Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
High-performance BS88 gM Type B1 fuse-link rated at 690VAC and 460VDC with central bolted tag connections for robust installation and reliable circuit protection.
£19.27
The Mersen BTC69V63M80 is an industrial gM motor circuit fuse-link designed to provide dependable short-circuit protection for electric motors, motor starters and associated switchgear. Its motor-duty operating characteristic allows it to withstand normal motor starting currents while responding rapidly to high-level fault currents.
Designed for use in compatible BS-type bolted-tag fusegear, the BTC69V63M80 provides a secure electrical and mechanical connection within motor control centres, fuse-switch disconnectors and industrial control panels. Its current-limiting performance helps reduce the thermal and mechanical stress imposed on contactors, cables and other downstream equipment during a short circuit.
The 63M80 designation identifies a motor-rated fuse-link with an 80 A conventional current rating and a motor-circuit rating associated with 63 A applications. With a voltage rating of up to 690 V AC, it is suitable for demanding industrial motor installations. A correctly selected overload relay or motor protection device should be used alongside the fuse-link to provide protection against sustained overload conditions.
Electric motors can draw several times their normal full-load current while starting. The Mersen BTC69V63M80 is designed to tolerate this temporary inrush without unnecessary operation, while still interrupting severe short-circuit currents before they cause extensive damage to the motor circuit.
As a gM fuse-link, the BTC69V63M80 primarily provides short-circuit protection. Complete motor protection normally requires coordination with a thermal overload relay, electronic motor protection relay or another suitable overload device. Together, these components protect the motor, contactor, conductors and associated switching equipment against a broad range of electrical faults.
Tick the specs you need, then view products that match.
| Fuse Class | gM | |
|---|---|---|
| Voltage | 690 V | |
| Item number | B1006619 | |
| Catalogue No | BTC69V63M80 | |
| Description | British Standard fuse-link IEC BS88 gM Type B1 690VAC 460VDC 63M80A BTC Central Bolted Tag | |
| EAN/UPC Code | 3605340536829 | |
| Rated voltage AC IEC | 690 V | |
| Rated voltage DC IEC | 460 V | |
| In M Ich | 63M80 A | |
| RoHS Compliant | Yes | |
| AC or DC | AC/DC | |
| Speed/Characteristic | gM | |
| Fuse Size | B1 | |
| Mounting | Bolted | |
| Clearing I2t At Rated Voltage | 48500 A²s | |
| Melting I2t | 8500 A²s | |
| AC Max I.R./Breaking Capacity | I1: 80 kA | |
| Max. Rated Breaking Capacity DC | 40 kA | |
| Connection/Terminal Material | Tin-Plated Copper | |
| Connection/Terminal Type | Central Bolted Tag | |
| Product Diameter | 26.9 mm | |
| Product Length | 137 mm | |
| Sell Pack Quantity | 10 EA | |
| Sell Pack Weight | 1.245 kg | |
| Sell Pack Width | 145 mm | |
| Sell Pack Length | 145 mm | |
| Sell Pack Height | 60 mm | |
| Product group | Low Voltage IEC Fuses | |
| Body/Insulating Material | Ceramic | |
| Product Weight | 0.1245 kg | |
| Power Dissipation at Rated Current Value | 5.1 W | |
| HS Code | 85361050 | |
| Country of Manufacture | India |
The BTC69V63M80 is used to provide short-circuit protection for industrial motors, motor starters, contactors and associated electrical equipment.
The 63M80 designation identifies a gM motor-duty fuse-link with an 80 A conventional fuse current, designed to coordinate with motor circuits associated with a 63 A rating.
The fuse-link is designed for compatible motor circuits operating at up to 690 V AC.
The fuse-link primarily provides short-circuit protection. A correctly selected overload relay or motor protection device should be installed to protect against sustained motor overloads.
No. It is a non-resettable fuse-link and must be replaced with a correctly specified equivalent after the fault has been identified and rectified.
Mersen motor fuse-links are specified by electrical engineers, panel builders and maintenance professionals for dependable protection of industrial motors, starters and power distribution equipment.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.