1sda054040r1  t4s 250 pr222ds/p-lsi in=160 4 pole abb mccb

1sda054040r1 t4s 250 pr222ds/p-lsi in=160 4 pole abb mccb

ABB 1SDA054040R1 Tmax T4S moulded case circuit breaker with PR222DS/P-LSI electronic trip unit, 160 A rated current, four-pole fixed configuration and front terminals for low voltage power distribution.

SKU: 1SDA054040R1Alt SKU: T4S 250 PR222DS/P-LSI In=160 4p F FMPN: 1SDA054040R1
Price
List Price £3,544.20 ex VAT
Your Price (ex VAT) Save 25%
£2,658.15 25% OFF
You save £886.05 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £2,658.15
Trade pricing is personalised to your account

Manufacturer Lead Time

£2,658.15

Why Choose the ABB 1SDA054040R1 Tmax T4S Moulded Case Circuit Breaker?

The ABB 1SDA054040R1 is a robust Tmax T4S moulded case circuit breaker (MCCB) designed for reliable protection of low voltage electrical distribution systems. Built within the proven ABB SACE Tmax T series, this breaker is suitable for industrial switchboards, commercial distribution panels, OEM machinery and automation systems requiring dependable circuit protection.

This MCCB is fitted with a PR222DS/P-LSI electronic trip unit, providing adjustable overload, short-circuit and selective protection for AC electrical installations. The solid-state release supports accurate trip settings and improved system selectivity, making it ideal for demanding industrial and commercial power distribution environments.

With a 160 A rated current, four-pole fixed configuration and front terminal connections, the ABB 1SDA054040R1 is ideal for feeder protection, distribution boards, switchboards and industrial control panels where reliable four-pole circuit protection is required.

Key Advantages

  • Reliable ABB Tmax T4S moulded case circuit breaker for industrial protection.
  • 160 A rated current for low voltage power distribution.
  • PR222DS/P-LSI electronic trip unit for adjustable protection functions.
  • Four-pole fixed MCCB with front terminal connections.
  • Supports overload, short-circuit and selective protection.
  • High breaking performance for demanding switchboard applications.
  • Compact construction suitable for distribution panels and control cabinets.

Key Features

  • ABB SACE Tmax T series.
  • T4S 250 frame size.
  • 160 A rated current.
  • 4-pole fixed moulded case circuit breaker.
  • PR222DS/P-LSI solid-state electronic release.
  • Front terminal connection type.
  • 690 V AC rated operational voltage.
  • Suitable for industrial and commercial electrical distribution systems.

Advanced Four-Pole Protection for Low Voltage Systems

Moulded case circuit breakers such as the ABB 1SDA054040R1 are used to protect electrical circuits from overloads and short-circuit fault conditions. The electronic PR222DS/P-LSI release provides accurate protection settings, helping engineers maintain safe, selective and reliable low voltage power distribution.

The Tmax T4S range is widely used across industrial and commercial installations due to its compact footprint, strong breaking performance and proven ABB engineering. Its four-pole configuration makes it suitable for applications where neutral switching or full-pole isolation is required.

Typical Applications

  • Industrial power distribution panels.
  • Commercial electrical switchboards.
  • Main feeder and sub-distribution protection.
  • Four-pole low voltage distribution circuits.
  • Motor control centres and machinery panels.
  • OEM electrical equipment and control cabinets.

Technical Specifications

Tick the specs you need, then view products that match.

Current 160 A
Phase Three Phase
Poles 4-pole
Device Type MCCB
Breaking Capacity 50 kA
Trip Unit Electronic
Manufacturer ABB
Series SACE Tmax T
Model T4S 250 PR222DS/P-LSI In=160 4p F F
Product ID 1SDA054040R1
EAN 8015644551322
Product type Moulded Case Circuit Breaker
Rated current (In) 160 A
Rated uninterrupted current (Iu) 250 A
Number of poles 4P
Release PR222DS/P-LSI
Release type Electronic
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 8 kV
Short-circuit performance level S
Rated ultimate breaking capacity (Icu) 50 kA at 400 V AC
Rated service breaking capacity (Ics) 50 kA at 400 V AC
Terminal connection Front terminals
Mounting type Fixed
Electrical durability 8,000 cycles
Mechanical durability 20,000 cycles
Power loss 4.4 W per pole at rated operating conditions
Dimensions (H × W × D) 205 × 140 × 103.5 mm
Weight approx. 3.05 kg

Frequently Asked Questions

What is the ABB 1SDA054040R1 used for?

The ABB 1SDA054040R1 is used to protect low voltage electrical distribution systems against overloads and short-circuit fault conditions.

What is the rated current of this MCCB?

This moulded case circuit breaker has a 160 A rated current.

What type of trip unit does it use?

The ABB 1SDA054040R1 is fitted with a PR222DS/P-LSI electronic trip unit for adjustable overload, short-circuit and selective protection.

How many poles does this circuit breaker have?

This model is a four-pole fixed MCCB designed for low voltage electrical distribution systems.

Where is the ABB 1SDA054040R1 typically installed?

It is typically installed in switchboards, distribution panels, motor control centres, industrial control cabinets and OEM electrical equipment.

Trusted by Electrical Professionals Worldwide

ABB SACE Tmax moulded case circuit breakers are trusted by panel builders, electrical engineers and industrial maintenance teams for reliable protection, strong breaking performance and long service life in demanding low voltage installations.