Mersen X1000152 Limitor-G DIN high voltage general purpose fuse-link rated at 12 kV AC and 10 A, with a 40 kA breaking capacity and 80 N striker for transformer protection.
£125.23
The Mersen X1000152 is a dependable Limitor®-G DIN high voltage general purpose fuse-link designed to protect medium voltage transformers against short-circuit currents and low overcurrents. Manufactured in accordance with IEC 60282-1, it provides reliable fault interruption for high voltage switchgear, controlgear and electrical distribution systems.
As part of the established Mersen Limitor®-G range, the X1000152 uses pure silver fuse elements, silver-plated copper terminals and a durable ceramic body. This high quality construction provides excellent current limitation, rapid fault clearing and dependable long-term performance in demanding medium voltage installations.
Rated at 12 kV AC with a 10 A current rating, the X1000152 has a fuse body measuring 65 mm in diameter and 292 mm in length. Its integrated 80 N striker provides clear fuse operation indication and supports compatible switchgear tripping mechanisms.
General purpose high voltage fuse-links provide protection across a wider current range than conventional back-up fuses. The X1000152 is designed to interrupt high short-circuit currents as well as lower overcurrents, helping protect transformers and associated switchgear against thermal and mechanical damage.
The Mersen Limitor®-G range combines high current limitation, low switching voltage and rapid fault clearing with a non-ageing fuse element design. These characteristics make the X1000152 suitable for both new transformer protection systems and replacement applications within established medium voltage installations.
Tick the specs you need, then view products that match.
| Fuse Indication | Striker | |
|---|---|---|
| Voltage | 120 V | |
| Device Type | Fuse link | |
| Fuse Type | High voltage | |
| Current | 10 A | |
| Manufacturer | Mersen | |
| Series | Limitor®-G | |
| Model | X1000152 | |
| Catalogue number | 45DG120V10P | |
| Product type | High voltage DIN general purpose fuse-link | |
| Application | Transformer protection | |
| Rated voltage | 12 kV AC | |
| Rated current | 10 A | |
| Current type | AC | |
| Breaking capacity | 40 kA | |
| Clearing I²t at rated voltage | 3.8 kA²s | |
| Fuse size | Ø65 × 292 mm | |
| Overall product length | 358 mm | |
| Mounting type | Clip mounting | |
| Indication system | Striker | |
| Striker force | 80 N | |
| Terminal material | Silver-plated copper | |
| Terminal type | Cylindrical | |
| Body material | Ceramic | |
| Fuse element material | Pure silver | |
| Power dissipation at rated current | 8 W | |
| Applicable standard | IEC 60282-1 | |
| RoHS compliant | Yes | |
| Product weight | 2.3 kg | |
| EAN / UPC | 3605340453256 | |
| HS Code | 85351000 | |
| Country of Manufacture | Hungary |
The X1000152 is a general purpose high voltage fuse-link designed to protect medium voltage transformers against short-circuit currents and low overcurrents.
The fuse-link has a rated voltage of 12 kV AC.
The Mersen X1000152 has a rated current of 10 A.
The fuse has a maximum AC breaking capacity of 40 kA.
Yes. It includes an integrated 80 N striker for fuse operation indication and compatible switchgear tripping.
Mersen Limitor®-G high voltage fuse-links are widely used by utilities, transformer manufacturers, switchgear builders and industrial engineers for dependable protection against short-circuit currents and overcurrents in medium voltage electrical systems.