British Standard fuse-link IEC BS88 gM Type A3 415VAC 240VDC 63M80A BTSDS Offset Tag providing reliable circuit protection for AC and DC applications.

SKU: BTSDS42V63M80Alt SKU: BTSDS42V63M80MPN: H1019183
Price
List Price £28.31 ex VAT
Your Price (ex VAT) Save 60%
£11.32 60% OFF
You save £16.99 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £11.32
Trade pricing is personalised to your account

Manufacturer Lead Time

Sold in packs of 10

£11.32

Why Choose the Mersen BTSDS42V63M80 BS88 Offset Tag Fuse-Link?

The Mersen BTSDS42V63M80 is a British Standard BS88 Type A3 offset tag fuse-link designed for general-purpose motor protection (gM) in low-voltage industrial electrical systems. Rated 63M80 A, it operates at up to 415 V AC and 240 V DC, providing dependable short-circuit protection for motor circuits while accommodating normal motor starting currents. It complies with EN 60269-2 Section II and BS88 Part 2.

The offset tag construction allows secure installation in compatible BS88 fuse holders, fuse-switch disconnectors and bolted busbar assemblies. Its gM operating characteristic offers excellent current limitation during fault conditions, helping protect motors, starters, contactors, cables and associated switchgear.

Key Advantages

  • British Standard BS88 Type A3 offset tag fuse-link.
  • 63M80 A gM motor protection rating.
  • 415 V AC / 240 V DC rated operation.
  • Designed to withstand normal motor starting currents.
  • Excellent current-limiting characteristics.
  • Suitable for industrial motor control centres and switchgear.

Key Features

  • Mersen BTSDS offset tag fuse series.
  • 63M80 A motor rating.
  • 415 V AC rated voltage.
  • 240 V DC rated voltage.
  • gM utilisation category.
  • Type A3 BS88 fuse-link.
  • Manufactured to EN 60269-2 Section II and BS88 Part 2.
  • 80 kA AC and 40 kA DC breaking capacity.

Reliable Protection for Motor Circuits

The Mersen BTSDS42V63M80 is engineered specifically for motor applications where temporary high inrush currents occur during starting. Its gM operating characteristic allows these normal transient currents while rapidly clearing high fault currents to minimise damage to motors, cables and associated equipment.

Its current-limiting design reduces thermal and mechanical stress during fault conditions, helping improve equipment reliability and minimise downtime in industrial installations.

Typical Applications

  • Motor control centres.
  • Industrial switchgear.
  • Motor starters and contactor assemblies.
  • Pumps and compressors.
  • Conveyor systems.
  • OEM machinery and automation equipment.

Technical Specifications

Tick the specs you need, then view products that match.

Fuse Class gM
Voltage 415 V
Item number H1019183
Catalogue No BTSDS42V63M80
Description British Standard fuse-link IEC BS88 gM Type A3 415VAC 240VDC 63M80A BTSDS Offset Tag
EAN/UPC Code 3605340515824
Rated voltage AC IEC 415 V
Rated voltage DC IEC 240 V
In M Ich 63M80 A
RoHS Compliant Yes
AC or DC AC/DC
Speed/Characteristic gM
Fuse Size A3
Mounting Bolted
Clearing I2t At Rated Voltage 38250 A²s
Melting I2t 8500 A²s
AC Max I.R./Breaking Capacity I1: 80 kA
Max. Rated Breaking Capacity DC 40 kA
Connection/Terminal Material Tin-Plated Copper
Connection/Terminal Type Offset Tag
Product Diameter 21 mm
Product Width 22.5 mm
Product Length 87 mm
Sell Pack Quantity 10 EA
Sell Pack Weight 0.58 kg
Sell Pack Width 94 mm
Sell Pack Length 110 mm
Sell Pack Height 49 mm
Product group Low Voltage IEC Fuses
Body/Insulating Material Ceramic
Product Weight 0.058 kg
Power Dissipation at Rated Current Value 5.1 W
HS Code 85361050
Country of Manufacture India

Frequently Asked Questions

What is the Mersen BTSDS42V63M80 used for?

The BTSDS42V63M80 is designed for general-purpose motor protection, providing short-circuit protection for industrial motors, starters, cables and associated switchgear.

What does the 63M80 rating mean?

The 63M80 designation identifies a gM motor fuse-link with a 63 A fuse element coordinated for motor circuits up to 80 A, allowing motor starting currents while providing short-circuit protection.

What voltage is the BTSDS42V63M80 rated for?

The fuse-link is rated for operation at up to 415 V AC and 240 V DC.

What is the breaking capacity of this fuse?

The BTSDS42V63M80 has a rated breaking capacity of 80 kA AC and 40 kA DC.

Can the BTSDS42V63M80 be reset after operation?

No. This is a non-resettable fuse-link and must be replaced with an identical correctly rated fuse after clearing a fault.

Trusted Motor Protection from Mersen

Mersen BS88 gM fuse-links provide dependable motor circuit protection in industrial installations, delivering high breaking capacity, excellent current limitation and compliance with recognised British and IEC standards.