Mersen NH0AM69V125 DIN NH0 aM fuse-link rated at 125 A and 690 V AC, designed to provide short-circuit protection for industrial motors and motor control equipment.
£9.11
The Mersen NH0AM69V125 is a high-performance DIN NH aM fuse-link designed to provide dependable short-circuit protection for motors, motor starters and associated industrial electrical equipment. As part of the Mersen NH motor protection range, this NH0 fuse-link accommodates the temporary inrush currents produced during motor starting while responding rapidly to damaging fault currents.
The specialised aM operating characteristic makes the NH0AM69V125 particularly suitable for motor circuits in machinery, manufacturing equipment and industrial control systems. As an aM partial-range fuse-link, it provides short-circuit protection and must be used alongside a suitable overload protection device, such as a thermal overload relay or electronic motor protection relay.
With a rated current of 125 A, a rated voltage of 690 V AC and an 80 kA breaking capacity, the NH0AM69V125 is suitable for demanding low-voltage motor control applications. Its standard NH0 format, live gripping lugs and integrated double indicator support straightforward installation, removal and fault identification within compatible NH fuse bases.
The Mersen NH0AM69V125 is engineered to protect motor circuits against high short-circuit currents while allowing the elevated current normally drawn during motor acceleration. Its current-limiting performance helps reduce the thermal and electrodynamic stress imposed on contactors, cables, switchgear and connected equipment during a fault.
Because the aM characteristic does not provide complete overload protection, the fuse-link should be coordinated with a correctly selected overload relay. This combination provides effective motor protection while helping minimise nuisance operation during normal starting and operating conditions.
Tick the specs you need, then view products that match.
| Current | 125 A | |
|---|---|---|
| Voltage | 690 V | |
| Device Type | Fuse link | |
| Fuse Type | NH (DIN) | |
| Fuse Size | NH0 | |
| Fuse Class | aM | |
| Manufacturer | Mersen | |
| Series | NH Fuse-links aM 690 VAC | |
| Model | NH0AM69V125 | |
| Manufacturer item number | Y227882 | |
| Product type | DIN NH motor protection fuse-link | |
| Fuse size | NH0 | |
| Rated current | 125 A | |
| Rated voltage | 690 V AC | |
| Operating characteristic | aM | |
| Protection range | Partial-range short-circuit protection | |
| Breaking capacity | 80 kA AC | |
| Current type | AC | |
| Indicator type | Double indicator | |
| Gripping lugs | Live gripping lugs | |
| Body width | 30 mm | |
| Mounting type | Compatible NH fuse base | |
| Installation requirement | Qualified electrical personnel | |
| HS Code | 85361090 | |
| Country of Manufacture | Hungary |
This fuse-link provides short-circuit protection for industrial motors, motor starters, contactors and associated electrical equipment.
The NH0AM69V125 has a rated current of 125 A.
The fuse-link is designed for motor circuits operating at up to 690 V AC.
The aM characteristic identifies a partial-range motor fuse that permits normal motor starting currents while providing short-circuit protection.
No. The NH0AM69V125 must be used with a suitable overload relay or another compatible overload protection device to provide complete motor protection.
Mersen NH aM fuse-links are widely used by electrical engineers, panel builders and machinery manufacturers for dependable short-circuit protection, effective current limitation and reliable operation in demanding motor control systems.