Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA054075R1 is a three-pole fixed SACE Tmax T4L 250 moulded case circuit breaker with front terminals, a 100 A PR222DS/P-LSI electronic trip unit and 120 kA ultimate breaking capacity at 400/415 V AC.
£2,723.36
The ABB 1SDA054075R1 is a SACE Tmax T4L 250 three-pole moulded case circuit breaker designed for demanding low-voltage distribution and circuit-protection applications. This fixed breaker combines a 250 A frame with a 100 A rated PR222DS/P-LSI electronic trip unit, providing adjustable electronic protection for industrial and commercial electrical systems.
Equipped with ABB's PR222DS/P-LSI electronic release, the breaker provides long-time, short-time and instantaneous overcurrent protection functions. The electronic trip technology enables more precise protection characteristics than conventional thermal-magnetic releases, making the T4L 250 suitable for installations requiring coordinated protection of feeders, cables and distribution equipment.
The 1SDA054075R1 features a fixed, three-pole construction with front terminals and a rated operational voltage of up to 690 V AC. Its L short-circuit performance level delivers an ultimate breaking capacity of 120 kA at 400/415 V AC, providing substantial fault-interruption capability for demanding low-voltage networks.
The PR222DS/P-LSI electronic trip unit provides protection against the principal overcurrent conditions encountered in low-voltage distribution systems. Long-time protection responds to sustained overloads, short-time protection supports selective coordination during higher fault currents, and instantaneous protection provides rapid interruption of severe short-circuit conditions.
Combined with the T4L breaker's high fault-interruption capability, the 100 A PR222DS/P-LSI release makes the ABB 1SDA054075R1 suitable for protecting feeders and distribution circuits where both accurate electronic protection and high short-circuit performance are required. The fixed three-pole design and front terminals also support straightforward integration into compatible switchboards and panel assemblies.
| Series | SACE Tmax T |
|---|---|
| Order code | 1SDA054075R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Frame / subtype | T4L 250 |
| Number of poles | 3 |
| Rated current (In) | 100 A |
| Rated uninterrupted current (Iu) | 250 A |
| Trip unit | PR222DS/P-LSI |
| Trip technology | Electronic |
| Protection functions | LSI – long-time, short-time and instantaneous |
| Short-circuit performance level | L |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Ultimate breaking capacity (Icu) at 400/415 V AC | 120 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 100 kA |
| Ultimate breaking capacity (Icu) at 500 V AC | 85 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 70 kA |
| Service breaking capacity (Ics) at 400/415 V AC | 120 kA |
| Installation | Fixed circuit breaker |
| Terminal connection | Front |
| Electrical durability | 8,000 cycles |
| Mechanical durability | 20,000 cycles |
| Power loss at rated operating conditions | 1.7 W per pole |
| Standard | IEC |
| Dimensions (W × H × D) | 105 × 205 × 103.5 mm |
| EAN | 8015644551674 |
The ABB 1SDA054075R1 is a SACE Tmax T4L 250 three-pole fixed moulded case circuit breaker with front terminals and a 100 A PR222DS/P-LSI electronic trip unit.
The LSI designation identifies long-time, short-time and instantaneous overcurrent protection, providing electronic protection against overload and short-circuit conditions.
The installed PR222DS/P-LSI trip unit has a rated current of 100 A, while the T4L 250 breaker frame has a rated uninterrupted current of 250 A.
The T4L version has an ultimate short-circuit breaking capacity of 120 kA at 400/415 V AC, 100 kA at 440 V AC, 85 kA at 500 V AC and 70 kA at 690 V AC.
The 1SDA054075R1 is a fixed three-pole circuit breaker with front terminals, intended for permanent installation within compatible low-voltage switchboards and distribution assemblies.
ABB SACE Tmax moulded case circuit breakers combine compact construction, high short-circuit performance and electronic protection technology for dependable low-voltage power distribution across industrial, commercial and infrastructure applications.
We use cookies