Mersen NH2GTR50KVA NH Size 2 gTr transformer protection fuse link rated at 72 A and 400 V AC for 50 kVA distribution transformers.
£20.20
The Mersen NH2GTR50KVA is a specialist NH gTr low voltage fuse link designed specifically for the protection of distribution transformers. As part of the proven Mersen NH gTr fuse-link series, it features a time/current characteristic carefully matched to transformer inrush currents, delivering excellent selectivity while protecting transformers against overloads and short circuits.
Rated at 400 V AC with a 72 A current rating, the NH2GTR50KVA is engineered for transformers with a nominal capacity of 50 kVA. The fuse incorporates a centre-mounted operating indicator together with live gripping lugs, allowing quick visual inspection and safe replacement using an approved NH fuse puller.
Its robust ceramic body, DIN NH construction and high breaking capacity make this fuse link ideal for transformer feeders, industrial distribution boards and commercial electrical installations where reliable transformer protection is essential.
Unlike general-purpose gG fuse links, the gTr characteristic is specifically developed for transformer protection. It tolerates the high magnetising inrush current that occurs when transformers are energised while still providing dependable protection against overloads and short-circuit faults. This helps maximise service continuity while protecting valuable transformer assets.
The NH2GTR50KVA is ideal for low voltage transformer feeders in industrial facilities, commercial buildings and utility distribution systems where dependable transformer protection and coordinated fault discrimination are required.
Tick the specs you need, then view products that match.
| Fuse Indication | Visual indicator | |
|---|---|---|
| Voltage | 400 V | |
| Device Type | Fuse link | |
| Fuse Type | NH (DIN) | |
| Fuse Size | NH2 | |
| Fuse Class | gTr | |
| Current | 72 A | |
| Manufacturer | Mersen | |
| Item number | S1028691 | |
| Series | NH Fuse-links gTr 400 VAC | |
| Model | NH2GTR50KVA | |
| Product type | NH transformer protection fuse link | |
| Fuse size | NH2 | |
| Rated current | 72 A | |
| Transformer nominal capacity | 50 kVA | |
| Rated voltage | 400 V AC | |
| Operating characteristic | gTr | |
| Current type | AC | |
| Indicator | Centre indicator | |
| Connection type | Live gripping lugs | |
| Body width | 40 mm | |
| Power dissipation | 5.5 W | |
| Weight | Approx. 0.5 kg | |
| Standards | DIN NH / IEC | |
| RoHS compliant | Yes | |
| HS Code | 85361090 | |
| Country of Manufacture | Hungary |
This fuse link is specifically designed to protect low voltage distribution transformers against overloads and short circuits.
The NH2GTR50KVA is designed for transformers with a nominal capacity of 50 kVA.
This transformer protection fuse has a 72 A rated current.
The gTr characteristic is optimised for transformer protection, allowing transformer energisation inrush currents while providing reliable fault protection.
The centre indicator provides a clear visual indication when the fuse has operated, helping maintenance personnel identify and replace the fuse quickly.
Mersen NH gTr fuse links are widely specified by electrical engineers and transformer manufacturers for dependable protection of low voltage transformers, delivering reliable operation and excellent coordination with transformer characteristics.