Why Choose the MERSEN FUSE 600V 1/10A CC TD FUSE ATQR1/10?
£10.06
The Mersen ATQR1/10 is a 0.1 A Class CC time-delay fuse designed to provide reliable branch-circuit protection for industrial control systems, control transformers and other sensitive equipment subject to temporary inrush currents. Part of the Mersen Amp-Trap 2000® ATQR series, it combines current-limiting performance with a compact rejection-style cartridge design.
Rated at 600 V AC and 300 V DC, the ATQR1/10 is engineered to withstand brief, non-damaging current surges produced when transformers, solenoids, relays and similar inductive loads are energised. Its time-delay characteristic helps minimise nuisance fuse operation while providing dependable protection against sustained overloads and short-circuit faults.
The ATQR1/10 uses the standard Class CC rejection cartridge format, preventing installation in ordinary non-rejection fuse holders. When installed in a compatible Class CC fuse holder, it delivers compact, high-performance branch-circuit protection for industrial control panels, OEM machinery and automation systems.
The Mersen ATQR1/10 is specifically designed for low-current industrial control applications where transformers, relays and other inductive devices generate temporary inrush currents during energisation. Its time-delay characteristic allows these normal operating conditions while maintaining dependable protection against overloads and fault currents.
Its Class CC current-limiting construction rapidly interrupts high fault currents, helping protect wiring, terminals and sensitive electrical equipment. The rejection design also helps ensure only the correct Class CC fuse type can be installed.
Tick the specs you need, then view products that match.
| Current | 0.1 A | |
|---|---|---|
| Voltage | 600 V | |
| Device Type | Fuse link | |
| Fuse Class | Time delay | |
| Manufacturer | Mersen | |
| Series | Amp-Trap 2000® ATQR | |
| Model | ATQR1/10 | |
| Product type | Time-delay current-limiting cartridge fuse | |
| Fuse class | Class CC | |
| Rated current | 0.1 A | |
| Rated voltage | 600 V AC / 300 V DC | |
| Frequency | 50 / 60 Hz | |
| Interrupting rating | 200 kA RMS Symmetrical | |
| Operating characteristic | Time delay | |
| Body style | Cylindrical rejection cartridge | |
| Terminal type | Ferrule | |
| Mounting type | Compatible Class CC fuse holder or fuse block | |
| Application | Branch-circuit and control circuit protection | |
| HS Code | 85361010 | |
| Country of Manufacture | Mexico |
The ATQR1/10 protects sensitive industrial control circuits, control transformers, relays, solenoids and instrumentation equipment against overloads and short-circuit faults.
The Mersen ATQR1/10 has a rated current of 0.1 A.
The fuse is rated for 600 V AC and 300 V DC operation.
Yes. The ATQR1/10 is a Class CC time-delay current-limiting fuse with rejection-style dimensions for use in compatible Class CC fuse holders.
Time-delay operation allows temporary transformer and inductive load inrush currents without nuisance opening while continuing to provide reliable protection against sustained overloads and short-circuit faults.
Mersen Amp-Trap 2000® ATQR Class CC fuses are trusted by panel builders, OEM manufacturers and maintenance professionals for dependable branch-circuit protection in industrial control systems.