ABB 1SDA054042R1 Tmax T4S moulded case circuit breaker with PR222DS/P-LSIG electronic trip unit, 100 A rated current, four-pole fixed configuration and front terminals for low voltage power distribution.
£2,914.56
The ABB 1SDA054042R1 is a high-performance Tmax T4S moulded case circuit breaker (MCCB) designed for dependable protection of low voltage electrical distribution systems. Built within the proven ABB SACE Tmax T series, this breaker is suitable for industrial switchboards, commercial distribution panels, OEM machinery and automation systems requiring reliable circuit protection.
This MCCB is fitted with a PR222DS/P-LSIG electronic trip unit, providing adjustable overload, short-circuit, instantaneous and ground fault protection for AC electrical installations. The solid-state release supports accurate trip settings and improved system selectivity, making it ideal for demanding industrial and commercial power distribution environments.
With a 100 A rated current, four-pole fixed configuration and front terminal connections, the ABB 1SDA054042R1 is ideal for feeder protection, distribution boards, switchboards and industrial control panels where reliable four-pole protection with ground fault functionality is required.
Moulded case circuit breakers such as the ABB 1SDA054042R1 are used to protect electrical circuits from overloads, short-circuit faults and earth fault conditions. The electronic PR222DS/P-LSIG release provides accurate protection settings, helping engineers maintain safe, selective and reliable low voltage power distribution.
The Tmax T4S range is widely used across industrial and commercial installations due to its compact footprint, strong breaking performance and proven ABB engineering. Its four-pole configuration makes it suitable for applications where neutral switching or full-pole isolation is required.
Tick the specs you need, then view products that match.
| Current | 100 A | |
|---|---|---|
| Phase | Three Phase | |
| Poles | 4-pole | |
| Device Type | MCCB | |
| Breaking Capacity | 50 kA | |
| Trip Unit | Electronic | |
| Manufacturer | ABB | |
| Series | SACE Tmax T | |
| Model | T4S 250 PR222DS/P-LSIG In=100 4p F F | |
| Product ID | 1SDA054042R1 | |
| EAN | 8015644551346 | |
| Product type | Moulded Case Circuit Breaker | |
| Rated current (In) | 100 A | |
| Rated uninterrupted current (Iu) | 250 A | |
| Number of poles | 4P | |
| Release | PR222DS/P-LSIG | |
| Release type | Electronic | |
| Rated operational voltage | 690 V AC | |
| Rated insulation voltage (Ui) | 1000 V | |
| Rated impulse withstand voltage (Uimp) | 8 kV | |
| Short-circuit performance level | S | |
| Rated ultimate breaking capacity (Icu) | 50 kA at 400 V AC | |
| Rated service breaking capacity (Ics) | 50 kA at 400 V AC | |
| Terminal connection | Front terminals | |
| Mounting type | Fixed | |
| Electrical durability | 8,000 cycles | |
| Mechanical durability | 20,000 cycles | |
| Power loss | 1.7 W per pole at rated operating conditions | |
| Dimensions (H × W × D) | 205 × 140 × 103.5 mm | |
| Weight | approx. 3.05 kg |
The ABB 1SDA054042R1 is used to protect low voltage electrical distribution systems against overloads, short-circuit faults and ground fault conditions.
This moulded case circuit breaker has a 100 A rated current.
The ABB 1SDA054042R1 is fitted with a PR222DS/P-LSIG electronic trip unit for adjustable overload, short-circuit, instantaneous and ground fault protection.
This model is a four-pole fixed MCCB designed for low voltage electrical distribution systems.
It is typically installed in switchboards, distribution panels, motor control centres, industrial control cabinets and OEM electrical equipment.
ABB SACE Tmax moulded case circuit breakers are trusted by panel builders, electrical engineers and industrial maintenance teams for reliable protection, strong breaking performance and long service life in demanding low voltage installations.