Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
High-performance BS88 gG Type C3 fuse-link designed for industrial power and control circuits up to 690VAC with 670A rating and central bolted tag connection.
£202.94
The Mersen BTLM69V670 is a high-current industrial fuse link designed to provide reliable overload and short-circuit protection in demanding low-voltage electrical distribution systems. Manufactured by Mersen, it is engineered for applications requiring dependable fault interruption, effective current limitation and robust performance.
This fuse link helps protect cables, switchgear, busbar systems and other electrical equipment by rapidly disconnecting the circuit when excessive current occurs. Its industrial construction makes it suitable for use by panel builders, electrical engineers, original equipment manufacturers and maintenance professionals.
With a rated current of 670 A and a rated operating voltage of up to 690 V AC, the BTLM69V670 is suitable for high-power distribution equipment, industrial switchboards and heavy-duty electrical installations. Its bolted connection format supports secure installation within compatible fuse bases and power distribution assemblies.
High-current fuse links such as the Mersen BTLM69V670 protect electrical installations by interrupting potentially damaging fault currents. During an overload or short circuit, the fuse element operates to disconnect the affected circuit and limit the amount of energy transferred to cables, switchgear and connected equipment.
The BTLM69V670 is designed for industrial systems where high current capacity, secure mounting and dependable fault protection are essential. Its bolted construction supports reliable integration into power distribution panels, switchboards and heavy-duty electrical assemblies.
Tick the specs you need, then view products that match.
| Fuse Class | gG | |
|---|---|---|
| Voltage | 690 V | |
| Item number | D1019271 | |
| Catalogue No | BTLM69V670 | |
| Description | British Standard fuse-link IEC BS88 gG Type C3 690VAC 69V670A BTLM Central Bolted Tag | |
| EAN/UPC Code | 3605340515664 | |
| Rated voltage AC IEC | 690 V | |
| In M Ich | 69V670 A | |
| RoHS Compliant | Yes | |
| AC or DC | AC | |
| Speed/Characteristic | gG | |
| Fuse Size | C3 | |
| Mounting | Bolted | |
| Clearing I2t At Rated Voltage | 10100 kA²s | |
| Melting I2t | 1950 kA²s | |
| AC Max I.R./Breaking Capacity | I1: 80 kA | |
| Connection/Terminal Material | Tin-Plated Copper | |
| Connection/Terminal Type | Central Bolted Tag | |
| Product Diameter | 82.4 mm | |
| Product Length | 212 mm | |
| Sell Pack Quantity | 1 EA | |
| Sell Pack Weight | 1.4 kg | |
| Sell Pack Width | 90 mm | |
| Sell Pack Length | 210 mm | |
| Sell Pack Height | 85 mm | |
| Product group | Low Voltage IEC Fuses | |
| Body/Insulating Material | Ceramic | |
| Product Weight | 1.4 kg | |
| Power Dissipation at Rated Current Value | 60 W | |
| HS Code | 85361090 | |
| Country of Manufacture | India |
The BTLM69V670 is used to protect high-current industrial electrical circuits, cables, switchgear and distribution equipment against excessive current and short-circuit faults.
The Mersen BTLM69V670 has a rated current of 670 A.
The fuse link is rated for operation at up to 690 V AC.
It uses bolted tag connections and is installed within a compatible fuse base, switchboard or bolted power distribution assembly.
No. The BTLM69V670 is a sacrificial protection device and must be replaced with an appropriately rated fuse link after it has operated.
Mersen industrial fuse links are used by electrical engineers, panel builders and maintenance professionals to provide dependable fault protection, effective current limitation and reliable performance in high-power electrical distribution systems.
We use cookies