Mersen FR10GG50V4 10 × 38 mm gG cylindrical fuse-link rated at 4 A, 500 V AC and 250 V DC for overload and short-circuit protection.
£0.63
The Mersen FR10GG50V4 is a dependable 10 × 38 mm gG cylindrical fuse-link designed to protect low-voltage electrical distribution circuits, cables and industrial equipment against overload and short-circuit currents. As part of the established Mersen FR10 gG fuse range, it provides full-range protection for commercial and industrial electrical installations.
Its gG utilisation category enables the fuse to interrupt both sustained overload currents and high short-circuit currents. The ceramic body and silver-plated contacts provide reliable electrical conductivity, effective thermal resistance and consistent operation in demanding control panels, switchgear and machinery.
With a rated current of 4 A, a rated voltage of 500 V AC and an AC breaking capacity of 120 kA, the FR10GG50V4 offers effective protection for cables, conductors, control circuits and industrial equipment. Its compact cylindrical format allows straightforward installation in compatible 10 × 38 mm fuse holders.
The Mersen FR10GG50V4 protects cables, conductors and electrical equipment by limiting unacceptable overcurrents and rapidly interrupting short-circuit faults. Its gG time-current characteristic provides complete protection across the fuse's operating range, helping reduce equipment damage and electrical safety risks.
Its high breaking capacity makes it suitable for installations where significant prospective fault currents may occur. The compact 10 × 38 mm construction also makes the fuse well suited to space-conscious distribution boards, control panels and industrial machinery.
Tick the specs you need, then view products that match.
| Current | 4 A | |
|---|---|---|
| Voltage | 500 V | |
| Device Type | Fuse link | |
| Fuse Type | Cylindrical | |
| Fuse Size | 10x38 mm | |
| Fuse Class | gG | |
| Manufacturer | Mersen | |
| Series | FR10 gG | |
| Model | FR10GG50V4 | |
| Manufacturer item number | X213598 | |
| Product type | Cylindrical fuse-link | |
| Fuse utilisation category | gG / gL | |
| Rated current | 4 A | |
| Rated voltage AC | 500 V | |
| Rated voltage DC | 250 V | |
| Breaking capacity AC | 120 kA | |
| Breaking capacity DC | 100 kA | |
| Power dissipation | 0.85 W | |
| Fuse size | 10 × 38 mm | |
| Body material | Ceramic | |
| Contact finish | Silver-plated | |
| Mounting | Compatible 10 × 38 mm cylindrical fuse holder | |
| HS Code | 85361010 |
The FR10GG50V4 protects cables, conductors and electrical equipment against overload and short-circuit currents in low-voltage distribution systems.
The gG classification identifies a full-range general-purpose fuse that provides protection against both overload currents and short-circuit faults.
The Mersen FR10GG50V4 has a rated current of 4 A.
The FR10GG50V4 is rated for operation at up to 500 V AC and 250 V DC.
This fuse is designed for installation in a compatible 10 × 38 mm cylindrical fuse holder.
Mersen cylindrical gG fuse-links are trusted by electrical contractors, panel builders and industrial engineers for dependable overcurrent protection, high fault interruption capability and consistent long-term performance.