Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA054059R1 SACE Tmax T4H 250 four pole moulded case circuit breaker with PR221DS-LS/I electronic trip unit and 250 A rated current for industrial and commercial power distribution.
£2,232.00
The ABB 1SDA054059R1 is a high-performance Tmax T4H moulded case circuit breaker (MCCB) designed to deliver reliable circuit protection for industrial, commercial and infrastructure power distribution systems. As part of the proven ABB SACE Tmax T series, it provides dependable overload and short circuit protection in demanding low voltage installations.
This circuit breaker features a PR221DS-LS/I electronic trip unit, providing precise protection functions for improved selectivity, safety and operational continuity. Its fixed four-pole design with front terminals makes it suitable for switchboards, distribution panels and control cabinets requiring robust and accurate protection.
With a 250 A rated current, a 250 A frame size and high breaking capacity performance, the ABB 1SDA054059R1 is ideal for demanding electrical systems where dependable fault interruption, long service life and compact installation are essential.
The ABB Tmax T4H range is engineered to protect low voltage circuits against overloads and short circuits while helping maintain reliable power distribution. Its electronic release supports accurate tripping characteristics, allowing better coordination across electrical installations.
The ABB 1SDA054059R1 is well suited to installations where compact design, high fault interruption capability and dependable operation are required. Its fixed front-terminal configuration makes it practical for integration into industrial switchgear, machinery panels and commercial distribution boards.
Tick the specs you need, then view products that match.
| Current | 250 A | |
|---|---|---|
| Phase | Three Phase | |
| Poles | 4-pole | |
| Device Type | MCCB | |
| Breaking Capacity | 70 kA | |
| Trip Unit | Electronic | |
| Manufacturer | ABB | |
| Series | SACE Tmax T | |
| Model | T4H 250 PR221DS-LS/I In=250 4P F F | |
| Product ID | 1SDA054059R1 | |
| EAN | 8015644551513 | |
| Product type | Moulded Case Circuit Breaker (MCCB) | |
| Rated current (In) | 250 A | |
| Rated uninterrupted current (Iu) | 250 A | |
| Number of poles | 4 | |
| Trip unit | PR221DS-LS/I electronic release | |
| Rated operational voltage | Up to 690 V AC | |
| Rated insulation voltage (Ui) | 1000 V | |
| Rated impulse withstand voltage (Uimp) | 8 kV | |
| Rated service short circuit breaking capacity (Ics) | 70 kA at 400 V AC | |
| Rated ultimate short circuit breaking capacity (Icu) | 70 kA at 400 V AC | |
| Terminal type | Front terminals | |
| Mounting type | Fixed | |
| Standards | IEC 60947-2 | |
| Dimensions (H × W × D) | 205 × 140 × 103.5 mm | |
| Weight | Approx. 3.05 kg |
It is used to protect low voltage electrical distribution systems against overloads and short circuits.
The ABB 1SDA054059R1 has a 250 A rated current.
This model is a four-pole (4P) moulded case circuit breaker.
It is fitted with an ABB PR221DS-LS/I electronic trip unit for accurate overload and short circuit protection.
It is commonly installed in industrial switchboards, commercial distribution panels, motor control centres and OEM control cabinets.
ABB SACE Tmax moulded case circuit breakers are trusted by engineers, panel builders and electrical contractors for reliable circuit protection, high breaking performance and long-term dependability in demanding installations.