BS88 gM Type F1 fuse-link rated at 550VAC and 250VDC with 16M20A current rating and offset blade terminals, suitable for industrial and commercial circuit protection.
£2.15
The Mersen BNS55V16M20 is a compact British Standard motor protection fuse link designed to provide dependable short-circuit protection for industrial motors, motor starters and associated control equipment. Its motor-rated operating characteristic allows it to tolerate the temporary inrush current produced during motor starting while responding rapidly to severe electrical faults.
The BNS55V16M20 provides current-limiting protection that helps reduce the thermal and mechanical energy passed through to contactors, cables, switchgear and downstream components during a short circuit. This can minimise equipment damage, support effective protection coordination and reduce disruption within industrial motor-control systems.
With a 16M20 motor rating and a nominal voltage rating of 550 V AC, this Mersen fuse link is suitable for compatible low-voltage motor circuits and machinery installations. Its bolted-tag construction provides a secure electrical connection when installed in an appropriately rated fuse holder, switch-fuse unit or motor-control assembly.
Electric motors can draw several times their normal running current during start-up. A motor-rated fuse such as the Mersen BNS55V16M20 is designed to withstand this temporary inrush without unnecessary operation while still interrupting dangerous short-circuit currents quickly.
The fuse is normally used alongside a correctly selected overload relay or electronic motor protection device. The fuse provides high-level fault protection, while the overload device protects the motor against sustained overcurrent conditions. Selection should account for the motor current, starting method, starting duration, conductor capacity and prospective short-circuit current.
Tick the specs you need, then view products that match.
| Fuse Class | gM | |
|---|---|---|
| Voltage | 550 V | |
| Item number | V1019217 | |
| Catalogue No | BNS55V16M20 | |
| Description | British Standard fuse-link IEC BS88 gM Type F1 550VAC 250VDC 16M20A BNS Offset Blade | |
| EAN/UPC Code | 3605340517132 | |
| Rated voltage AC IEC | 550 V | |
| Rated voltage DC IEC | 250 V | |
| In M Ich | 16M20 A | |
| RoHS Compliant | Yes | |
| AC or DC | AC/DC | |
| Speed/Characteristic | gM | |
| Fuse Size | F1 | |
| Mounting | Clip | |
| Clearing I2t At Rated Voltage | 1250 A²s | |
| Melting I2t | 250 A²s | |
| AC Max I.R./Breaking Capacity | I1: 80 kA | |
| Max. Rated Breaking Capacity DC | 40 kA | |
| Connection/Terminal Material | Tin-Plated Copper | |
| Connection/Terminal Type | Offset Blade | |
| Product Diameter | 13.5 mm | |
| Product Length | 61 mm | |
| Sell Pack Quantity | 10 EA | |
| Sell Pack Weight | 0.173 kg | |
| Sell Pack Width | 37 mm | |
| Sell Pack Length | 73 mm | |
| Sell Pack Height | 70 mm | |
| Product group | Low Voltage IEC Fuses | |
| Body/Insulating Material | Ceramic | |
| Product Weight | 0.0173 kg | |
| Power Dissipation at Rated Current Value | 1.36 W | |
| HS Code | 85361050 | |
| Country of Manufacture | India |
The BNS55V16M20 is used to provide short-circuit protection for compatible industrial motors, motor starters, cables and associated control equipment.
The 16M20 designation identifies a motor-rated fuse link with a 16 A continuous current rating and motor-circuit characteristics associated with a 20 A fuse rating.
The Mersen BNS55V16M20 is intended for compatible industrial electrical systems with a nominal voltage rating of up to 550 V AC.
The fuse is primarily intended to provide short-circuit protection. A correctly selected overload relay or motor protection device is normally required to protect the motor against sustained overload conditions.
No. The BNS55V16M20 is a non-resettable fuse link and must be replaced with a correctly rated equivalent after it has operated.