construction with advanced thermal-magnetic protection technology for industrial, commercial and infrastructure applications.
Featuring the TMA thermal-magnetic trip unit, the ABB T4L 250 provides effective overload and short-circuit protection through thermal protection for sustained overcurrents and magnetic protection for fault conditions. The fixed three-pole front-terminal configuration enables straightforward installation in switchboards and electrical assemblies.
With a 250 A frame size, 80 A rated current and adjustable magnetic protection up to 800 A, the T4L 250 TMA 80-800 3p F F is suitable for protecting feeders, machinery and distribution circuits where reliable fault interruption and long service life are required.
Moulded case circuit breakers such as the ABB T4L 250 provide essential electrical protection by disconnecting circuits during overload and short-circuit conditions. The TMA thermal-magnetic trip unit provides proven electromechanical protection for a wide range of low-voltage applications.
The Tmax T4 range is engineered for industrial switchboards, machinery power distribution and commercial electrical systems where compact installation, dependable operation and effective fault protection are required.
| Series | SACE Tmax T |
|---|---|
| Order code | 1SDA054228R1 |
| Product type | Moulded case circuit breaker |
| Frame size | T4L 250 |
| Rated current (In) | 80 A |
| Number of poles | 3P |
| Trip unit | TMA thermal-magnetic release |
| Magnetic protection range | 80–800 A |
| Terminal connection | Fixed front terminals |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V |
| Rated impulse withstand voltage | 8 kV |
| Mounting type | Fixed mounting |
This ABB Tmax T4 moulded case circuit breaker is used for protecting and switching low-voltage electrical distribution circuits against overloads and short circuits.
The ABB T4L 250 TMA 80-800 3p F F has a rated current of 80 A.
This model is a three-pole (3P) circuit breaker designed for three-phase electrical systems.
The circuit breaker is fitted with a TMA thermal-magnetic trip unit providing overload and short-circuit protection.
This circuit breaker is typically installed in industrial switchboards, distribution panels and electrical equipment assemblies.
ABB Tmax circuit breakers are widely selected by electrical engineers and system integrators for dependable protection, efficient power distribution and long-term performance in industrial installations.