Mersen NH1GG50V125-1 NH Size 1 gG fuse link rated at 125 A, 500 V AC and 250 V DC, with a 120 kA AC breaking capacity, isolated gripping lugs and a double operating indicator.
£11.16
The Mersen NH1GG50V125-1 is a dependable NH Size 1 gG low voltage fuse link designed to provide full-range protection for industrial power distribution systems, switchgear and electrical equipment. Its gG operating characteristic protects suitable cables and conductors against both overload and short-circuit currents, making it a practical choice for demanding commercial and industrial installations.
Rated at 125 A, 500 V AC and 250 V DC, this Mersen NH fuse link combines strong current-limiting performance with a high 120 kA AC breaking capacity. This enables the fuse to interrupt substantial prospective fault currents while helping to reduce the thermal and electrodynamic stress placed on downstream equipment.
The NH1GG50V125-1 incorporates isolated gripping lugs for improved handling safety and a double operating indicator for quick identification after operation. Its durable ceramic body, plain blade terminals and standard NH1 dimensions make it suitable for installation in compatible NH fuse bases by qualified electrical professionals.
The Mersen NH1GG50V125-1 provides full-range protection across both overload and short-circuit conditions. During sustained overcurrent, the fuse element operates to disconnect the affected circuit before excessive heating can damage cables, insulation or connected equipment. During a severe short circuit, its current-limiting action helps restrict the peak fault current and associated energy.
This combination makes the fuse suitable for protecting feeders, distribution circuits, industrial switchgear and general electrical installations. Correct fuse selection must account for the circuit voltage, normal load current, prospective fault level, cable capacity and coordination requirements with upstream and downstream protective devices.
The NH system is a plug-in fuse system comprising a fuse base, blade-contact fuse link and an appropriate low voltage HRC fuse replacement device. As the design does not prevent different current ratings from being fitted into the same compatible base, installation and replacement should only be undertaken by qualified electrical personnel.
Tick the specs you need, then view products that match.
| Fuse Indication | Dual indicator | |
|---|---|---|
| Current | 125 A | |
| Voltage | 500 V | |
| Device Type | Fuse link | |
| Fuse Type | NH (DIN) | |
| Fuse Size | NH1 | |
| Fuse Class | gG | |
| Manufacturer | Mersen | |
| Product Series | NH gG 500 V Fuse Links | |
| Catalogue Number | NH1GG50V125-1 | |
| Item Number | T236043 | |
| EAN / UPC | 3605340319439 | |
| Product Type | Low voltage NH fuse link | |
| Fuse Size | NH1 | |
| Rated Current | 125 A | |
| Rated Voltage AC | 500 V AC | |
| Rated Voltage DC | 250 V DC | |
| AC / DC Compatibility | AC and DC | |
| Operating Characteristic | gG | |
| AC Breaking Capacity | 120 kA | |
| Indication System | Double indicator | |
| Gripping Lugs | Isolated | |
| Terminal Material | Brass | |
| Terminal Type | Plain blades | |
| Body Material | Ceramic | |
| Mounting | Clip mounting / NH fuse base | |
| Product Width | 30 mm | |
| Product Length | Approximately 135 mm | |
| Product Height | Approximately 64 mm | |
| Power Dissipation at Rated Current | 11.8 W | |
| Product Weight | Approximately 0.28 kg | |
| RoHS Compliant | Yes | |
| Applicable Fuse Standard | IEC 60269 / DIN NH | |
| HS Code | 85361090 | |
| Country of Manufacture | Hungary |
It is used to protect suitable industrial cables, conductors, switchgear and distribution circuits against overload and short-circuit currents.
The fuse link has a rated current of 125 A.
The NH1GG50V125-1 is rated for operation at up to 500 V AC and 250 V DC.
A gG fuse provides full-range protection, covering both overload currents and short-circuit faults in general-purpose cable and distribution circuits.
The NH1GG50V125-1 has an AC breaking capacity of 120 kA under its specified operating conditions.
The double indicator provides clear visual confirmation that the fuse has operated, helping maintenance personnel locate a faulted fuse more quickly.
Yes. This model has isolated gripping lugs, which help reduce accidental contact risk during professional installation and replacement using an approved NH fuse puller.
Mersen NH fuse links are widely specified by electrical engineers, panel builders, switchgear manufacturers and industrial maintenance teams for dependable, standards-based protection of low voltage power distribution systems.