Mersen F075583 Limitor aSJB/D high-voltage motor back-up fuse rated at 3.6 kV AC and 350 A, with a 60 kA breaking capacity and integrated 20 N striker.
£810.86
The Mersen F075583, catalogue reference 45ASB36V350P-2, is a high-voltage back-up fuse-link designed specifically for the protection of medium-voltage motors, switchgear and controlgear. Part of the Mersen Limitor® aSJB/D series, it is engineered to interrupt damaging short-circuit currents while tolerating the repeated peak currents associated with motor starting.
Rated at 3.6 kV AC and 350 A, the F075583 provides dependable current-limiting protection for demanding industrial motor circuits. Its back-up operating characteristic makes it suitable for coordinated protection systems where overload protection is provided separately and the fuse is required to clear high-level faults rapidly.
The fuse-link features a robust melamine fibreglass insulating body, silver-plated copper fuse elements and silver-plated brass terminals. An integrated 20 N striker provides clear operation indication and can actuate compatible switchgear mechanisms following fuse operation.
Medium-voltage motors can draw substantial inrush currents during starting, so their protective fuse-links must tolerate repeated current peaks without unnecessary operation. The Mersen F075583 is designed for this purpose, providing a controlled motor protection characteristic while remaining capable of interrupting severe short-circuit currents.
Its current-limiting action helps reduce the peak fault current and associated let-through energy before they can damage motor windings, cables, contactors or switchgear. As a back-up fuse, the F075583 should be coordinated with suitable overload protection and selected according to the motor starting conditions, rated current and prospective fault level.
Tick the specs you need, then view products that match.
| Fuse Indication | Striker | |
|---|---|---|
| Device Type | Fuse link | |
| Fuse Type | High voltage | |
| Current | 350 A | |
| Voltage | 3600 V | |
| Manufacturer | Mersen | |
| Series | Limitor® aSJB/D | |
| Item number | F075583 | |
| Catalogue number | 45ASB36V350P-2 | |
| Product type | High-voltage motor back-up fuse-link | |
| Application | Medium-voltage motor protection | |
| Rated voltage | 3.6 kV AC | |
| Rated current | 350 A | |
| Maximum breaking capacity | 60 kA | |
| Minimum interrupting rating | 2,400 A | |
| Total clearing I²t | 1,700 kA²s | |
| Motor fuse coefficient K | 0.51 | |
| Power dissipation | 47 W at 0.7 × rated current | |
| Current type | AC | |
| Fuse operating class | Back-up | |
| Striker force | 20 N | |
| Indication system | Integrated striker | |
| Mounting method | Clip mounting | |
| Fuse size | Ø76 × 292 mm | |
| Product diameter | approximately 76 mm | |
| Overall product length | approximately 358 mm | |
| Terminal type | Cylindrical | |
| Terminal material | Silver-plated brass | |
| Fuse element material | Silver-plated copper | |
| Body material | Melamine fibreglass | |
| Product weight | approximately 3.3 kg | |
| EAN / UPC | 3605340010350 | |
| Product group | High-voltage IEC fuses | |
| Standards | IEC 60282-1, IEC 60644 and DIN 43625 | |
| RoHS compliant | Yes |
The Mersen F075583 is a high-voltage back-up fuse-link designed to protect medium-voltage motors, switchgear and controlgear against damaging short-circuit currents.
The fuse is rated at 3.6 kV AC with a nominal current rating of 350 A.
Yes. The Limitor® aSJB/D series is specifically designed to tolerate repeated peak currents produced during motor starting while still providing effective short-circuit protection.
The fuse has a maximum AC breaking capacity of 60 kA and a minimum interrupting rating of 2,400 A.
Yes. It includes an integrated 20 N striker for operation indication and actuation of compatible switchgear mechanisms.
No. It is a back-up fuse intended primarily to interrupt high short-circuit currents. Separate overload protection and correct coordination with the motor starter are required.
Mersen Limitor® motor fuse-links are widely used in industrial medium-voltage systems where reliable short-circuit interruption, motor-starting tolerance and robust construction are essential.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.