Reliable time-delay fuse rated at 10A for AC/DC circuits up to 600VAC and 300VDC, with a high interrupting rating of 200 kA. Supplied as a 6 pack with ferrule terminals for easy installation in industrial control panels.
£12.12
The Mersen ATDR10 is a compact 10 A Class CC time-delay fuse designed to provide dependable overload and short-circuit protection for industrial control systems, motors and branch circuits. Part of the established Mersen Amp-Trap 2000 ATDR series, it combines high current-limiting performance with the ability to withstand brief, harmless inrush currents.
Its time-delay operating characteristic helps prevent nuisance fuse operation during motor starting, transformer energisation and other temporary current surges. When a sustained overload or high-level fault occurs, the ATDR10 interrupts the circuit to help protect conductors, control components and connected equipment from damage.
With a rated current of 10 A and voltage ratings of up to 600 V AC and 300 V DC, the Mersen ATDR10 is suitable for demanding industrial installations. Its compact rejection-style Class CC format also helps panel builders conserve enclosure space while maintaining reliable branch-circuit protection.
The Mersen ATDR10 protects electrical circuits by interrupting excessive current before conductors and connected equipment sustain serious thermal or mechanical damage. Its current-limiting design restricts peak fault current and reduces the total energy permitted to pass through the circuit during a short circuit.
The fuse's time-delay characteristic allows it to tolerate temporary operating surges without sacrificing protection against sustained overloads. This makes the ATDR10 a practical choice for industrial motors, control transformers, automation equipment and branch circuits requiring compact, high-performance protection.
Tick the specs you need, then view products that match.
| Current | 10 A | |
|---|---|---|
| Voltage | 600 V | |
| Fuse Type | UL class | |
| Fuse Class | Time delay | |
| Item number | ATDR10-6PK | |
| Description | Fuse ATDR - Class CC - Time-Delay 600VAC 300VDC 10A Ferrule Amp-Trap 2000® 6 pack | |
| EAN/UPC Code | 782001355401 | |
| Rated voltage AC UL | 600 V | |
| Rated voltage DC UL | 300 V | |
| Frequency (Hz) | 50/60 Hz | |
| Ampere Rating | 10 A | |
| AC or DC | AC/DC | |
| Fuse Class | Class CC | |
| Speed/Characteristic | Time Delay | |
| Mounting | Clip | |
| AC Max I.R./Breaking Capacity | I1: 200 kA | |
| Connection/Terminal Material | Tin-Plated Copper | |
| Connection/Terminal Type | Ferrule | |
| Product Diameter | 10.4 mm | |
| Product Length | 38.1 mm | |
| Sell Pack Quantity | 6 EA | |
| Sell Pack Weight | 0.059 kg | |
| Sell Pack Width | 67.3 mm | |
| Sell Pack Length | 47.8 mm | |
| Sell Pack Height | 12.7 mm | |
| Product group | Low Voltage UL/CSA Fuses | |
| Body/Insulating Material | GMG | |
| Product Weight | 0.0091 kg | |
| HS Code | 85361010 | |
| Country of Manufacture | Mexico |
The ATDR10 protects motors, transformers, industrial controls, machinery and branch circuits against sustained overloads and short circuits.
The Mersen ATDR10 has a rated current of 10 A.
Yes. Its time-delay characteristic allows it to tolerate brief motor-starting and transformer inrush currents while maintaining effective overcurrent protection.
The fuse is rated for applications up to 600 V AC and 300 V DC.
The ATDR10 should be installed in a correctly rated Class CC rejection-style fuse holder or fuse block.
Mersen Amp-Trap 2000 ATDR Class CC fuses are widely specified by electrical engineers, OEMs and panel builders for compact, highly current-limiting protection of industrial equipment and branch circuits.