Mersen X1000267 Limitor-PTD DIN high voltage back-up fuse-link rated at 12 kV AC and 31.5 A, with a 63 kA breaking capacity and 80 N thermal striker for transformer protection.
£75.78
The Mersen X1000267 is a high performance Limitor®-PTD DIN high voltage back-up fuse-link designed to protect medium voltage transformers against the thermal and dynamic effects of short-circuit currents. Manufactured in accordance with IEC 60282-1 and VDE 0670 T402, it provides dependable fault interruption for air insulated and gas insulated switchgear.
As part of the advanced Mersen Limitor®-PTD range, the X1000267 incorporates controlled power dissipation technology and an integrated thermal striker. These features help manage thermal loading within enclosed switchgear while supporting reliable operation of compatible protection and switching mechanisms.
Rated at 12 kV AC with a 31.5 A current rating, the X1000267 has a 56 mm diameter × 292 mm fuse size and a maximum breaking capacity of 63 kA. Its pure silver fuse elements, silver-plated copper terminals and ceramic body provide reliable electrical performance and long service life.
High voltage back-up fuse-links interrupt significant short-circuit currents before they can expose transformers and associated switchgear to damaging thermal and mechanical stresses. This helps improve installation safety, reduce equipment damage and minimise costly electrical downtime.
The Mersen Limitor®-PTD range combines controlled power dissipation with an integrated thermal striker, making it well suited to modern air insulated and gas insulated switchgear. The X1000267 provides dependable transformer protection for both new electrical installations and maintenance replacement projects.
Tick the specs you need, then view products that match.
| Fuse Indication | Striker | |
|---|---|---|
| Device Type | Fuse link | |
| Fuse Type | High voltage | |
| Current | 31.5 A | |
| Voltage | 12000 V | |
| Manufacturer | Mersen | |
| Series | Limitor®-PTD | |
| Model | X1000267 | |
| Catalogue number | 45DB120V32PTD | |
| Product type | High voltage DIN back-up fuse-link | |
| Application | Transformer protection | |
| Rated voltage | 12 kV AC | |
| Rated current | 31.5 A | |
| Current type | AC | |
| Breaking capacity | 63 kA | |
| Minimum interrupting rating | 110 A | |
| Clearing I²t at rated voltage | 7 kA²s | |
| Fuse size | Ø56 × 292 mm | |
| Overall product length | 358 mm | |
| Mounting type | Clip mounting | |
| Indication system | Thermal striker | |
| Striker force | 80 N | |
| Terminal material | Silver-plated copper | |
| Terminal type | Cylindrical | |
| Body material | Ceramic | |
| Fuse element material | Pure silver | |
| Power dissipation at rated current | 39 W | |
| Design | VDE T402 | |
| Applicable standards | IEC 60282-1, VDE 0670 T402 | |
| RoHS compliant | Yes | |
| Product weight | 1.7 kg | |
| EAN / UPC | 3605340456608 | |
| HS Code | 85351000 | |
| Country of Manufacture | Hungary |
The X1000267 is a high voltage DIN back-up fuse-link designed to protect medium voltage transformers against the thermal and dynamic effects of short-circuit currents.
The fuse-link has a rated voltage of 12 kV AC.
The Mersen X1000267 has a rated current of 31.5 A.
The fuse has a maximum AC breaking capacity of 63 kA.
Yes. It includes an integrated 80 N thermal striker for indication and operation with compatible switchgear mechanisms.
Mersen Limitor®-PTD high voltage fuse-links are widely used by utilities, transformer manufacturers, switchgear builders and industrial engineers for dependable transformer protection and controlled thermal performance in medium voltage electrical systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.