MERSEN FUSE BEIT42V40 A1 BEIT42V40

MERSEN FUSE BEIT42V40 A1 BEIT42V40

British Standard fuse-link IEC BS88 gG Type A1 415VAC 250VDC 40A with Offset Tag terminals for reliable industrial circuit protection.

SKU: BEIT42V40Alt SKU: BEIT42V40MPN: B1019177
Price
List Price £4.55 ex VAT
Your Price (ex VAT) Save 60%
£1.82 60% OFF
You save £2.73 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1.82
Trade pricing is personalised to your account

Manufacturer Lead Time

Sold in packs of 10

£1.82

Why Choose the Mersen BEIT42V40 BS88 Offset Bolted Tag Fuse-Link?

The Mersen BEIT42V40 is a 40 A BS88 industrial fuse-link designed to provide dependable overload and short-circuit protection for low-voltage electrical distribution systems. Its general-purpose fuse characteristic makes it suitable for protecting cables, feeders, switchgear and connected industrial equipment.

Featuring an offset bolted tag arrangement, the BEIT42V40 provides a secure mechanical and electrical connection within compatible fuse carriers, fuse-switch disconnectors and distribution equipment. This established British Standard format is widely used in industrial and commercial installations where reliable circuit isolation and straightforward fuse replacement are required.

With a rated current of 40 A, an AC voltage rating of 415 V and a DC voltage rating of 250 V, the Mersen BEIT42V40 is suitable for a broad range of power distribution and equipment protection applications. Its current-limiting performance helps reduce the thermal and mechanical stress caused by high prospective fault currents.

Key Advantages

  • Reliable protection against overload and short-circuit currents.
  • 40 A rated current for industrial and commercial circuits.
  • Rated for operation at up to 415 V AC and 250 V DC.
  • Current-limiting performance helps reduce damaging fault energy.
  • Offset bolted tags provide a secure connection in compatible fusegear.
  • Replaceable construction supports straightforward maintenance.
  • Suitable for general cable, feeder and equipment protection.

Key Features

  • Mersen BS88 industrial fuse-link.
  • 40 A current rating.
  • 415 V AC rated voltage.
  • 250 V DC rated voltage.
  • General-purpose full-range protection characteristic.
  • BS Type A1 physical format.
  • Offset bolted tag terminal configuration.
  • Non-resettable, replaceable protective device.

Reliable Protection for Electrical Distribution Circuits

The Mersen BEIT42V40 protects electrical installations by interrupting the circuit when excessive current exceeds the fuse-link’s operating limits. This helps prevent overheating, insulation damage and severe mechanical stress within cables, terminals and distribution equipment.

Its gG full-range operating characteristic provides protection against sustained overloads as well as high-level short-circuit currents. During a severe fault, the fuse-link limits the magnitude and duration of the current allowed to pass, helping to minimise damage to downstream equipment.

Correct fuse selection is essential. Any replacement must match the required current rating, voltage rating, utilisation category, breaking capacity, dimensions and bolted-tag configuration specified for the installation.

Typical Applications

  • Industrial distribution boards.
  • Commercial electrical installations.
  • Cable and feeder protection.
  • Fuse-switch disconnectors.
  • Control panels and machinery.
  • Heating and lighting circuits.
  • Low-voltage switchgear assemblies.
  • General industrial equipment protection.

Technical Specifications

Tick the specs you need, then view products that match.

Fuse Class gG
Voltage 415 V
Item number B1019177
Catalogue No BEIT42V40
Description British Standard fuse-link IEC BS88 gG Type A1 415VAC 250VDC 40A BEIT Offset Tag
EAN/UPC Code 3605340515534
Rated voltage AC IEC 415 V
Rated voltage DC IEC 250 V
Ampere Rating 40 A
RoHS Compliant Yes
AC or DC AC/DC
Speed/Characteristic gG
Fuse Size A1
Mounting Bolted
Clearing I2t At Rated Voltage 4200 A²s
Melting I2t 1300 A²s
AC Max I.R./Breaking Capacity I1: 80 kA
Max. Rated Breaking Capacity DC 40 kA
Connection/Terminal Material Tin-Plated Copper
Connection/Terminal Type Offset Tag
Product Diameter 17.1 mm
Product Width 18.2 mm
Product Length 65.5 mm
Sell Pack Quantity 10 EA
Sell Pack Weight 0.315 kg
Sell Pack Width 80 mm
Sell Pack Length 90 mm
Sell Pack Height 40 mm
Product group Low Voltage IEC Fuses
Body/Insulating Material Ceramic
Product Weight 0.0315 kg
Power Dissipation at Rated Current Value 3 W
HS Code 85361050
Country of Manufacture India

Frequently Asked Questions

What is the Mersen BEIT42V40 used for?

The BEIT42V40 is used to protect compatible cables, feeders, switchgear and electrical equipment against overload and short-circuit currents.

What is the current rating of the BEIT42V40?

The Mersen BEIT42V40 has a rated current of 40 A.

What voltage is the BEIT42V40 rated for?

The fuse-link is rated for compatible circuits operating at up to 415 V AC or 250 V DC.

What type of terminals does the BEIT42V40 use?

The BEIT42V40 uses an offset bolted tag arrangement and has a BS Type A1 physical format.

Does the BEIT42V40 protect against overloads?

Yes. Its general-purpose full-range characteristic provides protection against both sustained overload and short-circuit currents when correctly selected for the circuit.

Can the BEIT42V40 be reset after it operates?

No. It is a non-resettable fuse-link and must be replaced with a correctly specified equivalent after the cause of the fault has been identified and rectified.

Trusted Industrial Circuit Protection

Mersen BS88 fuse-links are widely specified by electrical engineers, panel builders and maintenance professionals for dependable protection in industrial and commercial power distribution systems.