1sda054199r1  t4s 250 tmd 32-320 4 pole abb mccb

1sda054199r1 t4s 250 tmd 32-320 4 pole abb mccb

ABB 1SDA054199R1 Tmax T4S 250 A four-pole moulded case circuit breaker with TMD thermomagnetic release, 32 A rated current, adjustable 32-320 A, fixed mounting and front terminals.

SKU: 1SDA054199R1Alt SKU: T4S 250 TMD 32-320 4p F FMPN: 1SDA054199R1
Price
List Price £1,481.11 ex VAT
Your Price (ex VAT) Save 25%
£1,110.83 25% OFF
You save £370.28 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,110.83
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,110.83

Why Choose the ABB 1SDA054199R1 Tmax T4S Moulded Case Circuit Breaker?

The ABB 1SDA054199R1 is a dependable Tmax T4S moulded case circuit breaker (MCCB) engineered to protect industrial and commercial low-voltage electrical distribution systems. Featuring a 250 A frame size, 4-pole configuration and a TMD thermomagnetic release with a rated current of 32 A and adjustable range from 32-320 A, it delivers reliable overload and short-circuit protection for demanding industrial applications.

Part of the trusted ABB SACE Tmax T series, this fixed MCCB combines compact dimensions with excellent electrical performance. Its front terminal connections simplify installation into switchboards, control panels and industrial distribution assemblies while providing ABB's renowned reliability and long service life.

Designed for operation up to 690 V AC, the ABB 1SDA054199R1 offers excellent interrupting performance and dependable circuit protection. The thermomagnetic release provides accurate overload and magnetic short-circuit protection, helping safeguard electrical infrastructure and connected equipment while supporting system continuity.

Key Advantages

  • Reliable ABB Tmax T4S moulded case circuit breaker.
  • 250 A frame size for industrial power distribution.
  • 4-pole fixed MCCB with front terminal connections.
  • TMD thermomagnetic release adjustable from 32-320 A.
  • Provides dependable overload and short-circuit protection.
  • Compact Tmax T4 design for efficient panel installation.

Key Features

  • ABB SACE Tmax T4S series.
  • 250 A rated uninterrupted current (Iu).
  • 32 A rated current (In).
  • 4-pole moulded case circuit breaker.
  • TMD thermomagnetic release.
  • Release adjustment range of 32-320 A.
  • Fixed mounting version with front terminals.
  • Rated operational voltage up to 690 V AC / 750 V DC.

Reliable Protection for Low-Voltage Distribution

The ABB Tmax T4S range is engineered to protect electrical installations against overloads and short-circuit faults. Thermomagnetic releases provide dependable protection while helping protect switchgear, cabling and connected equipment from damaging fault currents.

The ABB 1SDA054199R1 is an excellent choice for panel builders, OEMs and electrical contractors requiring a compact four-pole MCCB with adjustable thermomagnetic protection and high interrupting performance for industrial applications.

Typical Applications

  • Industrial power distribution boards.
  • Main and sub-distribution switchboards.
  • Motor control centres.
  • Commercial electrical installations.
  • Manufacturing facilities.
  • Infrastructure and utility distribution systems.

Technical Specifications

Tick the specs you need, then view products that match.

Current 32 A
Phase Three Phase
Poles 4-pole
Device Type MCCB
Breaking Capacity 85 kA
Trip Unit Thermal-magnetic
Manufacturer ABB
Series SACE Tmax T
Model T4S 250 TMD 32-320 4p F F
Product ID 1SDA054199R1
EAN 8015644552992
Product type Moulded Case Circuit Breaker (MCCB)
Rated uninterrupted current (Iu) 250 A
Rated current (In) 32 A
Release adjustment range 32-320 A
Number of poles 4P
Release type Thermomagnetic
Trip unit TMD
Rated operational voltage 690 V AC / 750 V DC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 8 kV
Rated service short-circuit breaking capacity (Ics) Up to 85 kA at 230 V AC, 50 kA at 400 V AC, 25 kA at 690 V AC
Rated ultimate short-circuit breaking capacity (Icu) Up to 85 kA at 230 V AC, 50 kA at 400 V AC, 25 kA at 690 V AC
Terminal connection Front terminals
Mounting type Fixed
Standards IEC 60947-2
Dimensions (H × W × D) 205 × 140 × 103.5 mm
Weight Approx. 3.05 kg

Frequently Asked Questions

What is the ABB 1SDA054199R1 used for?

The ABB 1SDA054199R1 protects industrial and commercial low-voltage electrical distribution systems against overloads and short-circuit faults.

What is the rated current of this MCCB?

This breaker has a 32 A rated current within a 250 A frame size.

How many poles does the ABB 1SDA054199R1 have?

The breaker features a 4-pole configuration, making it suitable for three-phase systems where neutral switching or protection may be required.

Which trip unit is fitted?

The breaker is fitted with a TMD thermomagnetic release adjustable from 32-320 A.

Where is this circuit breaker typically installed?

It is commonly installed in switchboards, distribution panels, motor control centres and industrial electrical installations.

Trusted by Industry Worldwide

ABB Tmax moulded case circuit breakers are trusted worldwide for delivering reliable low-voltage circuit protection, excellent interrupting performance and long service life across industrial and commercial applications.