1sda054220r1  t4h 250 tma 100-1000 4 pole abb mccb

1sda054220r1 t4h 250 tma 100-1000 4 pole abb mccb

ABB 1SDA054220R1 SACE Tmax T4H 250 fixed four-pole moulded case circuit breaker with 100 A thermal magnetic TMA release and front terminals for industrial power distribution.

SKU: 1SDA054220R1Alt SKU: T4H 250 TMA 100-1000 4p F FMPN: 1SDA054220R1
Price
List Price £1,876.86 ex VAT
Your Price (ex VAT) Save 25%
£1,407.65 25% OFF
You save £469.22 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,407.65
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,407.65

Why Choose the ABB 1SDA054220R1 Tmax T4H Moulded Case Circuit Breaker?

The ABB 1SDA054220R1 is a premium Tmax T4H moulded case circuit breaker (MCCB) designed to provide dependable protection against overloads and short circuits in industrial and commercial low voltage electrical systems. As part of the trusted ABB SACE Tmax T series, it delivers excellent interrupting performance, robust thermal magnetic protection and long-term reliability for demanding power distribution applications.

This model features a 250 A frame size with a 100 A thermal magnetic TMA release. Its fixed four-pole configuration and front terminal connections make it ideal for protecting three-phase systems requiring switched neutral isolation in switchboards, motor control centres, distribution panels and OEM machinery.

Designed in accordance with IEC 60947, the ABB Tmax T4H range is trusted by panel builders, electrical engineers and industrial contractors worldwide for dependable circuit protection, high breaking capacity and long operational life.

Key Advantages

  • High-performance ABB SACE Tmax T4H moulded case circuit breaker.
  • 100 A thermal magnetic TMA trip unit within a 250 A frame.
  • Fixed four-pole construction for industrial power distribution.
  • High short-circuit breaking capacity up to 100 kA.
  • Compact panel-mounted design with front terminal connections.
  • Reliable overload and short-circuit protection.

Key Features

  • Manufacturer: ABB.
  • Series: SACE Tmax T.
  • Model: T4H 250 TMA 100-1000 4P F F.
  • Product ID: 1SDA054220R1.
  • 100 A rated current.
  • 250 A frame size.
  • Thermal magnetic TMA release.
  • Fixed four-pole configuration.
  • Front terminal connections.
  • Rated operational voltage up to 690 V AC.

Reliable Protection for Industrial Power Distribution

The ABB Tmax T4H series is engineered to disconnect electrical circuits rapidly during overload and short-circuit conditions, helping protect cables, switchgear and connected equipment. Its high interrupting capacity and durable construction make it suitable for demanding industrial environments where safety and reliability are essential.

The four-pole design enables isolation of all live conductors, including the neutral where required. Combined with the thermal magnetic TMA trip unit, this provides dependable protection for industrial switchboards, commercial installations and OEM electrical systems.

Typical Applications

  • Industrial switchboards.
  • Commercial power distribution systems.
  • Motor control centres.
  • OEM machinery and automation equipment.
  • Electrical distribution panels.
  • Three-phase installations requiring neutral isolation.

Technical Specifications

Tick the specs you need, then view products that match.

Current 100 A
Phase Three Phase
Poles 4-pole
Device Type MCCB
Breaking Capacity 100 kA
Trip Unit Thermal-magnetic
Manufacturer ABB
Series SACE Tmax T
Product ID 1SDA054220R1
EAN 8015644552572
Extended product type T4H 250 TMA 100-1000 4P F F
Product type Moulded Case Circuit Breaker (MCCB)
Frame size T4H 250
Rated current (In) 100 A
Rated uninterrupted current (Iu) 250 A
Release TMA
Release type Thermal Magnetic (TM)
Magnetic setting range 500-1000 A
Number of poles 4
Rated operational voltage 690 V AC / 750 V DC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 8 kV
Rated ultimate short-circuit breaking capacity (Icu) 100 kA at 230 V AC, 70 kA at 415 V AC, 40 kA at 690 V AC
Rated service short-circuit breaking capacity (Ics) 100 kA at 230 V AC, 70 kA at 415 V AC, 40 kA at 690 V AC
Short-circuit performance level H
Terminal type Front terminals
Mounting Fixed
Electrical durability 8,000 cycles
Mechanical durability 20,000 cycles
Dimensions (H × W × D) 205 × 140 × 103.5 mm
Weight Approx. 3.05 kg
Standards IEC 60947

Frequently Asked Questions

What is the ABB 1SDA054220R1 used for?

It provides overload and short-circuit protection for industrial and commercial low voltage electrical distribution systems.

How many poles does this circuit breaker have?

The ABB 1SDA054220R1 is supplied as a fixed four-pole moulded case circuit breaker.

What current rating does this breaker provide?

This breaker features a 100 A thermal magnetic TMA trip unit within a 250 A Tmax T4H frame.

What type of trip unit is fitted?

The breaker uses a thermal magnetic TMA release providing dependable overload and short-circuit protection.

Where is this MCCB typically installed?

It is commonly installed in industrial switchboards, distribution panels, motor control centres and OEM electrical equipment.

Trusted by Electrical Professionals Worldwide

ABB SACE Tmax moulded case circuit breakers are trusted worldwide by electrical engineers, panel builders and OEM manufacturers for dependable protection, high interrupting performance and long-term operational reliability.