Mersen S209362 Limitor-PD high voltage DIN back-up fuse rated at 36 kV AC and 6.3 A, with a 32 kA breaking capacity and an 80 N striker for transformer protection.
£78.66
The Mersen S209362 is a high performance Limitor®-PD high voltage DIN back-up fuse designed to protect transformers and associated medium voltage equipment against damaging short-circuit currents. Identified by the catalogue number 45DB360V6,3PD, it provides dependable current-limiting protection for industrial, commercial and utility power distribution systems.
Manufactured using a robust ceramic body, pure silver fuse elements and silver-plated copper end caps, the S209362 is engineered for consistent electrical performance and long-term reliability. As a back-up fuse manufactured in accordance with IEC 60282-1 and VDE 0670 T402, it interrupts substantial fault currents whilst helping reduce thermal and mechanical stress on transformers and switchgear.
Rated at 36 kV AC and 6.3 A, the S209362 has a 56 mm diameter, a 537 mm overall length and an integrated 80 N striker. Its DIN-format cylindrical construction enables installation within compatible high voltage fuse holders and transformer protection assemblies.
High voltage back-up fuses interrupt substantial short-circuit currents before excessive thermal and mechanical forces can damage transformers, cables and associated switchgear. Their current-limiting action reduces the peak fault current and total energy passed into the protected electrical system.
The Mersen S209362 is intended for use within a correctly coordinated medium voltage protection system. Its integrated striker can activate compatible switch-disconnectors or indication mechanisms when the fuse operates, helping isolate the affected circuit and improve installation safety.
Tick the specs you need, then view products that match.
| Device Type | Fuse link | |
|---|---|---|
| Fuse Type | High voltage | |
| Current | 6.3 A | |
| Voltage | 36000 V | |
| Manufacturer | Mersen | |
| Series | Limitor®-PD Back-up Fuses | |
| Model | S209362 | |
| Catalogue number | 45DB360V6,3PD | |
| EAN / UPC | 3605340218541 | |
| Product type | High voltage DIN back-up fuse | |
| Primary application | Transformer protection | |
| Rated voltage | 36 kV AC | |
| Rated current | 6.3 A | |
| Rated breaking capacity | 32 kA | |
| Power dissipation | 39 W | |
| Fuse diameter | 56 mm | |
| Fuse length | 537 mm | |
| Mounting type | Clip mounting | |
| Striker force | 80 N | |
| Fuse body material | Ceramic | |
| Fuse-element material | Pure silver | |
| End-cap material | Silver-plated copper | |
| Current type | AC | |
| RoHS compliance | Compliant | |
| Standards | IEC 60282-1, VDE 0670 Part 4, VDE 0670 Part 402, DIN 43625 | |
| Weight | Approx. 2.7 kg | |
| HS Code | 85351000 | |
| Country of Manufacture | Hungary |
The S209362 is a high voltage DIN back-up fuse designed to protect compatible transformers and switchgear against damaging short-circuit currents.
The fuse has a rated operating voltage of 36 kV AC.
The Mersen S209362 has a rated current of 6.3 A.
The fuse measures approximately 56 mm in diameter and 537 mm in overall length.
Yes. It incorporates an integrated 80 N striker for operation with compatible switch-disconnectors and indication equipment.
Mersen Limitor® high voltage fuse-links are trusted by utilities, switchgear manufacturers and electrical engineers to provide dependable transformer protection and reliable fault interruption within medium voltage power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.