Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Mersen N1000121 Limitor-PT high voltage DIN back-up fuse-link rated at 12 kV AC and 4 A, with controlled power dissipation, a 63 kA breaking capacity and an integrated 80 N striker.
£61.19
The Mersen N1000121 is a high voltage DIN back-up fuse-link designed to protect transformers and associated medium voltage equipment against damaging short-circuit currents. Part of the Mersen Limitor®-PT series, it combines dependable fault interruption with controlled power dissipation for use in high voltage switchgear, controlgear and electrical distribution systems.
This fuse-link uses pure silver fuse elements, silver-plated copper terminals and a durable ceramic body to provide reliable electrical performance in demanding installations. Its back-up operating characteristic allows it to interrupt high fault currents while being coordinated with suitable protective equipment for lower-level overload conditions.
Rated at 12 kV AC and 4 A, the N1000121 incorporates an 80 N striker for fault indication or operation of compatible switchgear. Its DIN-format construction, controlled power dissipation and high breaking capacity make it suitable for transformer substations, ring main units and industrial medium voltage distribution equipment.
High voltage back-up fuse-links protect transformers by rapidly interrupting significant short-circuit currents before excessive thermal and mechanical stress can damage transformer windings, switchgear or connected distribution equipment. Their current-limiting action can also reduce the peak energy passed into a fault.
The Mersen N1000121 includes controlled power dissipation technology, helping limit heat generation within compact switchgear installations. Its integrated striker can activate compatible switching equipment or provide a clear indication when the fuse-link has operated.
Tick the specs you need, then view products that match.
| Fuse Indication | Striker | |
|---|---|---|
| Voltage | 120 V | |
| Device Type | Fuse link | |
| Fuse Type | High voltage | |
| Current | 4 A | |
| Manufacturer | Mersen | |
| Series | Limitor®-PT | |
| Item number | N1000121 | |
| Catalogue number | 45DB120V4PT | |
| Product type | High voltage DIN back-up fuse-link | |
| Primary application | Transformer protection | |
| Rated voltage | 12 kV AC IEC | |
| Rated current | 4 A | |
| Current type | AC | |
| Fuse size | 56 mm diameter × 292 mm length | |
| Overall product length | 358 mm | |
| Mounting type | Clip mounting | |
| Maximum breaking capacity | 63 kA | |
| Minimum interrupting rating | 22 A | |
| Clearing I²t at rated voltage | 0.55 kA²s | |
| Power dissipation at rated current | 6 W | |
| Indication system | Striker | |
| Striker force | 80 N | |
| Terminal material | Silver-plated copper | |
| Terminal type | Cylindrical | |
| Body material | Ceramic | |
| Design | VDE T4 | |
| Product weight | Approx. 1.6 kg | |
| RoHS compliant | Yes | |
| EAN | 3605340452945 | |
| Applicable standard | IEC 60282-1 | |
| HS Code | 85351000 |
The Mersen N1000121 is a high voltage DIN back-up fuse-link designed to protect transformers and associated switchgear against damaging short-circuit currents.
The fuse-link has a rated voltage of 12 kV AC and a rated current of 4 A.
The Mersen N1000121 has a maximum AC breaking capacity of 63 kA.
Yes. It incorporates an 80 N striker that can provide fault indication or operate compatible switchgear when the fuse-link functions.
The fuse body measures approximately 56 mm in diameter and 292 mm in length, with an overall product length of approximately 358 mm.
The N1000121 is a back-up fuse intended primarily to interrupt high short-circuit currents. It should be coordinated with suitable equipment that provides protection against lower-level overload currents.
Mersen Limitor® high voltage fuse-links are widely used by utilities, switchgear manufacturers, electrical contractors and industrial engineers for dependable transformer and medium voltage equipment protection.
We use cookies