Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Mersen A1000132 Limitor-PT DIN high-voltage transformer back-up fuse rated at 12 kV AC and 100 A, with a 63 kA breaking capacity and integrated 80 N CPD striker.
£117.31
The Mersen A1000132, catalogue number 45DB120V100PT, is a high-performance DIN high-voltage back-up fuse designed to protect transformers against damaging short-circuit currents. Part of the Mersen Limitor®-PT series, it combines dependable current limitation with controlled power dissipation for use in modern high-voltage switchgear and controlgear.
Rated at 12 kV AC and 100 A, the A1000132 rapidly interrupts severe fault currents while limiting the peak current and energy passed into the protected system. This helps reduce thermal and mechanical stress on transformer windings, cables, contacts and associated switchgear components.
The fuse features pure silver fuse elements, silver-plated copper terminals and a robust ceramic body. Its integrated 80 N CPD striker provides controlled power dissipation and can actuate compatible switchgear mechanisms when the fuse operates. With a nominal fuse size of 78 × 292 mm, it is designed for secure clip mounting in compatible DIN high-voltage fusegear.
The Mersen A1000132 is designed to interrupt high short-circuit currents before they can cause extensive damage to a transformer or its associated electrical equipment. Its current-limiting action restricts both the peak fault current and the total energy allowed to pass through the circuit.
As a back-up fuse, the A1000132 is intended to clear high-value fault currents and must be coordinated with suitable switching or protective equipment for lower overcurrent conditions. Correct selection should consider transformer power, system voltage, inrush current, ambient conditions and switchgear requirements.
Tick the specs you need, then view products that match.
| Fuse Indication | Striker | |
|---|---|---|
| Voltage | 120 V | |
| Device Type | Fuse link | |
| Fuse Type | High voltage | |
| Current | 100 A | |
| Manufacturer | Mersen | |
| Series | Limitor®-PT | |
| Manufacturer part number | A1000132 | |
| Catalogue number | 45DB120V100PT | |
| Product type | DIN high-voltage transformer back-up fuse | |
| Rated voltage | 12 kV AC IEC | |
| Rated current | 100 A | |
| Maximum breaking capacity | 63 kA | |
| Minimum interrupting current | 500 A | |
| Clearing I²t at rated voltage | 200 kA²s | |
| Power dissipation at rated current | Approximately 156 W | |
| Fuse diameter | Approximately 78 mm | |
| Nominal fuse length | Approximately 292 mm | |
| Mounting type | Clip mounting | |
| Terminal type | Cylindrical | |
| Terminal material | Silver-plated copper | |
| Fuse element material | Pure silver | |
| Body material | Ceramic | |
| Indication system | CPD striker | |
| Striker force | 80 N | |
| Striker travel | Approximately 30 mm | |
| Current type | AC | |
| Approximate weight | 2.2 kg | |
| EAN | 3605340453058 | |
| Compliance | RoHS compliant | |
| Applicable standard | IEC 60282-1 | |
| HS Code | 85351000 |
The A1000132 is a high-voltage back-up fuse designed to protect transformers and associated switchgear against damaging short-circuit currents.
The fuse has an IEC rated voltage of 12 kV AC.
The Mersen A1000132 has a rated current of 100 A.
The fuse has a maximum AC breaking capacity of 63 kA and a minimum interrupting current of 500 A.
The integrated 80 N CPD striker provides controlled power dissipation and can operate a compatible switchgear tripping or indication mechanism when the fuse operates.
No. It is a back-up fuse designed primarily to interrupt high short-circuit currents. It must be coordinated with suitable protective equipment for complete transformer protection.
Mersen Limitor®-PT fuse-links are used by transformer manufacturers, utilities, switchgear builders and industrial engineers to provide reliable short-circuit protection in demanding medium-voltage power systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.